- 6 -
*Other models of BC controllers are available. For unit information, refer to the Data Book.
(4) CMB-P104V-G1
Model
CMB-P104V-G1
Number of branch
4
Power source
1-phase 220/230/240V
50Hz
60Hz
Power input
(220/230/240)
Cooling
kW
0.067/0.076/0.085
0.054/0.061/0.067
Heating
0.030/0.034/0.038
0.024/0.027/0.030
Current
(220/230/240)
Cooling
A
0.31/0.34/0.36
0.25/0.27/0.28
Heating
0.14/0.15/0.16
0.11/0.12/0.13
External finish
Galvanized steel plate
(Lower part drain pan painting N1.5)
Connectable outdoor unit/heat source unit
PURY-(E)P200/250/300/350YLM-A(1)(-BS)
PQRY-P200/250/300YHM-A
Indoor unit capacity
connectable to 1 branch
Model P80 or smaller
( Use optional joint pipe combing 2 branches when the total unit capacity exceeds 81. )
External dimension H x W x D
mm (in.)
284 x 648 x 432 (11-3/16 x 25-17/32 x 17-1/32)
Refrigerant
piping
diameter
Connectable outdoor unit/heat source unit
capacity
To outdoor unit/heat source unit
High press. pipe
Low press. pipe
to P200
mm (in.) O.D.
15.88 (5/8)
Brazed
19.05 (3/4)
Brazed
P250/P300
mm (in.) O.D.
19.05 (3/4)
Brazed
22.2 (7/8)
Brazed
to P350
mm (in.) O.D.
19.05 (3/4)
Brazed
28.58 (1-1/8)
Brazed
To indoor unit
Liquid pipe
Gas pipe
mm (in.) O.D.
Indoor unit Model 50 or smaller 6.35 (1/4) Brazed
bigger than 50 9.52 (3/8) Brazed
(12.7 (1/2) with optional joint pipe used.)
Indoor unit Model 50 or smaller 12.7 (1/2) Brazed
bigger than 50 15.88 (5/8) Brazed
(19.05 (3/4) with optional joint pipe used.)
Field drain pipe size
mm (in.) O.D.
32 (1-1/4)
Net weight
kg (lbs)
24 (53)
Accessories
Drain Connection pipe (with flexible hose and insulation)
Reducer
Remark
Note: *1. Installation/foundation work, electrical connection work, insulation work, power source switch, and other items shall be referred to the Installation Manual.
*2. The equipment is for R410A refrigerant.
*3. Install this product in a location where noise (refrigerant noise) emitted by the unit will not disturb the neighbors.
(For use in quiet environments with low background noise, position the BC CONTROLLER at least 5m away from any indoor units.)
*4. Indoor units P100, P125, P140 can be connected to 1 branch. (In this case, cooling capacity decrease a little.)
*5. Refrigerant piping diameter for connection of plural indoor units with 1 branch shall be referred to the Installation Manual.
(5) CMB-PW202V-J
Model
Power source
Number of branch
Power input
Current
External finish
Connectable outdoor unit/heat source unit
Connectable unit capacity
External dimension H x W x D
Field drain pipe size
Net weight
Accessories
kW
A
Total
Indoor / PWFY
branch
PWFY branch
mm(in.)
mm(in.)
mm(in.)
mm(in.)
mm(in.)
kg(lbs)
Refrigerant
piping
diameter
To
outdoor unit
/heat source
unit
To
indoor/
PWFY unit
High press. pipe
Low press. pipe
Liquid pipe
Gas pipe
Note:
*1. For installation/foundation work, electrical connection work, insulation work, and power source switch etc., refer to the Installation Manual.
*2. The equipment is for R410A refrigerant.
*3. Install this product in a location where noise (refrigerant noise) emitted by the unit will not disturb the neighbors.
(For use in quiet environments with low background noise, position the Water system Connection Box at least 5m away from any indoor units.)
*4. Install the unit horizontally.
*5. The indoor / PWFY unit branch is for cooling / heating. The indoor / PWFY unit cannot be simultaneously operated in different operation modes.
*6. The PWFY unit branch is for the heating only.
*7. Seal the unused branch using the optional cover cap (CMY-S202-J).
PURY-(E)P200/250/300/350YLM-A(1)(-BS)
PQRY-P200/250/300YHM-A
Cooling : 0.019/0.020/0.021
Heating : 0.020/0.022/0.024
Cooling : 0.018/0.019/0.019
Heating : 0.019/0.020/0.021
Cooling : 0.09/0.09/0.09
Heating : 0.10/0.10/0.10
Cooling : 0.09/0.09/0.09
Heating : 0.09/0.09/0.09
Galvanized steel plate
(Lower part drain pan painting N1.5)
CMB-PW202V-J
1N ~ 220/230/240V
50Hz
60Hz
20 (45)
2
O.D. 32mm (1-1/4" )
284 x 648 x 432 (11-3/16" x 25-9/16" x 17-1/16" )
50% ~ 130% of outdoor unit/heat source unit
up to 130% of outdoor unit/heat source unit
up to 100% of outdoor unit/heat source unit
Total down-stream Indoor unit capacity
Connectable outdoor unit capacity
ø19.05 (ø3/4" ) Brazed
·Drain Connection pipe (with flexible hose and insulation)
·Refrigerant connection pipe
P200
ø15.88 (ø5/8" ) Brazed
ø15.88 (ø5/8" )
Brazed
~P140
ø9.52 (ø3/8" )
Brazed
ø19.05 (ø3/4" )
Brazed
P141~P200
ø9.52 (ø3/8" )
Brazed
ø22.2 (ø7/8" )
Brazed
P201~P300
ø9.52 (ø3/8" )
Brazed
ø28.58 (ø1-1/8" )
Brazed
P301~P400
ø12.70 (ø1/2" )
Brazed
ø28.58 (ø1-1/8" )
Brazed
P401~
ø15.88 (ø5/8" )
Brazed
ø22.2 (ø7/8" ) Brazed
P250/P300
ø19.05 (ø3/4" ) Brazed
ø28.58 (ø1-1/8" ) Brazed
P350
ø19.05 (ø3/4" ) Brazed