5. Miscellaneous Notes

Secure the field-supplied pipes with a pipe cover and a cable tie in place to keep them from coming in contact with other pipes as 
necessary.

WT06205X03 

See reverse.

3. Pipe Connection Example

Connect the pipes between outdoor units, 
referencing the figure below.

1

Low-pressure 

twinning kit

2

High-pressure twinning pipe

Low-pressure connecting pipe 
(field-supplied)

High-pressure connecting pipe 
(field-supplied)

Main high-pressure pipe  
(field-supplied)

Main low-pressure pipe  
(field-supplied)

(6) Pipe connection (high-pressure side)

· Make sure the pipes from the twinning pipe to the outdoor unit are sloped downwards.

· If high-pressure twinning pipe is installed above the base of the outdoor unit, it should be no more than 200 mm [7-7/8 in].

A

B

To BC controller

High-pressure twinning pipe

Total pipe length = A + B < 5 m [16-7/16 ft]

To BC controller

Upward slope

Downward slope

100 mm [3-
15/16 in]  
or more

To  
BC controller

200 mm 
[7-7/8 in]  
max.

High-pressure  
Twinning pipe

Outdoor unit 1

Outdoor unit 2

4. Insulation Cover Installation

Install the insulation cover on the twinning kit after brazing the pipes and twinning kit. 
Insulate all refrigerant pipes. Insulate the high-pressure and low-pressure pipes separately, and pipes located inside the unit as well as 
the outside. Use heat-resistant insulation material (Heat resistant : at least 120°C [248°F], Thickness: high-pressure = 10 mm [13/32 in], 
low-pressure = 20 mm [13/16 in] ). Position the edges of the insulation cover and heat-resistant insulation material so as not to leave a 
gap, and then wrap the exterior perimeter of the pipe joints and middle with tape (field-supplied).

Tape (field-supplied)

Insulation cover

Heat-resistant insulation material (field-supplied)

Tape (field-supplied)

Insulation covers can shrink. 
Overlap the tape as shown in the 
left figure so that there will be no 
gap in between the insulation cover 
or field-installed insulation material.

Heat-resistant insulation material (field-supplied)

Heat-resistant insulation material (field-supplied)

To be gap free

To be gap free

field-supplied pipe

field-supplied pipe

field-supplied pipe

g

Insulation cover

2

High-pressure 

twinning pipe

Overlap margin of the tape

Содержание CITY MULTI CMY-R100XLCBK

Страница 1: ...nents with bare hands during and immediately after operation In the event of a refrigerant leak thoroughly ventilate the room s Improper installation may result in refrigerant gas leakage and equipment damage s If the wrong twinning pipe or wrong size connecting pipe is used air conditioning performance will suffer s If leaked refrigerant comes in contact with a heat source such as a fan heater st...

Страница 2: ... P216 P120 P96 CMY R100XLCBK ø28 58 1 1 8 ø28 58 1 1 8 P240 P120 P120 ø34 93 1 3 8 P264 P144 P120 P288 P144 P144 A1 B1 C1 A2 B2 C2 A3 B3 C3 PURY P96 P120 P144 ø19 05 3 4 ø19 05 3 4 ø22 2 7 8 ø22 2 7 8 ø28 58 1 1 8 ø28 58 1 1 8 Unit mm in Unit mm in 1 Confirming the Package Contents The following items are included with the Twinning Kit CMY R100XLCBK Verify that all items are present before starting...

Страница 3: ...re the slope of the twinning pipes are at an angle within 15 to the horizontal plane If the slope exceeds the specified angle the unit may be damaged Note Refer to the figure below for the installation position of the twinning pipe 5 The length of the straight pipe between indoor units and the twinning pipe high pressure pipe Use the pipes supplied in the twinning kit and make sure the section of th...

Страница 4: ...or unit 1 Outdoor unit 2 4 Insulation Cover Installation Install the insulation cover on the twinning kit after brazing the pipes and twinning kit Insulate all refrigerant pipes Insulate the high pressure and low pressure pipes separately and pipes located inside the unit as well as the outside Use heat resistant insulation material Heat resistant at least 120 C 248 F Thickness high pressure 10 mm...

Отзывы: