27
Control modes
Control details
1-1. Thermoregulating function (Function to prevent restarting for
3 minutes)
• Room temp.
desired temp. 30 °F ···Thermo ON
• Room temp.
desired temp. ···Thermo OFF
1. Thermoregulating
function
Remarks
Controlled by the remote controller (4-speed)
Give priority to under-mentioned controlled mode
2-1. Hot adjuster mode
2-2. Preheating exclusion mode
2-3. Thermo OFF mode (When the compressor off by the
thermoregulating)
2-4. Defrosting mode
2-1. Hot adjuster mode
The fan controller becomes the hot adjuster mode for the
following
conditions.
When starting the HEAT operation
When starting the compressor by the thermoregulating
When releasing the HEAT defrosting operation
2. Fan
Fan speed change notch
Refer to the model function table
A: HOT adjuster mode start
B: 5 min have passed since the condition A or the indoor
Condenser/Evaporator temp. turned to be 95 °F or more
C: 2 min have passed since the condition B
(Terminating the hot adjuster mode)
A
C
B
[Extra Low]
[Low]
Set fan speed by the remote controller
Hot adjuster mode
;
1
;
1 "STAND BY" will be displayed
during the hot adjuster mode.
To be continued on the next page
PAR-21MAA
ON/OFF
FILTER
CHECK
OPERATION
CLEAR
TEST
TEMP.
MENU
BACK
DAY
MONITOR/SET
CLOCK
ON/OFF
°F°C
°F°C
ERROR CODE
AFTER
TIMER
TIME SUN MON TUE WED THU FRI SAT
ON
OFF
Hr
AFTER
FILTER
FUNCTION
ONLY1Hr.
WEEKLY
SIMPLE
AUTO OFF
8-4. HEAT OPERATION
<How to operate>
1
Press POWER ON/OFF button.
2
Press the operation MODE button to display HEAT.
3
Press the TEMP. button to set the desired temperature.
NOTE
: The set temperature changes 2°F when the or button is
pressed one time. Heating 63 to 83°F.
<Display in HEAT operation>
[DEFROST]
The [DEFROST] symbol is only displayed during the defrost operation.
[STANDBY]
The [STANDBY] symbol is only displayed from the time the heating operation
starts unit the heated air begins to blow.