28
8-3. TEST POINT DIAGRAM
8-3-1. Indoor controller board
PCFY-P15NKMU-E.TH PCFY-P24NKMU-E.TH PCFY-P30NKMU-E.TH PCFY-P36NKMU-E.TH
PCFY-P15NKMU-ER1.TH PCFY-P24NKMU-ER1.TH PCFY-P30NKMU-ER1.TH PCFY-P36NKMU-ER1.TH
CN51
Centrally control
: Control signal
12VDC pulse input ( : +)
: Operation indicator
12VDC ( : +)
: Malfunction indicator
12VDC ( : +)
CN4Y
i-See sensor
CN2M
Connect to the terminal block (TB5)
(M-NET transmission connecting wire)
24-30VDC (non-polar)
CN3A
Connect to the terminal block (TB15)
(MA-Remote controller connecting wire)
- : 8.7-13V DC (Pin (+))
LED2
Power supply for
MA-Remote controller
CN32
Remote switch
SW4
Model selection
CN60
Linear expansion valve (LEV) output
12VDC pulse output
SW3
Function setting
SW2
Capacity setting
CN6Y
i-see sensor motor output
12VDC pulse output
CN44
Pipe temperature thermistor
: Liquid (TH22)
: Gas (TH23)
CN4F
Drain float switch (FS)
CN20
Room temperature
thermistor (TH21)
CN27
Damper signal output
12VDC( : +)
CN90
Connect to the wireless
remote controller board (W.B)
LED1
Main power supply
(Indoor unit : 208-230V)
CNMF
Connect to the
fan motor (MF)
: DC294~325V
: DC15V
: DC0~6V
: DC0 or DC15V (Stop)
DC7.5V (Operation)
(12VDC pulse)
CNP
Drain pump output (DP)
: 208-230VAC
FUSE
6.3A 250V
SWE
Test run(Drain pump)
Jumper wire J41, J42
Pair No.setting for wireless
remote controller
CND
Power supply for indoor controller board
- : 208-230VAC
CNV
Vane motor output
12VDC pulse
CN52
Remote indicator
1
-
2
: Status lamp 12VDC (
1
: +)
Fan motor output (SW1-5 OFF)
Thermostat ON (SW1-5 ON)
1
-
3
: Cooling/Dry status lamp
12VDC (
1
: +)
1
-
4
: Heating status lamp
12VDC (
1
: +)
CN24
External heater
12VDC (
1
: +)
OCH500A