3.  Installing the indoor unit

(mm)

Fig. 3-1

Fig. 3-2

3.1.2.  Drilling the piping hole (Fig. 3-2)

  Use a core drill to make a hole of 90-100 mm diameter in the wall in the 

piping direction, at the position shown in the diagram to the left. 

  The hole should incline so that the outside opening is lower than the in-

side opening.

  Insert a sleeve (with a 90 mm diameter and purchased locally) through the 

hole.

Note:
The purpose of the hole’s inclination is to promote drain fl ow.

 Sleeve
 Hole
 (Indoors)
  Wall
 (Outdoors)

3.1.3.  Installing the wall mounting fi xture

  Since the indoor unit weighs near 10 kg, selection of the mounting loca-

tion requires thorough consideration. If the wall does not seem to be 
strong enough, reinforce it with boards or beams before installation.

  The mounting fi xture must be secured at both ends and at the centre, if 

possible. Never fi x it at a single spot or in any unsymetrical way.

 

(If possible, secure the fi xture at all the positions marked with a bold ar-
row.) (Fig. 3-3) 

 Warning:

If possible, secure the fi xture at all positions indicated with a bold arrow.

 Caution:

•  The unit body must be mounted horizontally.
•  Fasten at the holes marked with 

 as shown by the arrows.

 Fasten a thread to the hole.

 The level can be easily obtained by hanging a weight from the string and aligning the 

string with the mark.

3.2.  Preparation for piping connection

  Remove the vinyl band that holds the drain pipe.

  Rear, right and lower piping (Fig. 3-4) 

  Bind the refrigerant pipes and drain pipe with vinyl tape at three or more 

points. This will facilitate passing the pipes through the wall.

 Vinyl  tape

 This fi gure is viewed from the back of the unit.

  Left and left rear piping

-

  For left rear piping, pull the pipes out the hole to determine their correct 

length, then bend them. The indoor unit should hang on the wall mounting 
fi xture. (Fig. 3-5) 

 Wall

 Wall  hole

 Bent  section

 Refrigerant  pipe

 Drain  pipe

 Transmission  cable

Fig. 3-3

Fig. 3-4

Fig. 3-5

 Min. 100 mm

 Min. 130 mm

 Min. 59 mm  

*1

 Mount board

*1: 69mm or more for left and left 

back piping

40.5

245.5

196.5

3

283

9

250

190

450

109.5

450

79.5

79.5

328

298

109.5

10

5

100

450

-

3.1.  Installing the wall mounting fi xture (Fig. 3-1)

3.1.1.  Setting the wall mounting fi xture and piping positions

  Using the wall mounting fi xture, determine the unit’s installation position 

and the locations of the piping holes to be drilled.

 Warning:

Before drilling a hole in the wall, you must consult the building contractor.

 Supporting piece

 Knockout hole (12-ø2.6)

 Mount board

 Knockout hole (4-ø9)

 Main body

 Knockout hole (87-ø5.4)

 Slot (4-4.5 × 35)

 Piping hole (ø65)

 Knockout hole (8-ø4.3)

 Slot (4-4.5 × 40)

 Level setting standard

 Slot (4-4.5 × 37)

 Knockout hole

 Slot (4-11 × 20)

W: Location for wall holes

 Wall mounting fi xture

 Hole centre

 Align the scale with the line.

 Insert scale.

RG79D177H01_0221.indd   3

RG79D177H01_0221.indd   3

22/02/2007   19:08:06

22/02/2007   19:08:06

Содержание CITY MULTI PKFY-P-VBM-E

Страница 1: ... di installare il con dizionatore d aria MANUAL DE INSTALACIÓN Para un uso seguro y correcto lea detalladamente este manual de instalación antes de montar la unidad de aire acondicionado FOR INSTALLER FÜR INSTALLATEURE POUR L INSTALLATEUR VOOR DE INSTALLATEUR PARA EL INSTALADOR PER L INSTALLATORE PARA O INSTALADOR 安装说明书 在安装空调机之前 请先通读此安装说明书 以便安全正确地使用 安装人员适用 ΕΓΧΕΙΡΙΔΙΟ ΟΔΗΓΙΩΝ ΕΓΚΑΤΑΣΤΑΣΗΣ Για ασφάλ...

Страница 2: ...ctrical work 6 6 Test run 7 Contents 1 Safety precautions Before installing the unit make sure you read all the Safety precau tions Please report to your supply authority or obtain their consent before connecting this equipment to the power supply system Warning Describes precautions that must be observed to prevent danger of injury or death to the user Caution Describes precautions that must be o...

Страница 3: ... for piping connection Remove the vinyl band that holds the drain pipe Rear right and lower piping Fig 3 4 Bind the refrigerant pipes and drain pipe with vinyl tape at three or more points This will facilitate passing the pipes through the wall Vinyl tape This figure is viewed from the back of the unit Left and left rear piping For left rear piping pull the pipes out the hole to determine their co...

Страница 4: ...ard Supporting piece Rib If the flare pipe is to be embedded into the wall in advance Fig 3 7 Determine the length of pipe to be embedded by marking on the mounting plate as a reference Mark Wall mounting fixture 3 3 Mounting the unit Fig 3 8 Securely place the hanging fixtures for the indoor unit over the catches on the wall mounting fixture Indoor unit Wall mounting fixture Catch When piping has...

Страница 5: ...erant and drain piping Fig 4 2 The drain pipe can be cut midway to meet the on site conditions Total length of flexible hose Gas pipe Liquid pipe Drain hose Determine the position of the knockout holes on the unit body Fig 4 3 Cut the knockout holes using a saw blade or an adequate knife Take care not to damage other parts of the unit Remove the corner box and drill a knockout hole If a hole is ma...

Страница 6: ... active phase conductors of the supply Power supply wiring Install an earth longer than other cables Power supply codes of appliance shall not be lighter than design 60245 IEC 53 or 60227 IEC 53 A switch with at least 3 mm contact separation in each pole shall be provided by the air conditioner installation Power cable size more than 1 5 mm2 Fig 5 3 A Switch 16 A D Total operating current be less ...

Страница 7: ...L HEAT ON OFF button Test run display Liquid pipe Indoor unit temperature display ON OFF lamp Power display Error code display Test run remaining time display Set temperature button Mode selection button Air direction button TEST button Fan Speed button Louver button 6 2 Test run Using wired remote controller Fig 6 1 Turn on the power at least 12 hours before the test run Press the TEST button twi...

Страница 8: ...ective 89 336 EEC This product is designed and intended for use in the residential commercial and light industrial environment HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN Printed in Japan RG79D177H01 The product at hand is based on the following EU regulations RG79D177H01_0221 indd 8 RG79D177H01_0221 indd 8 22 02 2007 19 08 11 22 02 2007 19 08 11 ...

Отзывы: