background image

3

(2) Routing the pipe through the bottom

(1) Braze item 

7

 high-pressure pipe to the refrigerant service valve so 

that the dimples on the pipe are parallel to the edge of the cutout 
hole. Expand the end of the field-supplied pipes, and braze them to 
item 

7

 high-pressure pipe.

(2) Attach item 

1

 low-pressure twinning kit to the sheet metal of the 

refrigerant service valve with item 

3

 screw, and braze it to the 

refrigerant service valve.

(3) Braze item 

6

 elbow pipe to the field-supplied pipe first, and then 

braze it to item 

1

 low-pressure twinning kit.

(4) Flare the field-supplied pipe end, and braze the pipe to the low-

pressure pipe in the middle.

(5) Wrap the pipe in front of item 

1

 low-pressure twinning kit with item 

9

 pipe cover, and attach compressor cables to item 

9

 pipe cover 

with item 

4

 cable tie to keep them out of direct contact with the 

pipes.

(3) Routing the pipe through the front

(1) Braze item 

8

 high-pressure pipe to the refrigerant service valve.

(2) Attach item 

1

 low-pressure twinning kit to the sheet metal of the 

refrigerant service valve with item 

3

 screw, and braze it to the 

refrigerant service valve.

(3) Braze item 

6

 elbow pipe to the field-supplied pipe first, and then 

braze it to item 

1

 low-pressure twinning kit.

(4) Braze item 

5

 elbow pipe to the low-pressure pipe in the middle.

(5) Wrap the pipe in front of item 

1

 low-pressure twinning kit with item 

9

 pipe cover, and attach compressor cables to item 

9

 pipe cover 

with item 

4

 cable tie to keep them out of direct contact with the 

pipes.

(4) Slope of twinning pipes (high-pressure side only) 

Make sure the slope of the twinning pipes are at an angle 
within ±15˚ to the horizontal plane. 
If the slope exceeds the specified angle, the unit may be 
damaged.

Note. Refer to the figure below for the installation position of the twinning pipe.

(5) The length of the straight pipe between indoor units and the twinning pipe (high-pressure pipe)

Use the pipes supplied in the twinning kit, and make sure the section of the field-supplied pipe that connects to the twinning 
pipe has at least 500 mm [19-11/16 in] of straight section. (The section of the field-supplied pipe that connects to the twinning 
pipe must have at least 500 mm [19-11/16 in] of straight section.) If the straight section is less than 500 mm [19-11/16 in], it 
may result in equipment damage.

· Before heating the pipes, place a wet towel on the refrigerant service 

valve to keep its temperature below 120˚C [248˚F].

· Direct the flame away from the cables and sheet metals inside the unit 

so as not to burn them. 

CAUTION

· Before heating the pipes, place a wet towel on the refrigerant service 

valve to keep its temperature below 120˚C [248˚F].

· Direct the flame away from the cables and sheet metals inside the unit 

so as not to burn them. 

CAUTION

1

3

6

7

Connect the pipe so that the 
dimples on the 

7

 high pressure 

pipe are parallel to the edge of 
the cutout hole.

9

  

Wrap the pipe cover here. 
Attach compressor cables to pipe 
cover with cable tie to keep them 
out of direct contact with the pipes.

Field-supplied pipes

Field-supplied 
pipes

±15

˚

Twinning pipe on the high-pressure side

Slope of the twinning pipe is at an angle within ±15° to the horizontal plane.

Wrap the pipe cover here. 
Attach compressor cables to pipe 
cover with cable tie to keep them 
out of direct contact with the pipes.

1

3

6

5

8

Field-supplied pipes

Содержание CITY MULTI CMY-R100XLCBK

Страница 1: ...nents with bare hands during and immediately after operation In the event of a refrigerant leak thoroughly ventilate the room s Improper installation may result in refrigerant gas leakage and equipment damage s If the wrong twinning pipe or wrong size connecting pipe is used air conditioning performance will suffer s If leaked refrigerant comes in contact with a heat source such as a fan heater st...

Страница 2: ... P216 P120 P96 CMY R100XLCBK ø28 58 1 1 8 ø28 58 1 1 8 P240 P120 P120 ø34 93 1 3 8 P264 P144 P120 P288 P144 P144 A1 B1 C1 A2 B2 C2 A3 B3 C3 PURY P96 P120 P144 ø19 05 3 4 ø19 05 3 4 ø22 2 7 8 ø22 2 7 8 ø28 58 1 1 8 ø28 58 1 1 8 Unit mm in Unit mm in 1 Confirming the Package Contents The following items are included with the Twinning Kit CMY R100XLCBK Verify that all items are present before starting...

Страница 3: ...re the slope of the twinning pipes are at an angle within 15 to the horizontal plane If the slope exceeds the specified angle the unit may be damaged Note Refer to the figure below for the installation position of the twinning pipe 5 The length of the straight pipe between indoor units and the twinning pipe high pressure pipe Use the pipes supplied in the twinning kit and make sure the section of th...

Страница 4: ...or unit 1 Outdoor unit 2 4 Insulation Cover Installation Install the insulation cover on the twinning kit after brazing the pipes and twinning kit Insulate all refrigerant pipes Insulate the high pressure and low pressure pipes separately and pipes located inside the unit as well as the outside Use heat resistant insulation material Heat resistant at least 120 C 248 F Thickness high pressure 10 mm...

Отзывы: