VII
Troubleshooting ]
- 23 -
HWE19070
GB
VII
Troubleshooting
[1] Troubleshooting
1. Check methods
1. Component and check points
(1) Thermistor
Room temperature thermistor (TH21)
Liquid pipe thermistor (TH22)
Gas pipe thermistor (TH23)
Disconnect the connector and measure the resistance between terminals with a tester.
(Ambient temperature 10°C - 30°C)
1) Thermistor characteristic graph
(2) Fan motor (CNMF)
Refer to the page on "DC fan motor (fan motor/indoor control board)."
(3) Linear expansion valve
Disconnect the connector, and measure the resistance between terminals with a tester.
Refer to the next page for details.
Normal
Abnormal
4.3k
Ω
- 9.6k
Ω
Open or short
(Refer to the thermistor characteristic graph below.)
Low-temperature thermistor
Room temperature thermistor (TH21)
Liquid pipe thermistor (TH22)
Gas pipe thermistor (TH23)
Drain sensor (DS)
Thermistor R
0
= 15 k
Ω
±3%
Multiplier of B = 3480 k
Ω
±2%
0°C 15k
Ω
10°C 9.6k
Ω
20°C 6.3k
Ω
25°C 5.2k
Ω
30°C 4.3k
Ω
40°C 3.0k
Ω
(A) Temperature (°C)
(B) Resistance
(k
Ω
)
Normal
Abnormal
1-6
2-6
3-6
4-6
Open or short
White-Red
Yellow-Red
Orange-Red
Blue-Red
(150
Ω
) ±10%
(A)
Red
(E)
Yellow
(C)
Blue
(F)
White
(D)
Orange
Rt = 15 exp { 3480(
) }
1
273+t
1
273
0
10
20
30
40
50
-20 -10 0 10 20 30 40 50
(A)
(B)
1
2
3
4
6
LEV
M
(A)
(C)
(D)
(E)
(F)
CN60
HWE19070.book Page 23 Thursday, September 12, 2019 3:46 PM