15
en
9.5. Selecting the external static pressure
Five levels of external static pressure are available for selection.
Set the setting either by using the switches on the control board (SW21-1, SW21-2, and SW21-5) or from the function selection screen on the remote controller.
[Fig. 9.5.1] (P.6)
Notes:
• When the static pressure setting was set from the remote controller, the actual setting and the switch setting on the control board may not match because the
latest setting from the remote controller overrides the previous setting. To check the latest static pressure setting, check it on the remote controller, not on
the switch.
• If the static pressure setting for the duct is lower than that for the unit, the fan of the unit may repeat start/stop, and the outdoor unit may remain in a stopped
state. Match the static pressure settings for the unit to that for the duct.
To set the external static pressure with the switches on the control board
To set the external static pressure from the function selection screen on the remote controller (PAR-33MAA, PAR-40MAA)
Follow the instructions below and the instructions detailed in the remote controller manual for how to set the switches.
1. Set the function setting No. 32 (Switch setting/Function selection) to “2”.
2. Set the function setting No. 8 and No. 10 to appropriate values, according to the external static pressure.
9.6. Setting addresses
(Be sure to operate with the main power turned OFF.)
[Fig. 9.5.1] (P.6)
• There are two types of rotary switch setting available: setting addresses 1 to 9
and over 10, and setting branch numbers.
• The rotary switches are all set to “0” when shipped from the factory. These
switches can be used to set unit addresses and branch numbers at will.
• The determination of indoor unit addresses varies with the system at site. Set
them referring to the Data Book.
9.7. Sensing room temperature with the built-in
sensor in a remote controller
If you want to sense room temperature with the built-in sensor in a remote controller,
set SW1-1 on the control board to “ON”. The setting of SW1-7 and SW1-8 as
necessary also makes it possible to adjust the air flow at a time when the heating
thermometer is OFF.
9.8. Changing the power voltage setting
(Be sure to operate with the main power turned OFF.)
[Fig. 9.5.1] (P.6)
Please set the switch SW21 according to the power voltage.
• Set SW21-6 to OFF side when the power supply is 240 volts.
• When the power supply is 220 and 230 volts, set SW21-6 to ON side.
<Indoor controller board>
External static pressure
SW21-1
SW21-2
SW21-5
Initial setting
M20–M63VMA-A1: 35 Pa
M71–M140VMA-A1: 40 Pa
OFF
OFF OFF
○
only M20–M100VMA-A1
50 Pa
ON
OFF
OFF
○
only M125,M140VMA-A1
70 Pa
OFF
ON
ON
100 Pa
OFF
OFF
ON
150 Pa
ON
OFF
ON
Selection
Function
setting No.
Initial
setting
Current
setting
External static pressure
Function
setting No.
Initial setting
Current
setting
[Important
]
Be sure to write down the
settings for all functions in
the “Current setting” row if
any of the initial settings
has been changed.
No. 32
No. 8
No. 10
Switch setting
1
○
M20–M63VMA-A1: 35 Pa
M71–M140VMA-A1: 40 Pa
2
1
○
only M20–M100VMA-A1
Function selection
2
50 Pa
3
1
○
only M125,M140VMA-A1
70 Pa
1
2
100 Pa
2
2
150 Pa
3
2
<Indoor controller board>
1
How to set addresses
Example: If Address is “3”, remain SW12 (for over 10) at “0”, and match
SW11 (for 1 to 9)
with “3”.
2
How to set branch numbers SW14 (Series R2 only)
The branch number assigned to each indoor unit is the port number of the
BC controller
to which the indoor unit is connected.
Leave it to “0” on the non-R2 series of units.
01_KJ79P971H02_en.book 15 ページ 2022年7月5日 火曜日 午前11時38分