4. Voltage test points on the control board
1. PFFY-W20, 25, 32, 40, 50VCM-A
F1
Fuse (AC 250V 6.3A)
CND
Power supply voltage (220 -
240VAC)
CN2M
For M-NET transmission cable
connection (24 - 30VDC)
SWE
Emergency operation
SW2
Capacity setting
SW4
Function setting
SW3
Function setting
CN32
Remote start/stop adapter
CN3A
For MA remote controller cable
connection
(10 - 13 VDC (Between 1 and 3.))
CN52
Remote display
CN51
Centralized control
CN41
JAMA standard HA terminal A
CN44
Thermistor (water inlet/outlet tem-
perature)
CN20
Thermistor (Inlet air temperature)
CNMF1 Fan motor output
1 - 4: 294 - 340 VDC
5 - 4: 15 VDC
6 - 4: 0 - 6.5 VDC
7 - 4: Stop 0 or 15 VDC
Run 7.5 VDC
(0 - 15 pulse)
CNSA
Pressure sensor (inner water)
CNSB
Pressure sensor (outlet water)
CN8A
Flow control valve (FCV)
(*1)
V
FG
Voltage on 3 of PC352 and the (-)
side of C081
(Same with the voltage between 7
(+) and 4 (-) of CNMF)
V
CC
Voltage between the C084 pins
15 VDC
(Same with the voltage between 5
(+) and 4 (-) of CNMF)
Vsp Voltage between the C351 pins
0VDC (with the fan stopped)
1 - 6.5VDC (with the fan in opera-
tion)
(Same with the voltage between 6
(+) and 4 (-) of CNMF)
CNMF1
CN44
CN22
CN20
CNSB
CNSA
CN3A
SW1
SW2
SW4
SW21
SW3
CN52
CN51 CN41
SW22
CN8A
F1
CND
SWE
CN32
CN2M