3. Refrigerant pipe and drain pipe

4. Electrical work

Fig. 3-6

Fig. 4-1

4.1. Electric wiring (Fig. 4-1)

* Make sure all electrical wiring is complete before installing the cover panel.
1. Remove the cover from the address board (two bolts).
2. Remove the cover from the electrical box (one bolt).
3. Remove the bolts securing the electrical box and lower the box (two bolts).
4. Insert the wires into the electrical box.
5. Connect the wires securely to the terminal block.

* Be sure to make the various wires long enough so the box may be lowered from

the unit during servicing.

6. Secure the wires with the wiring clamp on the side of the electrical box.
7. Replace the parts you have removed to their original locations.

A means for the disconnection of the supply with an isolation switch, or similar de-
vice, in all active conductors shall be incorporated in the fixed wiring.

Power supply wiring

• Power supply codes of appliance shall not be lighter than design 245 IEC 53 or 227

IEC 53.

• A switch with at least 3 mm contact separation in each pole shall be provided by the

air conditioner installation.

Power cable size: more than 1.5 mm

2

• Install an earth longer and thicker than other cables.

4.2. Connecting remote controller, indoor and outdoor

transmission cables (Fig. 4-2)

• Connect indoor unit TB5 and outdoor unit TB3. (Non-polarized 2-wire)

The “S” on indoor unit TB5 is a shielding wire connection. For specifications about
the connecting cables, refer to the outdoor unit installation manual.

• Install a remote controller following the manual supplied with the remote controller.
• Connect the remote controller’s transmission cable within 10 m using a 0.75 mm

2

core cable. If the distance is more than 10 m, use a 1.25 mm

2

 junction cable.

1

MA Remote controller

• Connect the “1” and “2” on indoor unit TB15 to a MA remote controller. (Non-polar-

ized 2-wire)

• DC 9 to 13 V between 1 and 2 (MA remote controller)

2

M-NET Remote controller

• Connect the “M1” and “M2” on indoor unit TB5 to a M-NET remote controller. (Non-

polarized 2-wire)

• DC 24 to 30 V between M1 and M2 (M-NET remote controller)

A

Terminal block for indoor transmission cable

B

Terminal block for outdoor transmission cable

C

Remote controller

Fig. 4-2

1

2

A

A

C

TB5

TB15 TB5

TB15

S

M1 M2

S

M1 M2

B

TB3

M1 M2

2

1

C

2

1

A

A

C

TB5

TB5

S

M1 M2

S

M1 M2

C

B

TB3

M1 M2

In cases of upward drainage (Fig. 3-5)

• The largest dimension possible for the vertical section at 

B

 is 60 cm from the

lower surface of the ceiling.  Make this vertical section as short as possible.

Water drainage check (Fig. 3-6)

1. Fill the drainage pan with about 0.5 liters of water.  (Don’t pour water directly into

the drain pump.)

2. Make a test run of the unit (in Cooling mode).
3. Check for water drainage at the transparent check window and the outlet of the

drainage pipe.

4. Stop the test run. (Don’t forget to turn off the power.)

A

Ceiling panel

B

Max. 60 cm

C

Position of drain outlet

D

Make as short as possible (Max. 15 cm)

E

Make as small as possible

F

Downward slope (1/100 or more)

G

Make as great as possible (Min. 10 cm)

H

Drainage pipe vertical section

I

Water bottle (procure locally)

H

A

C

D

G

F

E

B

I

Fig. 3-5

A

B

F

A

Cover

B

Electrical box

C

Terminal block for power supply

D

Terminal block for transmission cable

E

Control board

F

Address board

G

Secure with the wiring clamp

H

Terminal block for MA Remote controller

C

D

G

E

F

H

Содержание City Multi PMFY-P100VBM-E

Страница 1: ... ÛË Ú Î ÏÂ ÛÙÂ È ÛÂÙÂ ÚÔÛÂ ÙÈÎ Ùfi ÙÔ ÂÁ ÂÈÚ ÈÔ ÂÁÎ Ù ÛÙ ÛË ÚÈÓ Ú ÛÂÙÂ ÙËÓ ÂÁÎ Ù ÛÙ ÛË ÙË ÌÔÓ ÎÏÈÌ ÙÈÛÌÔ MANUAL DE INSTALAÇÃO Para segurança e utilização correctas leia atentamente este manual de instalação antes de instalar a unidade de ar condicionado MONTAJ ELK TABI Emniyetli ve do ru biçimde nas l kullan laca n ö renmek için lütfen klima cihaz n monte etmeden önce bu elkitab n dikkatle okuyunuz...

Страница 2: ...s etc 1 Safety precautions 2 2 Installing the indoor unit 2 3 Refrigerant pipe and drain pipe 4 4 Electrical work 6 5 Installing the grille 7 6 Test run Fig 6 1 9 1 Safety precautions Indicates an action that must be avoided Indicates that important instructions must be followed Indicates a part which must be grounded Indicates that caution should be taken with rotating parts Indicates that the ma...

Страница 3: ... been fixed and the direction of the pipes has been determined place the refrigerant and drainage pipes the wiring for the remote controller and the wiring that connects the indoor and outdoor units in their desired locations before suspending the indoor unit This is especially important in cases where the ceiling is already in existence 1 Wooden structures Fig 2 4 Use tie beams single storied hou...

Страница 4: ...ter in it Fig 2 8 Make sure that any slant in the unit after installation is less than 0 5 degrees approx 6 mm on the long dimension of the unit 5 Tighten all the nuts Fig 2 9 A Suspension bolt 3 8 or M10 B Clear plastic tubing C Underside of bracket D Secure front panel here E Make these surfaces are flush with each other 0 3 mm 2 5 Fresh air intake hole Fig 2 10 At the time of installation use t...

Страница 5: ...Fig 3 4 Use O D ø26 mm PVC TUBE for drain piping and provide 1 100 or more down ward slope Be sure to connect the piping joints using adhesive of polyvinyl chloride family Observe the figure for piping work Use attached drain hose to change the pipe extraction direction 1 Correct piping 2 Wrong piping A Insulation 9 mm or more B Downward slope 1 100 or more C Support metal K Air bleeder L Raised M...

Страница 6: ...er Connect the remote controller s transmission cable within 10 m using a 0 75 mm2 core cable If the distance is more than 10 m use a 1 25 mm2 junction cable 1 MA Remote controller Connect the 1 and 2 on indoor unit TB15 to a MA remote controller Non polar ized 2 wire DC 9 to 13 V between 1 and 2 MA remote controller 2 M NET Remote controller Connect the M1 and M2 on indoor unit TB5 to a M NET rem...

Страница 7: ...mm2 2 M NET Remote control cables Kind of remote control cable Shielding wire MVVS Cable diameter More than 0 5 to 1 25 mm2 Remarks When 10 m is exceeded use cable with the same specifications as transmission line wiring 3 MA Remote control cables Kind of remote control cable 2 core cable unshielded Cable diameter 0 3 to 1 25 mm2 Fig 4 3 SW14 0 SW11 0 SW12 0 1 2 3 4 5 6 7 8 9 10 ON OFF SW1 SW5 220...

Страница 8: ...ng bolts 2 and securing screws 3 in the center three places Finally tighten the securing bolts 2 in the four places at left and right At this point make sure there are no gaps between the indoor unit and the front panel and between the front panel and the ceiling surface If there are gaps the wind may come in and it may cause water to drip Fig 5 6 Tighten the securing bolts 2 and securing screws 3...

Страница 9: ... adjustment button Check that the wind speed is changed 4 Press Up down airflow selection button to change wind direction 5 Press ON OFF button to clear test run Test run stops A Lighting in operation B Displaying inspection code C Displaying remaining test run time D Displaying indoor unit s liquid pipe temperature E Displaying test run Note The 2 hour set timer is activated to automatically stop...

Страница 10: ... EEC Electromagnetic Compatibility Directive 89 336 EEC This product is designed and intended for use in the residential commercial and light industrial environment HEAD OFFICE MITSUBISHI DENKI BLDG 2 2 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN Printed in Japan BG79U328H02 The product at hand is based on the following EU regulations ...

Отзывы: