[
VIII
Troubleshooting ]
- 30 -
HWE1405A
GB
2. Capacity
code
setting
(1) SW2
1) Indoor control board
Dipswitch settings must be made while the unit is stopped.
Factory setting
The switches are set to correspond to the unit capacity.
3. Model
setting
(1) SW4
1) Indoor control board
Dipswitch settings must be made while the unit is stopped.
Note:
Changes made to the dipswitches SW1, SW2, and SW3 will become effective when the unit comes to a stop (remote controller
off). There is no need to power cycle the unit.
4. Power
voltage
setting
(1) SW5
1) Indoor control board
Dipswitch settings must be operated with the main power turned OFF.
Factory setting
Factory setting
Set SW5 to 240V side when the power supply is 230 volts.
When the power supply is 208 volts, set SW5 to 220V side.
PVFY-P12NAMU-E
PVFY-P18NAMU-E
PVFY-P24NAMU-E
PVFY-P30NAMU-E
PVFY-P36NAMU-E
PVFY-P48NAMU-E
PVFY-P54NAMU-E
220V
(208V)
240V
(230V)
Содержание CITY MULTI PVFY-P12NAMU-E
Страница 1: ......
Страница 5: ...iv HWE1405A GB ...
Страница 7: ...HWE1405A GB ...
Страница 44: ......