36
BASIC OPERATION
484
Fourth PID differential
time for values below
set point
0.01 to 10 s, 9999
9999
485
Integral control
activation
0 to 3
0
486
Deviation A
400.1 to 600%
600%
487
Deviation B
400 to 599.9%
400%
488
Deviation C1
400.1 to 599.9%,
9999
9999
489
Deviation C2
400.1 to 599.9%,
9999
9999
490
PID gain A
0.1 to 1000%,
9999
9999
491
PID gain B
0.1 to 1000%,
9999
9999
492
PID gain C1
0.1 to 1000%,
9999
9999
493
PID gain C2
0.1 to 1000%,
9999
9999
494
PID gain D
0.1 to 1000%,
9999
9999
495
Remote output
selection
0, 1, 10, 11
0
496
Remote output data 1 0 to 4095
0
497
Remote output data 2 0 to 4095
0
498
PLC function flash
memory clear
0, 9696
(0 to 9999)
0
502
Stop mode selection at
communication error
0 to 2, 11, 12
0
503
Maintenance timer 1
0 (1 to 9998)
0
504
Maintenance timer 1
warning output set
time
0 to 9998, 9999
9999
505
Speed setting
reference
1 to 590 Hz
60/50 Hz
*10
516
S-pattern time at a
start of acceleration
0.1 to 2.5 s
0.1 s
517
S-pattern time at a
completion of
acceleration
0.1 to 2.5 s
0.1 s
518
S-pattern time at a
start of deceleration
0.1 to 2.5 s
0.1 s
519
S-pattern time at a
completion of
deceleration
0.1 to 2.5 s
0.1 s
539
Modbus-RTU
communication check
time interval
0 to 999.8 s, 9999
9999
541
*19 Frequency command
sign selection
0, 1
0
544
*19 CC-Link extended
setting
0, 1, 12, 14, 18, 24,
28, 100, 112, 114,
118, 128
0
547
USB communication
station number
0 to 31
0
548
USB communication
check time interval
0 to 999.8 s, 9999
9999
Parameter Name
Setting range
Initial value
549
Protocol selection
0, 1
0
550
NET mode operation
command source
selection
0, 1, 5,
9999
*20
9999
551
PU mode operation
command source
selection
1 to 3, 5, 9999
*20
9999
552
Frequency jump range 0 to 30 Hz, 9999
9999
553
PID deviation limit
0.0 to 100.0%,
9999
9999
554
PID signal operation
selection
0 to 3
0
555
Current average time
0.1 to 1.0 s
1 s
556
Data output mask time 0 to 20 s
0 s
557
Current average value
monitor signal output
reference current
0 to 500 A
*2
Inverter
rated
current
0 to 3600 A
*3
560
Second frequency
search gain
0 to 32767, 9999
9999
561
PTC thermistor
protection level
0.5 to 30 k
,
9999
9999
563
Energization time
carrying-over times
(0 to 65535)
0
564
Operating time
carrying-over times
(0 to 65535)
0
565
Second motor
excitation current
break point
0 to 400 Hz, 9999
9999
566
Second motor
excitation current low-
speed scaling factor
0 to 300%
9999
569
Second motor speed
control gain
0 to 200%, 9999
9999
570
Multiple rating setting 0 to 3, 12
2
571
Holding time at a start 0.0 to 10.0 s, 9999
9999
573
4 mA input check
selection
1 to 3, 9999
9999
574
Second motor online
auto tuning
0, 1
0
598
Undervoltage level
175 to 215 V,
9999
*7
9999
350 to 430 V,
9999
*8
599
X10 terminal input
selection
0, 1
0
*14
1
*15
600
First free thermal
reduction frequency 1
0 to 590 Hz, 9999
9999
601
First free thermal
reduction ratio 1
1 to 100%
100%
602
First free thermal
reduction frequency 2 0 to 590 Hz, 9999
9999
603
First free thermal
reduction ratio 2
1 to 100%
100%
604
First free thermal
reduction frequency 3
0 to 590 Hz, 9999
9999
Parameter Name
Setting range
Initial value
*2
The setting range or initial value for FR-A820-03160(55K)-R2R or lower and FR-A840-01800(55K)-R2R or lower
*3
The setting range or initial value for FR-A820-03800(75K)-R2R or higher and FR-A840-02160(75K)-R2R or higher
*7
The value for the 200 V class.
*8
The value for the 400 V class.
*10
Differs according to types. (FM type/CA type)
*14
The initial value is for standard models.
*15
The initial value is for separated converter types.
*19
Available for the Ethernet models only,
*20
The setting value "5" is available for the Ethernet models only