5

Fig. 3-3

3. Refrigerant pipe and drain pipe

3.4. Drainage piping work (Fig. 3-4)

• Use VP25 (O.D. ø32 (1-1/4”) PVC TUBE) for drain piping and provide 1/100 or

more downward slope.

• Be sure to connect the piping joints using a polyvinyl type adhesive.
• Observe the figure for piping work.
• Use the included drain hose to change the extraction direction.

1

Correct piping

2

Wrong piping

A

Insulation (9 mm or more)

B

Downward slope (1/100 or more)

C

Support metal

K

Air bleeder

L

Raised

M

Odor trap

Grouped piping

D

O. D. ø32 PVC TUBE

E

Make it as large as possible

F

Indoor unit

G

Make the piping size large for grouped piping.

H

Downward slope (1/100 or more)

I

O. D. ø38 PVC TUBE for grouped piping.
(9 mm or more insulation)

J

Up to 500 mm

1. Connect the drain socket (supplied with the unit) to the drain port. (Fig. 3-5)

(Affix the tube using PVC adhesive then secure it with a band.)

2. Install a locally purchased drain pipe (PVC pipe, O.D. ø32).

(Affix the pipe using PVC adhesive then secure it with a band.)

3. Insulate the tube and pipe. (PVC pipe, O.D. ø32 and socket)
4. Check that drain flows smoothly.
5. Insulate the drain port with insulating material, then secure the material with a

band. (Both insulating material and band are supplied with the unit.)

A

Unit

B

Insulating material

C

Band (large)

D

Drain port (transparent)

E

Insertion margin

F

Matching

G

Drain pipe (O.D. ø32 PVC TUBE)

H

Insulating material (purchased locally)

I

Transparent PVC pipe

J

O.D. ø32 PVC TUBE (Slope 1/100 or more)

K

Band (small)

L

Drain socket

Max. 20m

1.5–2m

A

B

C

B

M

L

K

D

E

D

H

I

G

D

F

F

F

Max. 15cm

J

F

Fig. 3-4

Fig. 3-5

B

Refrigerant pipe sizes & Flare nut tightening torque

Flare nut O.D.

Liquid

Gas

pipe

pipe

(mm)

(mm)

17

26

22

29

22

29

22

36

C

Apply refrigerating machine oil over the entire flare seat surface.

* Use the provided flare nut for the following pipes: Liquid pipe of P50, P100, P125, and gas pipe of P50.

R410A

Liquid pipe

Gas pipe

Tightening

Tightening

Pipe size

torque

Pipe size

torque

(mm)

(N.m)

(mm)

(N.m)

ODø6.35 (1/4”)

14 - 18

ODø12.7 (1/2”)

49 - 61

ODø6.35 (1/4”)

34 - 42

ODø12.7 (1/2”)

68 - 82

ODø9.52 (3/8”)

34 - 42

ODø15.88 (5/8”)

68 - 82

ODø9.52 (3/8”)

34 - 42

ODø15.88 (5/8”)

100 - 120

R407C or R22

Liquid pipe

Gas pipe

Tightening

Tightening

Pipe size

torque

Pipe size

torque

(mm)

(N.m)

(mm)

(N.m)

ODø6.35 (1/4”)

14 - 18

ODø12.7 (1/2”)

49 - 61

ODø9.52 (3/8”)

34 - 42*

ODø15.88 (5/8”)

68 - 82*

ODø9.52 (3/8”)

34 - 42

ODø15.88 (5/8”)

68 - 82

ODø9.52 (3/8”)

34 - 42

ODø19.05 (3/4”)

100 - 120*

J

H

I

B

,

C

F

G

G

11

30

30

30

B

A

C

K

F

L

H

D

E

E

I

J

C

,

K

(mm)

P20/25/32/40
P50
P63/80
P100/125

3.3. Indoor unit (Fig. 3-3)

Heat insulation for refrigerant pipes:

1

Wrap the enclosed large-sized pipe cover around the gas pipe, making sure that
the end of the pipe cover touches the side of the unit.

2

Wrap the enclosed small-sized pipe cover around the liquid pipe, making sure
that the end of the pipe cover touches the side of the unit.

3

Secure both ends of each pipe cover with the enclosed bands. (Attach the bands
20 mm from the ends of the pipe cover.)

• After connecting the refrigerant piping to the indoor unit, be sure to test the pipe

connections for gas leakage with nitrogen gas. (Check that there is no refrigerant
leakage from the refrigerant piping to the indoor unit.)

A

Refrigerant pipe and insulating material

(Procure locally)

B

Pipe cover (large) (Accessory)

C

Pipe cover (small) (Accessory)

D

Refrigerant pipe (gas)

E

Refrigerant pipe (liquid)

F

Band (Accessory)

g

Cross-sectional view of connection

H

Refrigerant pipe

I

Insulating material

J

Squeeze

Содержание CITY MULTI PLFY-P-VCM-E

Страница 1: ... ÛË Ú Î ÏÂ ÛÙÂ È ÛÂÙÂ ÚÔÛÂ ÙÈÎ Ùfi ÙÔ ÂÁ ÂÈÚ ÈÔ ÂÁÎ Ù ÛÙ ÛË ÚÈÓ Ú ÛÂÙÂ ÙËÓ ÂÁÎ Ù ÛÙ ÛË ÙË ÌÔÓ ÎÏÈÌ ÙÈÛÌÔ MANUAL DE INSTALAÇÃO Para segurança e utilização correctas leia atentamente este manual de instalação antes de instalar a unidade de ar condicionado MONTAJ ELK TABI Emniyetli ve do ru biçimde nas l kullan laca n ö renmek için lütfen klima cihaz n monte etmeden önce bu elkitab n dikkatle okuyunuz...

Страница 2: ...pipe 4 4 Electrical work 6 5 Installing the grille 7 6 Test run Fig 6 1 9 1 Safety precautions Indicates an action that must be avoided Indicates that important instructions must be followed Indicates a part which must be grounded Indicates that caution should be taken with rotating parts Indicates that the main switch must be turned off before servicing Beware of electric shock Beware of hot surf...

Страница 3: ...ch inner diameter fits into the outer diamete of the duct flange In case that the environment above the ceiling is high temperature and high humid ity wrap the duct in a heat insulate to avoid causing dew drop on the wall A Duct flange recommended shape Thickness 0 8 or more B 3 ø5 hole C Detail drawing of fresh air intake D Indoor unit E Ceiling surface F 3 ø2 8 Burring hole G ø73 4 cutout hole H...

Страница 4: ...on bolts Fig 2 7 Using the gauge attached to the grille ensure that the bottom of the main unit is properly aligned with the opening of the ceiling Be sure to confirm this otherwise condensation may form and drip due to air leakage etc Confirm that the main unit is horizontally levelled using a level or a vinyl tube filled with water After checking the position of the main unit tighten the nuts of...

Страница 5: ...ening torque Flare nut O D Liquid Gas pipe pipe mm mm 17 26 22 29 22 29 22 36 C Apply refrigerating machine oil over the entire flare seat surface Use the provided flare nut for the following pipes Liquid pipe of P50 P100 P125 and gas pipe of P50 R410A Liquid pipe Gas pipe Tightening Tightening Pipe size torque Pipe size torque mm N m mm N m ODø6 35 1 4 14 18 ODø12 7 1 2 49 61 ODø6 35 1 4 34 42 OD...

Страница 6: ...ler Connect the remote controller s transmission cable within 10 m using a 0 75 mm2 core cable If the distance is more than 10 m use a 1 25 mm2 junction cable 1 MA Remote controller Connect the 1 and 2 on indoor unit TB15 to a MA remote controller Non polar ized 2 wire DC 9 to 13 V between 1 and 2 MA remote controller 2 M NET Remote controller Connect the M1 and M2 on indoor unit TB5 to a M NET re...

Страница 7: ...5 1 1 4 5 2 3 Fig 5 3 B A C 1 1 D E 2 F G F B 1 Fig 5 4 5 2 Preparing to attach the grille Fig 5 2 With the gauge supplied with this kit adjust and check the positioning of the unit relative to the ceiling If the unit is not properly positioned in the ceiling there may be air leaks condensation may form or the up down vanes may not operate cor rectly Make sure that the opening in the ceiling is wi...

Страница 8: ...ng to the preference of the customer The operation of the fixed up down vanes and all automatic controls cannot be performed using the remote controller In addition the actual position of the vanes may differ from the position indicated on the remote controller 1 Turn off the main power switch Injuries and or an electrical shock may occur while the fan of the unit is rotating 2 Disconnect the conn...

Страница 9: ...nstallation in a new premises 1 Remove the cover of the water supply inlet and add about 1000 cc of water using a water supply pump etc During this process be careful not to spray water into the drain pump mechanism 2 Confirm that water is being drained out through the drainage outlet after switch ing over from remote control mode to trial run mode 3 After checking the drainage ensure that the cov...

Страница 10: ...EC Electromagnetic Compatibility Directive 89 336 EEC This product is designed and intended for use in the residential commercial and light industrial environment HEAD OFFICE MITSUBISHI DENKI BLDG 2 2 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN Printed in Thailand BG79U363H01 The product at hand is based on the following EU regulations ...

Отзывы: