OBJECT DICTIONARY
8
8.2.3 (Index 1002h) Manufacturer Status Register
<Detail>
Sub Index
Item
Description
00h
Name
Manufacturer Status Register
Data type
UNSIGNED32 (32 bit unsigned)
Default value
0 (Inverter alarm is not occurred.)
Access attribute
Read Only
Availability of mapping to PDO Enable
Bit
Description
REMARKS
0
Running (RUN signal)
0: Not running, 1: Running
Signals are not
affected by settings
of
Pr.190 to Pr.196
(output terminal
function selection).
1
During forward rotation
0: Not forward rotation, 1: Forward rotation
2
During reverse rotation
0: Not reverse rotation, 1: Reverse rotation
3
Up-to-running frequency (SU signal)
0: Not reached the running frequency,
1: Reached the running frequency
4
Overload (OL signal)
0: Not overloaded, 1: Overloaded
5
Instantaneous power failure (IPF signal)
0: Instantaneous power failure not
occurred,
1: Instantaneous power failure occurred
6
Frequency detection (FU signal)
0: Frequency detection not exercised,
1: Frequency detection exercised
7
Error
0: Inverter alarm not occurred,
1: Inverter alarm occurred
8 to 14
(Inhibited)
(Always 0)
15
Operation ready completion
0: Operation ready not completed,
1: Operation ready completed
16 to 31
(Inhibited)
(Always 0)