3
SPECIFICATION
3-1. Specification
6
Notes: *1 Cooling/Heating capacity indicates the maximum value at operation under the following condition.
Cooling: Indoor: 26.7 ˚C [80 ˚F] DB/19.4 ˚C [67 ˚F] WB
Outdoor: 35
˚C [95 ˚F ] DB
Heating: Indoor: 21.1
˚C [70 ˚F] DB
Outdoor: 8.3
˚C [47 ˚F] DB/6.1˚C [ 43 ˚F] WB
*2 The operating noise is the data that was obtained in an anechoic room.
*4 The figure in ( ) indicates Panel's.
Item Model
PLFY-P0
PLFY-P-NMLU-E
6NLMU-E
PLFY-P08NLMU-E
PLFY-P12NLMU-E
PLFY-P15NLMU-E
PLFY-P18NLMU-E
Power sourse
208/230V, 60Hz
Capacity
*1
Cooling
kW
1.8
2.3
3.5 4.4
5.3
BTU/h
6000
8000
12000
15000
18000
Heating
kW
2.0
2.6
4.0 5.0
5.9
BTU/h
6700
9000
13500
17000
20000
Dimension
*4
Height
mm
290 (20)
in
11-7/16 (13/16)
Width
mm
776 (1080)
946 (1250)
in
30-9/16 (42-17/32)
37-1/4 (49-7/32)
Depth
mm
634 (710)
in
24-31/32 (27-31/32)
Net weight
kg
23 (6.5)
24 (6.5)
27 (7.5)
lb
51 (15)
53 (15)
60 (17)
FAN
Airflow rate
(Low-Middle-High)
m
3
/min
6.5-8.0-9.5
6.5-8.0-9.5
6.5-8.0-9.5
7.0-8.5-10.5
9.0-11.0-12.5
cfm
230-282-335
230-282-335
230-282-335
247-300-371
318-388-441
External static
pressure
Pa
208V
-
-
-
-
-
230V
-
-
-
-
-
Noise level
(Low-Middle-High) *2
dB(A)
208V
27-30-33
27-30-33
27-30-33
29-33-36
31-34-37
230V
28-31-34
28-31-34
28-31-34
30-34-37
32-35-38
Filter
Standard filter