2. INSTALLATION AND WIRING
2.6 Control circuit
Output signal
*1
Terminal functions can be selected using
Pr.190 to Pr.195 (Output terminal function selection)
. (Refer to
Communication
2.6.2
Control logic (sink/source) change
Switch the control logic of input signals as necessary.
To change the control logic, change the jumper connector position on the control circuit board.
Connect the jumper connector to the connector pin of the desired control logic.
The control logic of input signals is initially set to the sink logic (SINK).
Type
Terminal
symbol
Terminal name
Terminal function description
Rated specification
Relay
A1,
B1,
C1
Relay output 1 (fault
output)
1 changeover contact output that indicates that the protective function
of the converter unit has been activated and the outputs are stopped.
Fault: discontinuity across B and C (continuity across A and C),
Normal: continuity across B and C (discontinuity across A and C)
Contact capacity: 230
VAC 0.3 A
(power factor = 0.4), 30
VDC 0.3 A
88R, 88S For manufacturer setting. Do not use.
Open collector
Inverter operation
enable (NO contact)
Switched to LOW when the converter unit operation is ready.
Connect this terminal to terminal MRS (X10) of the inverter.
The inverter can be started when the RDA status is LOW.
Permissible load: 24 VDC
(27 VDC at maximum) 0.1
A
(The voltage drop is 2.8 V
at maximum while the
signal is ON.)
The open collector
transistor is ON
(conductive) in LOW
state.
The transistor is OFF (not
conductive) in HIGH
state.
Inverter operation
enable (NC contact)
Switched to LOW when a converter unit fault occurs or the converter
is reset.
The inverter can be started when the RDB status is HIGH.
RSO
Inverter reset
Switched to LOW when the converter is reset (RES-ON).
Connect this terminal to terminal RES of the inverter.
The inverter is reset when it is connected with the RSO status LOW.
Instantaneous power
failure
Switched to LOW when an instantaneous power failure is detected.
FAN
Cooling fan fault
Switched to LOW when a cooling fan fault occurs.
SE
Open collector output
common
Common terminal for terminals RDA, RDB, RSO, IPF, FAN
—
Type
Terminal
symbol
Terminal name
Terminal function description
RS-485
—
PU connector
RS-485 communication can be made through the PU connector (For connection on a 1:1
basis only)
Conforming standard: EIA-485 (RS-485)
Transmission format: Multidrop link
Communication speed: 4800 to 115200 bps
Wiring length: 500 m
R
S
-485 ter
m
inals
TXD+
Converter unit
transmission terminal RS-485 communication can be made through the RS-485 terminals.
Conforming standard: EIA-485 (RS-485)
Transmission format: Multidrop link
Communication speed: 300 to 115200 bps
Overall length: 500 m
TXD-
RXD+
Converter unit
reception terminal
RXD-
GND
(SG)
Earthing (grounding)
CAUTION
• Do not use the empty terminals (NC) of the control circuit. Doing so may lead to damage of the converter unit and the
inverter.
• Always connect the terminal RDA of the converter unit and the terminal MRS (X10) of the inverter, and the terminal SE
of the converter unit and the terminal SD (terminal PC in the source logic) of the inverter. Not doing so may lead to
damage of the converter unit.
Содержание FR-CC2-N Series
Страница 61: ...60 3 PRECAUTIONS FOR USE OF THE CONVERTER UNIT 3 4 Checklist before starting operation MEMO ...
Страница 137: ...136 5 PARAMETERS 5 10 Checking parameters changed from their initial values initial value change list MEMO ...
Страница 153: ...152 6 PROTECTIVE FUNCTIONS 6 6 Check first when you have a trouble MEMO ...
Страница 165: ...164 7 PRECAUTIONS FOR MAINTENANCE AND INSPECTION 7 2 Measurement of main circuit voltages currents and powers MEMO ...
Страница 171: ...170 8 SPECIFICATIONS 8 3 Outline dimension drawings MEMO ...