(N) Operation via communication and its settings
Parameters
5 - 676
The setting is applied after an inverter reset or power-ON.
1432
N644
Ethernet communication
check time interval
9999
0
Ethernet communication is available, but the
inverter trips in the NET operation mode.
0.1 to 999.8 s
Set the interval of the communication check
(signal loss detection) time for all devices with IP
addresses in the range specified for Ethernet
command source selection (Pr. 1449 to Pr. 1454).
If a no-communication state persists for the
permissible time or longer, the inverter will trip.
9999
No communication check (signal loss detection)
1424
Ethernet communication
network number
1
1 to 120
Enter the network number.
1425
Ethernet communication
station number
1
1 to 120
Enter the station number.
1442
Ethernet IP filter address 1
0
0 to 255
Set the range of connectable IP addresses for the
network devices.
(When Pr. 1442 to Pr. 1445 = "0 (initial value)", the
function is invalid.)
1443
Ethernet IP filter address 2
0
0 to 255
1444
Ethernet IP filter address 3
0
0 to 255
1445
Ethernet IP filter address 4
0
0 to 255
1446
Ethernet IP filter address 2
range specification
9999
0 to 255, 9999
1447
Ethernet IP filter address 3
range specification
9999
0 to 255, 9999
1448
Ethernet IP filter address 4
range specification
9999
0 to 255, 9999
1449
Ethernet command source
selection IP address 1
0
0 to 255
To limit the network devices that send the
operation or speed command through the
Ethernet network (Modbus®/TCP or CCLink IE
Field Network Basic), set the range of IP addresses
of the devices. When Pr. 1449 to Pr. 1452 = "0
(initial value)", no IP address is specified for
sending commands through the Ethernet
network.
In this case, operation through the Ethernet
network (Modbus®/TCP or CC-Link IE Field
Network Basic) is not available. When four or
more clients attempt a connection to the inverter
during Modbus®/TCP communication, the
connection attempted from outside of the IP
address range set for Ethernet command source
selection may be forced to be closed.
1450
Ethernet command source
selection IP address 2
0
0 to 255
1451
Ethernet command source
selection IP address 3
0
0 to 255
1452
Ethernet command source
selection IP address 4
0
0 to 255
1453
Ethernet command source
selection IP address 3 range
specification
9999
0 to 255, 9999
1454
Ethernet command source
selection IP address 4 range
specification
9999
0 to 255, 9999
NOTE
The monitored items and parameter settings can be read during communication with the Pr.1432
Ethernet communication check time interval = "0" setting, but an inverter fault occurs instantly
when the operation mode is switched to the NET operation mode. When the NET operation mode
is selected as the start-up operation mode, communication is performed once, then an Ethernet
communication fault (E.EHR) occurs.
To perform operation or parameter writing via communication, set Pr.1432 to "9999" or a value
larger than the communication cycle or retry time setting (refer to page 5-682).
Pr.
Name
Initial
value
Setting range
Description
Содержание FR-A820-00046 (0.4K)
Страница 2: ......
Страница 4: ......
Страница 144: ...System configuration for Ethernet communication FR A800 E Installation and wiring 2 114 ...
Страница 202: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Страница 1090: ...Check first when you have a trouble Protective functions 6 50 ...
Страница 1110: ...Measurement of main circuit voltages currents and powers Precautions for maintenance and inspection 7 20 ...
Страница 1188: ...EC Declarations of Conformity Appendix A 48 A 7 EC Declarations of Conformity A 7 1 FR A820 FR A840 FR A842 series ...
Страница 1189: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Страница 1190: ...EC Declarations of Conformity Appendix A 50 ...
Страница 1191: ...Appendix EC Declarations of Conformity FR A800 A 51 ...
Страница 1192: ...EC Declarations of Conformity Appendix A 52 ...
Страница 1193: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Страница 1194: ...EC Declarations of Conformity Appendix A 54 ...
Страница 1195: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Страница 1196: ...EC Declarations of Conformity Appendix A 56 ...
Страница 1197: ...Appendix EC Declarations of Conformity FR A800 A 57 ...
Страница 1198: ...EC Declarations of Conformity Appendix A 58 ...
Страница 1199: ...Appendix EC Declarations of Conformity FR A800 A 59 ...
Страница 1200: ...EC Declarations of Conformity Appendix A 60 ...
Страница 1201: ...Appendix EC Declarations of Conformity FR A800 A 61 ...
Страница 1202: ...EC Declarations of Conformity Appendix A 62 ...
Страница 1203: ...Appendix EC Declarations of Conformity FR A800 A 63 ...
Страница 1204: ...EC Declarations of Conformity Appendix A 64 ...
Страница 1205: ...Appendix EC Declarations of Conformity FR A800 A 65 ...
Страница 1206: ...EC Declarations of Conformity Appendix A 66 ...
Страница 1207: ...Appendix EC Declarations of Conformity FR A800 A 67 ...
Страница 1208: ...EC Declarations of Conformity Appendix A 68 ...
Страница 1209: ...Appendix EC Declarations of Conformity FR A800 A 69 ...
Страница 1210: ...EC Declarations of Conformity Appendix A 70 ...
Страница 1211: ...Appendix EC Declarations of Conformity FR A800 A 71 ...
Страница 1212: ...EC Declarations of Conformity Appendix A 72 A 7 2 FR A846 series ...
Страница 1213: ...Appendix EC Declarations of Conformity FR A800 A 73 ...
Страница 1214: ...EC Declarations of Conformity Appendix A 74 ...
Страница 1215: ...Appendix EC Declarations of Conformity FR A800 A 75 ...
Страница 1216: ...EC Declarations of Conformity Appendix A 76 A 7 3 Frequency inverters with option unit FR A8NP ...
Страница 1217: ......