12. PIPING DESIGN
WR2-Series-575V
12-4. Compatibility
GA(1)/HA(1)/GB(1)/HB(1) type and JA1/KA1/KB1 type can be mixed.
The only combination that is not available is mix of GB(1)/HB(1) type and KB1 type.
When mixing GA(1)/HA(1)/GB(1)/HB(1) type and JA1/KA1/KB1 type, specifications and restrictions are according to
GA(1)/HA(1)/GB(1)/HB(1) type. (piping length, connectable number of Sub BC)
Outdoor/Heat source unit
BC controller
Compatibility
PQRY-P-Z(S)LMU S/W Ver. 6.42 or later
J1 type
Compatible
PQRY-P-Z(S)LMU
G1 type
Compatible
PQRY-P-Z(S)LMU
G type
Compatible
Outdoor/Heat source unit
BC controller
Compatibility
Main
Sub
PQRY-P-Z(S)LMU S/W Ver. 6.42 or later
JA1/KA1 type
GB1/HB1 type GB1/HB1 type
Compatible
JA1/KA1 type
KB1 type
GB1/HB1 type
Not compatible
JA1/KA1 type
GB1/HB1 type
GB/HB type
Compatible
JA1/KA1 type
GB/HB type
GB/HB type
Compatible
JA1/KA1 type
KB1 type
GB/HB type
Not compatible
JA1/KA1 type
GB1/HB1 type
-
Compatible
JA1/KA1 type
GB/HB type
-
Compatible
GA1/HA1 type
KB1 type
KB1 type
Compatible
GA1/HA1 type
KB1 type
GB1/HB1 type
Not compatible
GA1/HA1 type
KB1 type
GB/HB type
Not compatible
GA1/HA1 type
KB1 type
-
Compatible
GA/HA type
KB1 type
KB1 type
Compatible
GA/HA type
KB1 type
GB1/HB1 type
Not compatible
GA/HA type
KB1 type
GB/HB type
Not compatible
GA/HA type
KB1 type
-
Compatible
Outdoor/Heat source unit
BC controller
Compatibility
Main
Sub
PQRY-P-Z(S)LMU S/W Ver. 6.42 or later
JA1/KA1 type
KB1 type
Compatible(*)
*Up to 11 Sub BC controllers can be connected (KB1 type only).