Mitsubishi Electric CITY MULTI CMY-R100NCBK Скачать руководство пользователя страница 3

3

PURY-(E)P264 to (E)P336

Set model

PURY-(E)P264

PURY-(E)P288

PURY-(E)P312

PURY-(E)P336

Set Unit

Unit 1

PURY-(E)P144

PURY-(E)P144

PURY-(E)P168

PURY-(E)P168

Unit 2

PURY-(E)P120

PURY-(E)P144

PURY-(E)P144

PURY-(E)P168

Twinning type

CMY-R300NCBK

Twinning pipe - BC Controller

High-pressure

a

ø28.58 [1-1/8]

Twinning pipe - BC Controller

Low-pressure

b

ø34.93 [1-3/8]

ø41.28 [1-5/8]

Twinning pipe - Outdoor unit

Unit model

High-pressure

Low-pressure

PURY-HP72

ø15.88 [5/8]

ø19.05 [3/4]

PURY-HP/(E)P96

ø19.05 [3/4]

ø22.2 [7/8]

PURY-HP/(E)P120

ø19.05 [3/4]

ø28.58 [1-1/8]

PURY-(E)P144

ø22.2 [7/8]

ø28.58 [1-1/8]

PURY-(E)P168

ø22.2 [7/8]

ø28.58 [1-1/8]

(2)  Slope of twinning pipes

Make sure the slope of the twinning pipes are at an angle 

within ±15˚ to the horizontal plane. 

If the slope exceeds the specified angle, the unit may be 

damaged.

±15

˚

(3)  The length of the straight pipe between indoor units and the twinning pipe 

Use the pipes supplied in the twinning kit, and make sure the section of the field-supplied pipe that connects to the twinning pipe has 

at least 500 mm [19-11/16 in] of straight section. (The section of the field-supplied pipe that connects to the twinning pipe must have 

at least 500 mm [19-11/16 in] of straight section.) If the straight section is less than 500 mm [19-11/16 in], it may result in equipment 

damage.

(4)  Pipe connection

• Make sure the pipes from the twinning pipe to the outdoor unit are sloped downwards.

 

A

B

 

• If twinning pipe is installed above the base of the outdoor unit,  

it should be no more than 200 mm [7-7/8 in].

• If the length of the pipe between the branching point and the outdoor unit exceeds 2 m (6 ft), provide a trap within 2 m (6 ft) from the 

branching point.  

The trap must be at least 200 mm (7-7/8 in) in height. (low-pressure pipe only) If there is no trap, oil can accumulate inside the pipe, 

causing a shortage of oil and may damage the compressor.

*  Small dots in the figures indicate branching points.

Ⓐ 

To indoor units

Ⓑ 

Trap (low-pressure pipe only)

Ⓒ 

High-pressure pipe

Twinning pipe

Slope of the twinning pipe is at an angle within ±15° to the horizontal plane.

100 mm

[3-15/16 in] 

max

Total pipe length = A + B < 5 m [16-7/16 ft]

Unit 2

Upward slope

Unit 1

To BC controller

Downward slope

Twinning pipe

To BC controller

Unit 2

Unit 1

Unit 1

To  

BC controller

Unit 2

Twinning pipe

200 mm

[7-7/8 in] 

max

2 m (6 ft)

≤ 2 m (6 ft)

Содержание CITY MULTI CMY-R100NCBK

Страница 1: ...r wrong size connecting pipe is used air conditioning performance will suffer If leaked refrigerant comes in contact with a heat source such as a fan heater stove or electric grill toxic gases will be generated Improper installation may result in water leakage electric shock or fire Any presence of foreign substance or air can cause abnormal pressure rise or explosion If refrigerant leaks and come...

Страница 2: ...0NCBK High pressure Low pressure OD22 2 7 8 ID28 58 1 1 8 2 OD28 58 1 1 8 ID34 93 1 3 8 CMY R300NCBK High pressure OD19 05 3 4 ID22 2 7 8 2 Low pressure OD34 93 1 3 8 ID41 28 1 5 8 3 List of field supplied parts Refrigerant pipes other than the ones provided in the kit Heat resistant insulation material for field supplied refrigerant pipes Insulation cover tape 2 Selecting the Correct Size Refrige...

Страница 3: ...tion The section of the field supplied pipe that connects to the twinning pipe must have at least 500 mm 19 11 16 in of straight section If the straight section is less than 500 mm 19 11 16 in it may result in equipment damage 4 Pipe connection Make sure the pipes from the twinning pipe to the outdoor unit are sloped downwards A B If twinning pipe is installed above the base of the outdoor unit it...

Страница 4: ...inning kit Insulation cover Tape field supply Tape field supply 5 Miscellaneous Notes Secure the field supplied pipes with a pipe cover and a cable tie in place to keep them from coming in contact with other pipes as necessary The pipe section before the twinning pipe must have at least 500 mm 19 11 16 in of straight section Twinning kit On site piping On site piping Tape field supplied To be gap ...

Отзывы: