33
OCH439M
Mode
Cooling
(A35/W7)
Heating
(A7/W35)
Cooling
(A35/W7)
Heating
(A7/W35)
Cooling
(A35/W7)
Heating
(A7/W35)
Total
Capacity
W
12,500
14,000
10,000
11,200
12,500
14,000
Input
kW
4.80
3.32
3.60
2.53
5.00
3.29
Electrical circuit
Outdoor unit
PUHZ-HW140VHA/
PUHZ-HW140YHA
PUHZ-HW112YHA2
PUHZ-HW140VHA2/
PUHZ-HW140YHA2
Phase, Hz
1 / 3, 50
3, 50
1 / 3, 50
Voltage
V
230 / 400
400
230 / 400
Current
A
21.5 / 7.3
14.9 / 5.1
5.6
4.0
22.2 / 7.6
14.4 / 5.0
Refrigerant circuit
Discharge pressure
MPa
2.81
2.11
2.63
2.07
2.81
2.11
Suction pressure
MPa
0.78
0.66
0.78
0.69
0.78
0.66
Discharge temperature
ºC
84
67
78
64
84
67
Condensing temperature ºC
47
37
46
36
47
37
Suction temperature
ºC
11
3
9
5
11
3
W
ater
conditions
Flow volume
L/min
35.8
40.1
28.7
32.1
35.8
40.1
Outlet water temperature
ºC
7
35
7
35
7
35
Outdoor conditions
Intake air
temperature
D.B. ºC
35
7
35
7
35
7
W.B. ºC
24
6
24
6
24
6
The unit of pressure has been changed to MPa based on international SI system.
The conversion factor is: 1 (MPa) = 10.2 (kgf/cm
2
)