3. Connecting drain pipe
B
C
6
30 30
7
7
18
A
A
H
H
G
G
D E
C K
F
F
C
J
I
1
A
B
K
B
F
D
F
F
H
I
G
E
D
D
L
M
C
F
J
2
3
3.1. Drainage piping work (Fig. 3-1)
• The indoor parts of the drain pipe should be wrapped with polyethylene foam
insulation materials (specific gravity of 0.03, thickness of 9 mm or more).
• Use VP25 (O.D. ø32 PVC TUBE) for drain piping and provide 1/100 or more
downward slope.
• Be sure to connect the piping joints using a PVC type adhesive.
• Observe the figure for piping work.
• Use the included drain hose to change the extraction direction.
• When performing the drainage piping work, be sure to use the support metal hold-
ers.
If a load is applied to the drain socket that damages the hose or causes the hose
to become detached, water leakage may result.
1
Correct piping
G
Make the piping size large for grouped pip-
ing.
2
Wrong piping
3
Grouped piping
H
Downward slope (1/100 or more)
A
Insulation (9 mm or more)
I
O.D. ø38 PVC TUBE for grouped piping
(9 mm or more insulation)
B
Downward slope (1/100 or more)
C
Support metal
J
Up to 85 cm
D
O.D. ø32 PVC TUBE
K
Air bleeder
E
Make it as large as possible
(about 10 cm)
L
Raised
M
Odor trap
F
Main unit
1. Connect the drain socket (supplied with the unit) to the drain port. (Fig. 3-2)
(Fix the tube using PVC adhesive then secure it with a band.)
2. Install a locally purchased drain pipe (PVC pipe, O.D. ø32).
(Fix the pipe using PVC adhesive then secure it with a band.)
3. Check that drain flows smoothly.
4. Insulate the drain port and socket with insulating material, then secure the material
with a band. (Both insulating material and band are supplied with the unit.)
5. Insulate the tube and pipe. (PVC pipe, O.D. ø32)
A
Main unit
G
Drain pipe (O.D. ø32 PVC TUBE)
B
Insulating material
H
Insulating material (purchased locally)
C
Band
I
Transparent PVC pipe
D
Drain port (transparent)
J
O.D. ø32 PVC TUBE (Slope 1/100 or more)
E
Insertion margin
K
Drain socket
F
Matching
Fig. 3-1
Fig. 3-2
Max. 20 m
Max. 15 cm
1.5 - 2 m
(mm)
4
en
BT79D035H01_en.indd 4
2019/07/30 11:12:38
006