•     Do not install unit at a site where fire detector is located at the supply air side.

(Fire detector may operate erroneously due to the heated air supplied during
heating operation.)

•     When special chemical product may scatter around such as site chemical plants

and hospitals, full investigation is required before installing unit. (The plastic
components may be damaged depending on the chemical product applied.)

•     If the unit is run for long hours at high temperature/ high humidity (dew point

above 26 °C), dew condensation may be produced in the indoor unit. When
operating the units in this condition, add insulation material (10-20 mm) to the
entire surface of the indoor unit to avoid dew condensation.

•     Do not place things that are vulnerable to water damage under the unit. 

Condensation may form in a situation such as when foreign object is trapped in
the LEV. Install an emergency drain pan under the unit as necessary.

 Warning:

 

The unit must be securely installed on a structure that can sustain its weight.
If the unit is mounted on an unstable structure, it may fall down causing inju-
ries.

3.1.   Securing installation and service space

[Fig. 3.1.1] (P.2)

3.2.   Combining indoor units with outdoor units

For combining indoor units with outdoor units, refer to the outdoor unit installation
manual.

4. Installing the unit

4.1.   Assembling the unit

Install the unit frame in parallel with the floor securely when installing.
There are the following two methods of installing the unit.

For fixing on the floor
[Fig. 4.1.1] [Fig. 4.1.2] (P.2)

For fixing on the wall
[Fig. 4.1.3] (P.2)



To fix the indoor unit on the wall, use the hanging bolts.

[Fig. 4.1.4] (P.2)



When the unit is installed on the wall, vibrations may be transmitted to the

wall. Take measures against vibrations as needed at the site.

4.2.   Center of gravity and product weight

[Fig. 4.2.1] (P.3)

4.3.   Confirming the unit’s position and fixing hanging 

bolts



Ensure that the hanging bolt nuts are tightened to fix the hanging bolts.



To ensure that drain is discharged, be sure to hang the unit at level using a

level.

Caution:

Install the unit in horizontal position. If the side with drain port is installed
higher, water leakage may be caused.

5. Refrigerant pipe and drain pipe specifications

To avoid dew drops, provide sufficient antisweating and insulating work to the refrig-
erant and drain pipes.
When using commercially available refrigerant pipes, be sure to wind commercially
available insulating material (with a heat-resisting temperature of more than 100 °C
and thickness given below) onto both liquid and gas pipes.
Insulate all indoor pipes with form polyethylene insulation with a minimum density of
0.03 and a thickness as specified in the table below.

1

Select the thickness of insulating material by pipe size.

2

If the unit is used on the highest story of a building and under conditions of

 

high

temperature and humidity, it is necessary to use pipe size and insulating mate-
rial’s thickness more than those given in the table above.

3

If there are customer’s specifications, simply follow them.

5.1.   Refrigerant pipe and drain pipe specifications

5.2.   Refrigerant pipe, drain pipe

[Fig. 5.2.1] (P.3)

A

Floor

B

Piping space

C

Electrical part service space

For PFFY-P-VCM-E

(mm)

Model name

(A)

(B)

20

·

25

·

32

700

More than 240

40

·

50

900

More than 240

63

1100

More than 240

<Viewed from top of the unit>

A  

Leg

B  

Screw

C  

Wall

<Viewed from front of the unit>

A  

Floor

A  

Nuts (field supply)

B  

Washers

C  

M10 hanging bolt (field supply)

For PFFY-P-VCM-E

(mm)

Model name

(E)

(F)

20

·

25

·

32

730

756

40

·

50

930

956

63

1130

1156

A  

Floor hole for fixing

For PFFY-P-VCM-E

Model name

W

(mm)

L

(mm)

X

(mm)

Y

(mm)

Z

(mm)

Product weight 

(kg)

PFFY-P20VCM-E

730

95

5

365

290

18

PFFY-P25VCM-E

730

95

5

365

290

18

PFFY-P32VCM-E

730

95

5

365

290

18.5

PFFY-P40VCM-E

930

95

5

495

300

22.5

PFFY-P50VCM-E

930

95

5

495

300

22.5

PFFY-P63VCM-E

1130

95

5

615

320

25.5

Pipe size

Insulating material’s thickness

6.4 mm to 25.4 mm

More than 10 mm

28.6 mm to 38.1 mm

More than 15 mm

PFFY-P·VCM-E

20·25·32·40·50

63

Refrigerant pipe

(Brazing connection)

Liquid pipe

ø 6.35

ø 9.52

Gas pipe

ø 12.7

ø 15.88

Drain pipe

O.D. ø 32

Item

Model

A  

Refrigerant piping (liquid)

B  

Refrigerant piping (gas)

C  

Drain outlet

VG79D813H01_en.book  9 ページ  2018年12月14日 金曜日 午前11時20分

Содержание CITY MULTI PFFY-P20VCM-E

Страница 1: ...oken noga innan luftkonditioneringsenheten installeras för säker och korrekt användning pl no ru bg РЪКОВОДСТВО ЗА МОНТАЖ За безопасна и правилна употреба моля прочетете внимателно това ръководство преди монтажа на климатизатора PODRĘCZNIK INSTALACJI W celu bezpiecznego i poprawnego korzystania należy przed zainstalowaniem klimatyzatora dokładnie zapoznać się z niniejszym podręcznikiem instalacji ...

Страница 2: ...the wall Viewed from front of the unit A Floor Unit mm A B B C A A Nuts field supply B Washers C M10 Hanging bolt field supply For PFFY P VCM E mm Model name A B 20 25 32 700 More than 240 40 50 900 More than 240 63 1100 More than 240 A Floor B Piping space C Electrical part service space For PFFY P VCM E mm Model name E F 20 25 32 730 756 40 50 930 956 63 1130 1156 VZ79D813H01_DA book 2 ページ 2018年...

Страница 3: ...nt piping liquid B Refrigerant piping gas C Drain outlet Unit mm B A A Cut here B Remove brazed cap A A Cool by a wet cloth A A E C F B D A Thermal insulation B Pull out insulation C Wrap with damp cloth D Return to original position E Ensure that there is no gap here F Wrap with insulating tape VZ79D813H01_DA book 3 ページ 2018年12月3日 月曜日 午後5時17分 ...

Страница 4: ...xing part D Insertion margin E Drain hose accessory F Drain pipe O D ø32 PVC TUBE field supply G Insulating material field supply Unit mm B D F A G C E A Air inlet B Air filter C Duct D Canvas duct E Access door F Wall G Air outlet B A C A Filter B Front plate C Fan guard A B C C C C D C 220 240V A Ground fault interrupter B Local switch Wiring breaker C Indoor unit D Pull box VZ79D813H01_DA book ...

Страница 5: ...rew holding cover 3pcs B Cover C B A A Terminal bed box B Knockout hole C Remove C H J I D N L N L M1 1 2 M2 S B E A G F A Use a cable tie to secure the cable B Use PG bushing to keep the weight of the cable and external force from being applied to the power supply terminal connector C Power source wiring D Use ordinary bushing E Power source terminal block F Terminal block for indoor transmission...

Страница 6: ...6 8 6 Fig 8 6 1 SW21 SW14 SW12 SW11 Indoor controller board VZ79D813H01_DA book 6 ページ 2018年12月3日 月曜日 午後5時17分 ...

Страница 7: ... away from water washing water etc It might result in electric shock catching fire or smoke Securely install the outdoor unit terminal cover panel If the terminal cover panel is not installed properly dust or water may enter the outdoor unit and fire or electric shock may result Do not use refrigerant other than the type indicated in the manuals pro vided with the unit and on the nameplate Doing s...

Страница 8: ... circuit breaker is not installed electric shock may result Use power line cables of sufficient current carrying capacity and rating Cables that are too small may leak generate heat and cause a fire Use only a circuit breaker and fuse of the specified capacity A fuse or circuit breaker of a larger capacity or a steel or copper wire may result in a general unit failure or fire Do not wash the air c...

Страница 9: ... the unit at level using a level Caution Install the unit in horizontal position If the side with drain port is installed higher water leakage may be caused 5 Refrigerant pipe and drain pipe specifications To avoid dew drops provide sufficient antisweating and insulating work to the refrig erant and drain pipes When using commercially available refrigerant pipes be sure to wind commercially availa...

Страница 10: ...on indoors and keep both ends of the piping sealed until just before brazing If dust dirt or water gets into the refrigerant cycle the oil will deteriorate and the compressor may fail Use Suniso 4GS or 3GS small amount refrigerator oil to coat the flare and flange connection part For models using R22 Use ester oil ether oil or alkylbenzene small amount as the refrigerator oil to coat flares and fl...

Страница 11: ... shall be provided by the Air conditioner installation Fig 8 1 1 P 4 Apply to IEC61000 3 3 about Max Permissive System Impedance 1 The Ground fault interrupter should support Inverter circuit The Ground fault interrupter should combine using of local switch or wiring breaker 2 Please take the larger of F1 or F2 as the value for F0 F1 Total operating maximum current of the indoor units 1 2 F2 V1 Qu...

Страница 12: ...roller Fig 8 2 4 P 5 M NET Remote controller The MA remote controller and the M NET remote controller cannot be used at the same time or interchangeably Caution Install wiring so that it is not tight and under tension Wiring under tension may break or overheat and burn 8 3 Connecting electrical connections Please identify the model name of the operation manual attached on the terminal box cover wi...

Страница 13: ...t addresses and branch numbers at will The determination of indoor unit addresses varies with the system at site Set them referring to the Data Book 8 7 Sensing room temperature with the built in sen sor in a remote controller If you want to sense room temperature with the built in sensor in a remote controller set SW1 1 on the control board to ON The setting of SW1 7 and SW1 8 as nec essary also ...

Страница 14: ...14 en VG79D813H01_en book 14 ページ 2018年12月14日 金曜日 午前11時20分 ...

Страница 15: ...IP20 N 10 R410A 4 15 220 220 230 230 240 240 VZ79D813H01_DA book 171 ページ 2018年12月3日 月曜日 午後5時17分 ...

Страница 16: ...wing EU regulations Low Voltage Directive 2014 35 EU Electromagnetic Compatibility Directive 2014 30 EU Machinery Directive 2006 42 EC Please be sure to put the contact address telephone number on this manual before handing it to the customer HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN VG79D813H01_en book 172 ページ 2018年12月14日 金曜日 午前11時20分 ...

Отзывы: