1.4. Before installation (relocation) - electri-

cal work

 Caution:

Ground the unit.

- Do not connect the ground wire to gas or water pipes, lightning rods, or

telephone ground lines. Improper grounding may result in electric shock.

Install the power cable so that tension is not applied to the cable.

- Tension may cause the cable to break and generate heat and cause a fire.

Install a leak circuit breaker, as required.

- If a leak circuit breaker is not installed, electric shock may result.

Use power line cables of sufficient current carrying capacity and rating.

- Cables that are too small may leak, generate heat, and cause a fire.

Use only a circuit breaker and fuse of the specified capacity.

- A fuse or circuit breaker of a larger capacity, or the use of a substitute simple

steel or copper wire may result in a general unit failure or fire.

Do not wash the air conditioner units.

- Washing them may cause an electric shock.

Be careful that the installation base is not damaged by long use.

- If the damage is left uncorrected, the unit may fall and cause personal injury

or property damage.

Install the drain piping according to this Installation Manual to ensure
proper drainage. Wrap thermal insulation around the pipes to prevent
condensation.

- Improper drain piping may cause water leakage causing damage to furniture

and other possessions.

Be very careful about transporting the product.

- One person should not carry the product. Its weight is in excess of 20 kg

[45LBS].

- Some products use PP bands for packaging. Do not use any PP bands as a

means of transportation. It is dangerous.

- Do not touch the heat exchanger fins. Doing so may cut your fingers.
- When transporting the outdoor unit, support it at the specified positions on

the unit base. Also support the outdoor unit at four points so that it cannot
slip sideways.

Safely dispose of the packing materials.

- Packing materials, such as nails and other metal or wooden parts, may cause

stabs or other injuries.

- Tear apart and throw away plastic packaging bags so that children will not

play with them. If children play with a plastic bag which has not been torn
apart, they face the risk of suffocation.

1.5. Before starting the test run

 Caution:

Turn on the power at least 12 hours before starting operation.

- Starting operation immediately after turning on the main power switch can

result in irreversible damage to internal parts. Keep the power switch turned
on during the operational season. Make sure of the phase order of power
supply and voltage between each phase.

Do not touch the switches with wet fingers.

- Touching a switch with wet fingers can result in an electric shock.

Do not touch the refrigerant pipes during and immediately after opera-
tion.

- During and immediately after operation, the refrigerant pipes may be hot or

cold, depending on the condition of the refrigerant flowing through the refrig-
erant piping, compressor, and other refrigerant cycle parts. Your hands may
suffer burns or frostbite if you touch the refrigerant pipes.

Do not operate the air conditioner with the panels and guards removed.

- Rotating, hot, or high-voltage parts can cause injuries.

Do not turn off the power immediately after stopping operation.

- Always wait at least 5 minutes before turning off the power. Otherwise,

drainage water leakage or mechanical failure of sensitive parts may occur.

Do not touch the surface of the compressor during servicing.

- If the unit is connected to a supply and not running, the crank case heater

located at the base of the compressor may still be operating.

1.2. Precautions for devices that use R410A

refrigerant

 Caution:

Do not use existing refrigerant piping.

- The old refrigerant and refrigerant oil in the existing piping contains a large

amount of chlorine which may cause the refrigerant oil of the new unit to
deteriorate.

- R410A is a high-pressure refrigerant and can cause the existing piping to

burst.

Use refrigerant piping made of phosphorus deoxidized copper and cop-
per alloy seamless pipes and tubes. In addition, be sure that the inner
and outer surfaces of the pipes are clean and free of hazardous sulphur,
oxides, dust/dirt, shaving particles, oils, moisture, or any other contami-
nant.

- Contaminants on the inside of the refrigerant piping may cause the refriger-

ant oil to deteriorate.

Store the piping to be used during installation indoors and keep both
ends of the piping sealed until just before brazing. (Store elbows and
other joints in a plastic bag.)

- If dust, dirt, or water enters the refrigerant cycle, deterioration of the oil and

compressor failure may result.

Apply only a small amount of ester oil, ether oil, or alkyl benzene to flare
connections (for indoor unit).

- Infiltration of a large amount of mineral oil may cause the refrigerant oil to

deteriorate.

Use liquid refrigerant to fill the system.

- If gas refrigerant is used to fill the system, the composition of the refrigerant

in the cylinder will change and performance may drop.

Do not use a refrigerant other than R410A.

- If another refrigerant (R22, etc.) is mixed with R410A, the chlorine in the

refrigerant may cause the refrigerant oil to deteriorate.

Use a vacuum pump with a reverse flow check valve.

- The vacuum pump oil may flow back into the refrigerant cycle and cause the

refrigerant oil to deteriorate.

Do not use the following tools that are used with conventional refriger-
ants.
(Gauge manifold, charge hose, gas leak detector, reverse flow check valve,
refrigerant charge base, refrigerant recovery equipment)

- If the conventional refrigerant and refrigerant oil are mixed in the R410A, the

refrigerant may deteriorate.

- If water is mixed in the R410A, the refrigerant oil may deteriorate.
- Since R410A does not contain any chlorine, gas leak detectors for conven-

tional refrigerants will not react to it.

Do not use a charging cylinder.

- Using a charging cylinder may cause the refrigerant to deteriorate.

Be especially careful when managing the tools.

- If dust, dirt, or water gets into the refrigerant cycle, the refrigerant may dete-

riorate.

1.3. Before installation

 Caution:

Do not install the unit where combustible gas may leak.

- If the gas leaks and accumulates around the unit, an explosion may result.

Do not use the air conditioner where food, pets, plants, precision instru-
ments, or artwork are kept.

- The quality of the food, etc. may deteriorate.

Do not use the air conditioner in special environments.

- Oil, steam, sulfuric smoke, etc. can significantly reduce the performance of

the air conditioner or damage its parts.

When installing the unit in a hospital, communication station, or similar
place,  provide sufficient protection against noise.

- Inverter equipment, private power generator, high-frequency medical equip-

ment, or radio communication equipment may cause the air conditioner to
operate erroneously, or fail to operate. On the other hand, the air conditioner
may affect such equipment by creating noise that disturbs medical treatment
or image broadcasting.

Do not install the unit on or over things that are subject to water damage.

- When the room humidity exceeds 80% or when the drain pipe is clogged,

condensation may drip from the indoor unit. Perform collective drainage work
together with the outdoor unit, as required.

2. About the product

This unit uses R410A-type refrigerant

Piping for systems using R410A may be different from that for systems using
conventional refrigerant because the design pressure in systems using R410A
is higher. Refer to the Data Book for more information.

Some of the tools and equipment used for installation with systems that use
other types of refrigerant cannot be used with the systems using R410A. Refer
to the Data Book for more information.

Do not use the existing piping, as it contains chlorine, which is found in con-
ventional refrigerating machine oil and refrigerant. This chlorine will deteriorate
the refrigerant machine oil in the new equipment. The existing piping must not
be used as the design pressure in systems using R410A is higher than that in
the systems using other types of refrigerant and the existing pipes may burst.

Содержание City Multi PUHY-P-THMU-A

Страница 1: ...ATION MANUAL For safe and correct use please read this installation manual thoroughly before installing the air conditioner unit MANUEL D INSTALLATION Veuillez lire le manuel d installation en entier avant d installer ce climatiseur pour éviter tout accident et vous assurer d une utilisation correcte For use with R410A ...

Страница 2: ...and fire may result Securely install the outdoor unit terminal cover panel If the terminal cover panel is not installed properly dust or water may enter the outdoor unit and fire or electric shock may result When installing and moving the air conditioner to another site do not charge it with a refrigerant different from the refrigerant specified on the unit If a different refrigerant or air is mix...

Страница 3: ...ping made of phosphorus deoxidized copper and cop per alloy seamless pipes and tubes In addition be sure that the inner and outer surfaces of the pipes are clean and free of hazardous sulphur oxides dust dirt shaving particles oils moisture or any other contami nant Contaminants on the inside of the refrigerant piping may cause the refriger ant oil to deteriorate Store the piping to be used during...

Страница 4: ... P120YHMU A BS PUHY P120YHMU A BS PUHY P120YHMU A BS PUHY P120YHMU A BS PUHY P120YHMU A BS PUHY P120YHMU A BS PUHY P120YHMU A BS PUHY P72YHMU A BS PUHY P72YHMU A BS PUHY P72YHMU A BS PUHY P96YHMU A BS PUHY P120YHMU A BS PUHY P144 to P360YSHMU A BS require Twinning Kit to connect component unit modules in the field 5 Parts included list Unit mm in 1 The total indoor capacity of units run simultaneo...

Страница 5: ... Up to the unit height Back Up to 500mm 19 11 16 in from the unit bottom Side Up to the unit height 4 If there are obstacles at the upper part of the unit C When there is little space up to an obstruction Unit mm in 240 9 15 32 1 31 32 39 3 8 45 A D C 50 1000 A Front B Unit height C Back D Air outlet guide field supplied Unit mm in 30 450 300 C B B C A 11 13 16 17 23 32 1 3 16 100 450 100 B B C C ...

Страница 6: ...ecessary so that it does not move to the side and support it at 4 points If the unit is installed or suspended with 3 point support the unit may become unstable and fall 8m 26ft 8m 26ft 40 Fix unit tightly with bolts so that unit will not fall down due to earthquakes or strong winds Use concrete base or an angle bracket as the foundation of unit Vibration may be transmitted to the installation sec...

Страница 7: ...led information on refrigerant piping system 2 Always observe the restrictions on the refrigerant piping such as rated length height difference and piping diameter to prevent equipment failure or a de cline in heating cooling performance 3 Branching cannot be made after header branching corresponding parts are marked with in the diagram below To the outdoor unit To the outdoor unit CAP 4 Do not in...

Страница 8: ...ne in conventional refrigerant and refrigerant oil in the existing piping will cause the new refrigerant to deteriorate Store the piping to be used during installation indoors and keep both ends of the piping sealed until just before brazing If dust dirt or water gets into the refrigerant cycle the oil will deteriorate and the compressor may fail Do not use a charging cylinder Using a charging cyl...

Страница 9: ... 4 ø22 2 7 8 ø22 2 7 8 Liquid pipe ø19 05 3 4 ø19 05 3 4 ø19 05 3 4 ø19 05 3 4 ø19 05 3 4 Gas pipe ø34 93 1 3 8 ø34 93 1 3 8 ø34 93 1 3 8 ø34 93 1 3 8 ø34 93 1 3 8 A2 3 A3 3 1 ø12 7 for over 90m 295 ft 2 ø12 7 for over 40m 131 ft 3 The pipe sizes listed in columns A1 to A3 in this table correspond to the sizes for the models listed in the unit 1 2 and 3 columns When the order of the models for uni...

Страница 10: ...frigerant line Use the table below as a guide for calculating the amount of additional charg ing and then charge the system accordingly If the calculation results in a fraction of less than 0 1 kg 4 oz round up to the next 0 1 kg 4 oz For example if the result of the calculation was 11 38 kg 402 oz round the result up to 11 4 kg 404 oz Additional Charge Additional refrigerant charge kg oz 10 Addit...

Страница 11: ...r completing the operation D Pinched connecting pipe severing portion E Pinched connecting pipe brazing portion Refrigerant piping connection examples Fig 10 2 2 A Front pipe routing B Bottom pipe routing C Included with outdoor unit A Gas pipe field supply required B Liquid pipe field supply required C Shape Warning The section of the pipe on the unit between the two refrigerant service valves is...

Страница 12: ...rigerant charge by using the formula and charge refrigerant additionally through the service port after completing piping connection work After completing work tighten the service port and cap securely so as not to generate any gas leakage Refer to the table on the below for appropriate tightening torque Restriction If a flammable gas or air oxygen is used as the pressurization gas it may catch fi...

Страница 13: ... Pay special attention to insulation work in the ceiling plenum Fig 10 4 1 C A B D E A Steel wire B Piping C Oily mastic asphalt or asphalt D Heat insulation material A E Outer covering B Note When using polyethylene cover as covering material asphalt roofing shall not be required No heat insulation must be provided for electric wires Fig 10 4 2 B A D C E E E D A B A Liquid pipe B Gas pipe C Elect...

Страница 14: ...nection does not allow the system to operate 8 When connecting a System Controller to outdoor units or performing a group operation of indoor units that are connected to different outdoor units a transmission line for centralized control is required When using a transmission line for centralized control connect the transmission line non polar 2 core wire to all TB7 terminals between all outdoor un...

Страница 15: ...a possibility of small animal s entering the unit 11 3 Wiring transmission cables 1 Types of control cables 1 Wiring transmission cables Types of transmission cables Shielding wire CVVS CPEVS or MVVS Cable diameter More than 1 25 mm2 AWG 16 Maximum wiring length Within 200 m 656 ft Maximum length of transmission lines for centralized control and indoor outdoor transmission lines Maximum length via...

Страница 16: ... CN40 2 If a system controller is used set SW2 1 on all of the outdoor units to ON Fig 11 3 2 MA Remote Controller 1 When the power supply unit is not connected to the transmission line for centralized control disconnect the male power supply connector CN41 from ONE outdoor unit in the system and connect it to CN40 2 If a system controller is used set SW2 1 on all of the outdoor units to ON A Chan...

Страница 17: ...or more Max transmission cable length M NET cable L1 and L3 L4 and L6 and L2 L6 200 m 656 ft 1 25 mm2 AWG 16 or more Remote controller cable length c1 c2 and c1 c2 c3 c4 200 m 656 ft 0 3 to 1 25 mm2 AWG 22 to 16 3 Transmission booster Fig 11 3 3 Max transmission cable length M NET cable 1 L1 L2 L3 L5 L6 200 m 656 ft 1 25 mm2 AWG 16 2 L1 L2 L3 L5 L7 200 m 656 ft 1 25 mm2 AWG 16 3 L1 L2 L4 200 m 656...

Страница 18: ...A or 100 mA 0 1 sec or less 30 A 30 mA or 100 mA 0 1 sec or less 40 A 30 mA or 100 mA 0 1 sec or less 30 A 30 mA or 100 mA 0 1 sec or less 50 A 100 mA 0 1 sec or less 30 A 30 mA or 100 mA 0 1 sec or less 50 A 100 mA 0 1 sec or less 40 A 30 mA or 100 mA 0 1 sec or less 50 A 100 mA 0 1 sec or less 50 A 100 mA 0 1 sec or less 50 A 100 mA 0 1 sec or less 30 A 30 mA or 100 mA 0 1 sec or less 30 A 30 mA...

Страница 19: ...4YSHMU A BS PUHY P72YHMU A BS PUHY P72YHMU A BS PUHY P120YHMU A BS PUHY P288YSHMU A BS PUHY P96YHMU A BS PUHY P72YHMU A BS PUHY P120YHMU A BS PUHY P312YSHMU A BS PUHY P120YHMU A BS PUHY P72YHMU A BS PUHY P120YHMU A BS PUHY P336YSHMU A BS PUHY P120YHMU A BS PUHY P96YHMU A BS PUHY P120YHMU A BS PUHY P360YSHMU A BS PUHY P120YHMU A BS PUHY P120YHMU A BS Indoor unit 15 A 30 mA or 100 mA 0 1 sec or less...

Страница 20: ...of the refrigerant circuit operating properly Unstable flow of the refrigerant emits a sound This is temporary and does not imply a problem The LEV is slightly open for preventing any refrigerant inside of the indoor unit that is not performing the heating operation from being liquefied This does not imply a problem 13 Rating plate information Model PUHY P72THMU A BS PUHY P96THMU A BS PUHY P120THM...

Страница 21: ...0A 11 5 kg 25 LBS 6 oz 9 0 kg 19 LBS 13 oz 11 5 kg 25 LBS 6 oz 9 0 kg 19 LBS 13 oz 11 5 kg 25 LBS 6 oz 11 5 kg 25 LBS 6 oz Allowable pressure Ps 4 15 MPa 601 psi LP 2 21 MPa 320 psi Net weight 260 kg 573 LBS 5 oz 215 kg 473 LBS 16 oz 260 kg 573 LBS 5 oz 215 kg 473 LBS 16 oz 260 kg 573 LBS 5 oz 260 kg 573 LBS 5 oz Model PUHY P264YSHMU A BS PUHY P288YSHMU A BS Unit combination PUHY P120YHMU A BS PUH...

Страница 22: ...panneau n est pas installé correctement la poussière ou l eau peut pénétrer dans l unité extérieure et un incendie ou un choc électrique peut en résulter En installant et en déplaçant le climatiseur vers un autre site ne le chargez pas avec un frigorigène différent de celui qui est spéci é sur l unité Si un autre frigorigène ou de l air est mélangé au frigorigène original le cycle frigori que peut...

Страница 23: ...ez vous que les surfaces intérieures et extérieures des tuyaux sont propres et dépourvues de soufre d oxydes de poussières saletés de particules de rasage d huile d humidité ou de n importe quel autre contaminant dangereux Les contaminants à l intérieur de la tuyauterie du frigorigène peuvent détériorer l huile du frigorigène Entreposez à l intérieur la tuyauterie à utiliser pour l installation et...

Страница 24: ... P192TSHMU A BS PUHY P216TSHMU A BS PUHY P240TSHMU A BS PUHY P72YHMU A BS PUHY P96YHMU A BS PUHY P120YHMU A BS PUHY P144YSHMU A BS PUHY P168YSHMU A BS PUHY P192YSHMU A BS PUHY P216YSHMU A BS PUHY P240YSHMU A BS Niveau de bruit 60 Hz 58dB A 58dB A 60dB A 61dB A 61dB A 62 5dB A 62 5dB A 63dB A Pression statique externe 0 Pa 2 Unités d intérieur Capacité totale 50 130 1 Modèle 06 96 Quantité 1 15 1 2...

Страница 25: ...vant Jusqu à la hauteur de l appareil Dos Jusqu à 500 mm 19 11 16 in du fond de l appareil Côté Jusqu à la hauteur de l appareil 4 S il y a des obstacles à la partie supérieure de l unité C Quand il y a peu d espace jusqu à une obstruction Unité mm in 240 9 15 32 1 31 32 39 3 8 45 50 1000 A Avant B Hauteur de l unité C Dos D Guide de sortie d air fourni sur le terrain 2 En cas d installation colle...

Страница 26: ...vents forts Utilisez du support en béton ou une cornière d assemblage comme fondation de l unité Des vibrations peuvent être transmises à la section d installation et bruit et vibration peuvent être produits par le plancher et les murs selon les conditions d installation Fournissez par conséquent une protection suf sante contre les vibrations coussinets cadre de coussin etc Construisez les fondati...

Страница 27: ...connectée qu un essai d étanchéité du frigorigène ait été exécuté et que le processus d évacuation ait été complété c N utilisez jamais de frigorigène pour exécuter une purge d air Servez vous toujours d une pompe à vide pour évacuer d Soyez sûr de charger le système avec un frigorigène liquide e Un manque ou un excès de frigorigène provoque un arrêt d urgence de l unité Chargez le système d une q...

Страница 28: ... de récupération du frigorigène Le mélange de frigorigène conventionnel et d huile réfrigérant peut détériorer l huile réfrigérante Le mélange d eau détériore l huile réfrigérante Le frigorigène R410A ne contient aucun chlore Par conséquent les détecteurs de fuite de gaz pour les frigorigènes conventionnels ne réagissent pas Gérez les outils utilisés pour le R410A plus soigneusement que d habitude...

Страница 29: ...s dans les colonnes 1 2 et 3 Lorsque l ordre des modèles change veillez à utiliser la taille de tuyau appropriée B C D Unité mm in Capacité totale d unités d intérieur Tube de uide Tube de gaz Total de modèle d unité en aval Joint 54 ø9 52 3 8 ø15 88 5 8 72 CMY Y102S G2 55 72 ø9 52 3 8 ø19 05 3 4 73 144 CMY Y102S L2 73 108 ø9 52 3 8 ø22 2 7 8 145 240 CMY Y202 G2 109 144 ø12 7 1 2 ø28 58 1 1 8 La 1...

Страница 30: ...m ft 3 1 oz ft m 0 2 kg m ft 2 15 oz ft m 0 12 kg m ft 1 29 oz ft Taille de tube de uide Longueur totale de ø9 52 mm 3 8 in Taille de tube de uide Longueur totale de ø6 35 mm 1 4 in D m 0 06 kg m ft 0 65 oz ft m 0 024 kg m ft 0 26 oz ft Exemple Intérieur 1 48 A ø12 7 mm 1 2 in 40 m 131 ft a ø9 52 mm 3 8 in 10 m 32 ft 2 36 B ø9 52 mm 3 8 in 10 m 32 ft b ø9 52 mm 3 8 in 5 m 16 ft 3 15 C ø9 52 mm 3 8...

Страница 31: ...alves haute et basse pression pour empêcher la fuite de gaz Prenez les mesures suivantes 1 à 4 pour retirer le tube de connexion rétréci avant de connecter les tubes de frigorigène à l unité extérieure 1 Véri ez que la valve de frigorigène est complètement fermée tournée à fond dans le sens horaire 2 Branchez un tube de remplissage au port de service sur la valve basse pression haute pression et e...

Страница 32: ...rès le test d herméticité éliminez l agent de barbotage Si un gaz in ammable ou l air oxygène est utilisé comme gaz de pressurisation il peut s en ammer ou exploser 2 Pressurisation avec un gaz réfrigérant et de l azote 1 Après une première pressurisation du frigorigène liquide R410A en gaz de pression d environ 0 2 MPa 29 psi pressurisez à la pression nominale de 4 15 MPa 602 psi avec de l azote ...

Страница 33: ...u pourrait avoir pénétré Appliquez une pression d azote sec jusqu à 0 05 MPa 7 25 psi et appliquez de nouveau le vide Pour nir scellez avec le frigorigène liquide à travers le tube de uide et ajustez la tuyauterie de gaz pour obtenir une quantité appropriée de frigorigène pendant le fonctionnement N exécutez jamais de purge d air à l aide du frigorigène Remarque Ajoutez toujours une quantité appro...

Страница 34: ...et emplacement pour le raccordement des câbles 1 Unité extérieure 1 Retirez le panneau avant du boîtier de commande en retirant les 4 vis et en le poussant légèrement vers le haut avant de le sortir 2 Connectez la ligne de transmission intérieur extérieur au bloc de jonction TB3 Si plusieurs appareils extérieurs sont connectés au sein du même système frigori que connectez en série TB3 borne M1 M2 ...

Страница 35: ...ieur longueur maximale par l intermédiaire des unités extérieures 500 m 1 640 ft maximum La longueur maximale du câblage entre le bloc d alimentation pour des lignes de transmission sur les lignes de transmission pour la commande centralisée et chaque appareil extérieur et contrôleur de système est de 200 m 656 ft 2 Câbles de la télécommande Télécommande M NET Type de câble de télécommande Câble e...

Страница 36: ... un contrôleur de système est utilisé réglez SW2 1 sur tous les appareils extérieurs sur ON marche Fig 11 3 2 Télécommande MA A Changez le cavalier de CN41 à CN40 1 B SW2 1 ON marche 2 C Laissez le cavalier sur CN41 B SW2 1 ON marche 2 1 Quand l alimentation n est pas connectée à la ligne de transmission pour la commande centralisée débranchez le connecteur mâle de l alimentation CN41 sur UN appar...

Страница 37: ... principale au sein du même groupe plus 100 M NET R C secondaire 151 à 200 Réglez sur une adresse IC principale au sein du même groupe plus 150 MA R C Dé nition inutile d adresse dé nition principale secondaire nécessaire 1 OC OS1 et OS2 des appareils extérieurs dans le même système frigori que sont automatiquement identi és Ils sont identi és comme OC OS1 et OS2 dans l ordre décroissant de capaci...

Страница 38: ...HMU A BS PUHY P120THMU A BS 13 3 6 13 3 6 50 50 50 50 A 100 mA 0 1 sec ou moins 43 6 PUHY P96THMU A BS 13 3 6 13 3 6 40 40 40 40 A 30 mA ou 100 mA 0 1 sec ou moins 36 3 PUHY P240TSHMU A BS PUHY P120THMU A BS 13 3 6 13 3 6 50 50 50 50 A 100 mA 0 1 sec ou moins 43 6 PUHY P120THMU A BS 13 3 6 13 3 6 50 50 50 50 A 100 mA 0 1 sec ou moins 43 6 PUHY P264TSHMU A BS PUHY P120THMU A BS 13 3 6 13 3 6 50 50 ...

Страница 39: ...P336YSHMU A BS PUHY P120YHMU A BS 5 3 10 5 3 10 25 25 25 25 A 30 mA ou 100 mA 0 1 sec ou moins 19 6 PUHY P120YHMU A BS 5 3 10 5 3 10 25 25 25 25 A 30 mA ou 100 mA 0 1 sec ou moins 19 6 PUHY P96YHMU A BS 3 3 12 3 3 12 20 20 20 20 A 30 mA ou 100 mA 0 1 sec ou moins 16 4 PUHY P360YSHMU A BS PUHY P120YHMU A BS 5 3 10 5 3 10 25 25 25 25 A 30 mA ou 100 mA 0 1 sec ou moins 19 6 PUHY P120YHMU A BS 5 3 10 ...

Страница 40: ...dique que le circuit du frigorigène fonctionnement correctement Immédiatement après la mise en route l unité intérieure émet le bruit de l écoulement du frigorigène Af chage normal L écoulement instable du frigorigène émet un bruit Ceci est provisoire et n indique pas un problème De l air chaud provient d une unité intérieure qui n exécute pas de chauffage Af chage normal Le LEV est légèrement ouv...

Страница 41: ...UHY P264YSHMU A BS PUHY P288YSHMU A BS Unité combinée PUHY P120YHMU A BS PUHY P72YHMU A BS PUHY P72YHMU A BS PUHY P120YHMU A BS PUHY P96YHMU A BS PUHY P72YHMU A BS Frigorigène R410A 11 5 kg 25 LBS 6 oz 9 0 kg 19 LBS 13 oz 9 0 kg 19 LBS 13 oz 11 5 kg 25 LBS 6 oz 9 0 kg 19 LBS 13 oz 9 0 kg 19 LBS 13 oz Pression autorisée Ps 4 15 MPa 601 psi LP 2 21 MPa 320 psi Poids net 260 kg 573 LBS 5 oz 215 kg 47...

Страница 42: ......

Страница 43: ......

Страница 44: ...I CHIYODA KU TOKYO 100 8310 JAPAN Please be sure to put the contact address telephone number on this manual before handing it to the customer This product is designed and intended for use in the residential commer cial and light industrial environment ...

Отзывы: