12

en

*3 Current sensitivity is calculated using the following formula.

G1 = (V2 

 Quantity of Type1) + (V3 

 Wire length [km])

 Warning:

•      Be sure to use specified wires for connections and ensure no external force is imparted to terminal connections. If connections are not fixed firmly, heating or

fire may result.

•      Be sure to use the appropriate type of overcurrent protection switch. Note that generated overcurrent may include some amount of direct current.

Caution:

•      Some installation sites may require attachment of an earth leakage breaker for the inverter. If no earth leakage breaker is installed, there is a danger of electric

shock.

•      Do not use anything other than the correct capacity breaker and fuse. Using fuse, wire or copper wire with too large capacity may cause a risk of malfunction

or fire.

Notes:
•      This device is intended for the connection to a power supply system with a maximum permissible system impedance (Refer to IEC61000-3-3.) at the interface

point (power service box) of the user’s supply.

•      The user must ensure that this device is connected only to a power supply system which fulfils the requirement above. 

If necessary, the user can ask the public power supply company for the system impedance at the interface point.

8.2.   Connecting remote controller, indoor

 

and out-

door transmission cables

•     Connect indoor unit TB5 and outdoor unit TB3. (Non-polarized 2-wire)

The “S” on indoor unit TB5 is a shielding wire connection. For specifications
about the connecting cables, refer to the outdoor unit installation manual.

•     Install a remote controller following the manual supplied with the remote control-

ler.

•     Connect the “1” and “2” on indoor unit TB15 to a MA remote controller. (Non-

polarized

 

2-wire)

•     Connect the “M1” and “M2” on indoor unit TB5 to a M-NET remote controller.

 

(Non-polarized 2-wire)

•     Connect the remote controller’s transmission cable within 10 m using a 0.75 mm

2

core cable. If the distance is more than 10 m, use a 1.25 mm

2

 junction cable.

[Fig. 8.2.1] (P.5) MA Remote controller
[Fig. 8.2.2] (P.5) M-NET Remote controller

•     DC 9 to 13 V between 1 and 2 (MA remote controller)
•     DC 24 to 30 V between M1 and M2 (M-NET remote controller)

[Fig. 8.2.3] (P.5) MA Remote controller
[Fig. 8.2.4] (P.5) M-NET Remote controller

•     The MA remote controller and the M-NET remote controller cannot be used at

the same time or interchangeably.

Caution:

Install wiring so that it is not tight and under tension. Wiring under tension
may break, or overheat and burn.

8.3.   Connecting electrical connections

Please identify the model name of the operation manual attached on the terminal
box cover with that shown on the rating name plate.

1.  Remove the screws holding the cover to dismount the cover.

[Fig. 8.3.1] (P.5)

2.   Open knockout holes

(Recommend to use a screwdriver or the like for this work.)

3.   Fix power source wiring to terminal box by using buffer bushing for tensile

force. (PG connection or the like.) Connect transmission wiring to transmission
terminal block through the knockout hole of terminal box using ordinary bush-
ing.

4.   Connect the power source, Earth, transmission and remote controller wiring.

The dismounting of the terminal box is not needed.

[Fig. 8.3.2] (P.5)

[Shield wire connection]

[Fig. 8.3.3] (P.5)

5.   After wiring is complete, make sure again that there is no slack on the connec-

tions,

 

and attach the cover onto the terminal box in the reverse order of

removal.

Notes:
•      Do not pinch the cables or wires when attaching the terminal box cover.

Doing so may cause a risk of disconnection.

•      When accommodating the terminal box, make sure that the connectors

 

on

the box side are not removed. If removed, it cannot operate normally.

G1

Current sensitivity

Wire thickness

V3

30 or less

30 mA 0.1 sec or less

1.5 mm

2

48

100 or less

100 mA 0.1 sec or less

2.5 mm

2

56

4.0 mm

2

66

A  

Terminal block for indoor transmission cable

B  

Terminal block for outdoor transmission cable

C  

Remote controller

A  

Non-polarized

B  

TB15

C  

Remote Controller

D  

TB5

A  

Screw holding cover (3pcs.)

B  

Cover

A  

Terminal bed box

B  

Knockout hole

C  

Remove

A  

Use a cable tie to secure the cable.

B  

Use PG bushing to keep the weight of the cable and external force from being applied 

to the power supply terminal connector.

C  

Power source wiring

D  

Use ordinary bushing

E  

Power source terminal block

F  

Terminal block for indoor transmission

G  

Terminal block for remote controller

H  

To 1-phase power source

I  

Transmission line 30 VDC

J  

Transmission line to the remote controller, terminal block for indoor unit and BC con-

troller

VG79D813H01_en.book  12 ページ  2018年12月14日 金曜日 午前11時20分

Содержание CITY MULTI PFFY-P20VCM-E

Страница 1: ...oken noga innan luftkonditioneringsenheten installeras för säker och korrekt användning pl no ru bg РЪКОВОДСТВО ЗА МОНТАЖ За безопасна и правилна употреба моля прочетете внимателно това ръководство преди монтажа на климатизатора PODRĘCZNIK INSTALACJI W celu bezpiecznego i poprawnego korzystania należy przed zainstalowaniem klimatyzatora dokładnie zapoznać się z niniejszym podręcznikiem instalacji ...

Страница 2: ...the wall Viewed from front of the unit A Floor Unit mm A B B C A A Nuts field supply B Washers C M10 Hanging bolt field supply For PFFY P VCM E mm Model name A B 20 25 32 700 More than 240 40 50 900 More than 240 63 1100 More than 240 A Floor B Piping space C Electrical part service space For PFFY P VCM E mm Model name E F 20 25 32 730 756 40 50 930 956 63 1130 1156 VZ79D813H01_DA book 2 ページ 2018年...

Страница 3: ...nt piping liquid B Refrigerant piping gas C Drain outlet Unit mm B A A Cut here B Remove brazed cap A A Cool by a wet cloth A A E C F B D A Thermal insulation B Pull out insulation C Wrap with damp cloth D Return to original position E Ensure that there is no gap here F Wrap with insulating tape VZ79D813H01_DA book 3 ページ 2018年12月3日 月曜日 午後5時17分 ...

Страница 4: ...xing part D Insertion margin E Drain hose accessory F Drain pipe O D ø32 PVC TUBE field supply G Insulating material field supply Unit mm B D F A G C E A Air inlet B Air filter C Duct D Canvas duct E Access door F Wall G Air outlet B A C A Filter B Front plate C Fan guard A B C C C C D C 220 240V A Ground fault interrupter B Local switch Wiring breaker C Indoor unit D Pull box VZ79D813H01_DA book ...

Страница 5: ...rew holding cover 3pcs B Cover C B A A Terminal bed box B Knockout hole C Remove C H J I D N L N L M1 1 2 M2 S B E A G F A Use a cable tie to secure the cable B Use PG bushing to keep the weight of the cable and external force from being applied to the power supply terminal connector C Power source wiring D Use ordinary bushing E Power source terminal block F Terminal block for indoor transmission...

Страница 6: ...6 8 6 Fig 8 6 1 SW21 SW14 SW12 SW11 Indoor controller board VZ79D813H01_DA book 6 ページ 2018年12月3日 月曜日 午後5時17分 ...

Страница 7: ... away from water washing water etc It might result in electric shock catching fire or smoke Securely install the outdoor unit terminal cover panel If the terminal cover panel is not installed properly dust or water may enter the outdoor unit and fire or electric shock may result Do not use refrigerant other than the type indicated in the manuals pro vided with the unit and on the nameplate Doing s...

Страница 8: ... circuit breaker is not installed electric shock may result Use power line cables of sufficient current carrying capacity and rating Cables that are too small may leak generate heat and cause a fire Use only a circuit breaker and fuse of the specified capacity A fuse or circuit breaker of a larger capacity or a steel or copper wire may result in a general unit failure or fire Do not wash the air c...

Страница 9: ... the unit at level using a level Caution Install the unit in horizontal position If the side with drain port is installed higher water leakage may be caused 5 Refrigerant pipe and drain pipe specifications To avoid dew drops provide sufficient antisweating and insulating work to the refrig erant and drain pipes When using commercially available refrigerant pipes be sure to wind commercially availa...

Страница 10: ...on indoors and keep both ends of the piping sealed until just before brazing If dust dirt or water gets into the refrigerant cycle the oil will deteriorate and the compressor may fail Use Suniso 4GS or 3GS small amount refrigerator oil to coat the flare and flange connection part For models using R22 Use ester oil ether oil or alkylbenzene small amount as the refrigerator oil to coat flares and fl...

Страница 11: ... shall be provided by the Air conditioner installation Fig 8 1 1 P 4 Apply to IEC61000 3 3 about Max Permissive System Impedance 1 The Ground fault interrupter should support Inverter circuit The Ground fault interrupter should combine using of local switch or wiring breaker 2 Please take the larger of F1 or F2 as the value for F0 F1 Total operating maximum current of the indoor units 1 2 F2 V1 Qu...

Страница 12: ...roller Fig 8 2 4 P 5 M NET Remote controller The MA remote controller and the M NET remote controller cannot be used at the same time or interchangeably Caution Install wiring so that it is not tight and under tension Wiring under tension may break or overheat and burn 8 3 Connecting electrical connections Please identify the model name of the operation manual attached on the terminal box cover wi...

Страница 13: ...t addresses and branch numbers at will The determination of indoor unit addresses varies with the system at site Set them referring to the Data Book 8 7 Sensing room temperature with the built in sen sor in a remote controller If you want to sense room temperature with the built in sensor in a remote controller set SW1 1 on the control board to ON The setting of SW1 7 and SW1 8 as nec essary also ...

Страница 14: ...14 en VG79D813H01_en book 14 ページ 2018年12月14日 金曜日 午前11時20分 ...

Страница 15: ...IP20 N 10 R410A 4 15 220 220 230 230 240 240 VZ79D813H01_DA book 171 ページ 2018年12月3日 月曜日 午後5時17分 ...

Страница 16: ...wing EU regulations Low Voltage Directive 2014 35 EU Electromagnetic Compatibility Directive 2014 30 EU Machinery Directive 2006 42 EC Please be sure to put the contact address telephone number on this manual before handing it to the customer HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN VG79D813H01_en book 172 ページ 2018年12月14日 金曜日 午前11時20分 ...

Отзывы: