- 10 -
(4) CMB-PW202V-J
Connection pipe of PWFY
(Gas)
Connection pipe of PWFY
(Liquid)
Connection pipe of indoor unit/PWFY
(Liquid)
Connection pipe of indoor unit/PWFY
(Gas)
Liquid lin
e
Indoor unit/PWFY (Cooling/Heating)
PWFY(Heating only)
Gas line
Liquid lin
e
Gas line
(Lifting bolt pitch)
(Lifting bolt pitch)
250
700
200
200
Access door 450
~P300: ø9.52<Brazed>(use attachment pipe) P301~P400: ø12.7<Brazed>(use attachment pipe) P401~: ø15.88<Brazed>
~P140: ø15.88<Brazed>(use attachment pipe) P141~P200: ø19.05<Brazed>(use attachment pipe) P201~P300: ø22.2<Brazed>(use attachment pipe) P301~: ø28.58<Brazed>(use attachment pipe)
~P140: ø15.88<Brazed>(use attachment pipe
)
P141~P200: ø19.05<Brazed> P201~P300: ø22.2<Brazed>(use attachment pipe)
~P300: ø9.52<Brazed>
Drain hose(Accessory)
Band(Accessory)
Connection pipe of outdoor unit (Low pressure)
Connection pipe of outdoor unit (High pressure)
12
14
30
ø
31
27
Y
X
Dtail of
Y
section
284
648
90
Drain piping VP-25 connection
Control box
200
255
Detail of X sectio
n
298
702
190
423
300
252
103
58
90
127
21
90
181
255
70
362
103
PUR
Y-P200: ø19.05<Brazed>(use attachment pipe)
PUR
Y-P250,P300: ø22.2<Brazed>
PUR
Y-P350: ø28.58<Brazed>(use attachment pipe)
PUR
Y-P200: ø15.88<Brazed>(use attachment pipe)
PUR
Y-P250,P300,P350: ø19.05<Brazed>
<Accessories> Refrigerant<Low pressure> conn. pipe Refrigerant<High pressure> conn. pipe Refrigerant<Gas> conn. pipe Refrigerant<Liquid> conn. pipe Drain hose(VP-25 connection) Hose band T
ie band
2pcs. 1pc. 6pcs. 2pcs. 1pc. 1pc. 1pc.
Note1. Suspension bolt (ø10), washer (M10), and nut (M10)
prepare in the field.
2.
Ta
ke notice of service space as follows
.
(Please give attention not to occupy service space by letting ducts and pipes through.)
3. Install this product in a location where noise (refrigerant noise)
emitted by the unit will not disturb the neighbors. (For use in quiet enviroments with low background noise, position the BC CONTROLLER at least 5m away from any indoor units.)
4. Install the unit horizontally
.
5.
The indoor unit/PWFY
branch is for cooling/heating.The indoor unit/PWF
Y
cannot be simultaneously operated in dif
ferent operation modes.
6.
The PWFY
unit branch is for the heating only
.
Service space
<Unit:mm>