28
9-4. TEST POINT DIAGRAM
9-4-1. Indoor controller board
PMFY-P06NBMU-E PMFY-P08NBMU-E PMFY-P12NBMU-E PMFY-P15NBMU-E
PMFY-P06NBMU-E
1
PMFY-P08NBMU-E
1
PMFY-P12NBMU-E
1
PMFY-P15NBMU-E
1
LED1
Power supply (I.B)
(Indoor unit :
208-230V)
CNP
Drain pump output
(DP)
Between
1
to
3
208-230V AC
FUSE
6A 250V
FAN
Fan motor output
(MF)
CN2M
Connect to the terminal block (TB5)
(M-NET transmission connecting wire)
24-30V DC (non-polar)
CN3A
Connect to the terminal block (TB15)
(MA-Remote controller connecting wire)
Between
1
to
3
8.7-13V DC (Pin
1
(+))
CN29
Pipe temperature
thermistor/Gas
(TH23)
CN60
Linear expansion
valve output (LEV)
12VDC pulse output
CN31
Drain sensor (DS)
CN51
Centrally control
1
-
2
: Control signal
12VDC pulse input
(
1
: +)
3
-
4
: Operation indicator
12VDC (
3
: +)
3
-
5
: Malfunction indicator
12VDC (
3
: +)
SW2
Capacity setting
CN6V
Vane motor output
(MV)
12VDC pulse output
CN20
Room temperature
thermistor (TH21)
CN27
Connector
(Damper)
12VDC (
1
: +)
SW3
Function setting
CN32
Connector
(Remote switch)
SW4
Model selection
CND
Connect to the
terminal block (TB2)
(Power supply for
indoor controller
board connecting
wire)
Between
1
to
3
208-230V AC
LED2
Power supply (R.B)
CN21
Pipe temperature
thermistor/Liquid
(TH22)
CN41
HA terminal-A
CN52
Remote indicator
1
-
2
: Status lamp 12VDC (
1
: +)
Fan motor output (SW1-5 OFF)
Thermostat ON (SW1-5 ON)
1
-
3
: Cooling/Dry status lamp
12VDC (
1
: +)
1
-
4
: Heating status lamp
12VDC (
1
: +)
OC341F
Содержание CITY MULTI PMFY-P06NBMU-E