1.  Confirming the Package Contents

The following items are included with the Twinning Kit (CMY-R100NCBK, CMY-R200NCBK, CMY-R300NCBK). Verify that all items are 

present before starting installation.
* Always use the twinning pipes included in the kit when preparing the twinning kit. 

If the field-supplied pipes do not fit the parts in the kit, use the accessory piping parts listed below.

Twinning a

Insulation cover

Twinning kit

Pipe b (Before the twinning)

Pipe c (After the twinning)

L-shape pipe d (After the twinning)

(1)  Twinning pipes

Model

Section

Twinning a

Pipe b (Before the 

twinning)

Pipe c (After the 

twinning)

L-shape Pipe d 

(After the twinning) Insulation cover Installation Manual

CMY-R100NCBK

High-pressure

15.88 [5/8] × 15.88 [5/8] × 19.05 [3/4]

-

-

-

Small

1 (This booklet)

Low-pressure

25.4 [1] × 25.4 [1] × 28.58 [1-1/8]

OD28.58 [1-1/8]-

ID28.58 [1-1/8]

OD25.4 [1]- 

ID22.2 [7/8]

OD25.4 [1]- 

ID22.2 [7/8]

Large

CMY-R200NCBK

High-pressure

19.05 [3/4] × 19.05 [3/4] × 22.2 [7/8]

-

-

-

Small

Low-pressure

25.4 [1] × 25.4 [1] × 28.58 [1-1/8]

OD28.58 [1-1/8]-

ID28.58 [1-1/8]

OD25.4 [1]- 

ID22.2 [7/8]

OD25.4 [1]- 

ID22.2 [7/8]

Large

CMY-R300NCBK

High-pressure

19.05 [3/4] × 19.05 [3/4] × 28.58 [1-1/8]

-

-

-

Small

Low-pressure

28.58 [1-1/8] × 28.58 [1-1/8]  

× 31.75 [1-1/4]

OD31.75 [1-1/4]-

ID34.93 [1-3/8]

OD28.58 [1-1/8]-

ID28.58 [1-1/8]

OD28.58 [1-1/8]-

ID28.58 [1-1/8]

Large

(2)  Accessory piping parts

Model

Section

Supplied pipe

CMY-R100NCBK

High-pressure

 OD19.05 [3/4]-ID22.2 [7/8]

-

Low-pressure

 OD22.2 [7/8]-ID19.05 [3/4] (2)

-

CMY-R200NCBK

High-pressure

-

-

Low-pressure

OD22.2 [7/8]-ID28.58 [1-1/8] (2)

OD28.58 [1-1/8]-ID34.93 [1-3/8]

CMY-R300NCBK

High-pressure

 OD19.05 [3/4]-ID22.2 [7/8] (2)

-

Low-pressure

 OD34.93 [1-3/8]-ID41.28 [1-5/8]

-

(3)  List of field-supplied parts

• Refrigerant pipes other than the ones provided in the kit

• Heat-resistant insulation material (for field-supplied refrigerant pipes)

• Insulation cover tape

2.  Selecting the Correct Size Refrigerant Pipes and Using the Twinning Kit

(1)  Pipe size

Field-supply the pipes to be connected to the kit.

Select the correct size pipe referring to the Installation 

manual of the unit model in use or the Databook.

If the pipe was cut with a pipe cutter, remove 

the burrs and eliminate foreign materials before 

connecting.

PURY-HP144 to HP240, (E)P192 to (E)P240

Set model

PURY-HP144

PURY-HP/(E)P192

PURY-(E)P216

PURY-HP/(E)P240

Set Unit

Unit 1

PURY-HP72

PURY-HP/(E)P96

PURY-(E)P120

PURY-HP/(E)P120

Unit 2

PURY-HP72

PURY-HP/(E)P96

PURY-(E)P96

PURY-HP/(E)P120

Twinning type

CMY-R100NCBK

CMY-R200NCBK

Twinning pipe - BC Controller

High-pressure

a

ø22.2 [7/8]

ø22.2 [7/8]*

Twinning pipe - BC Controller

Low-pressure

b

ø28.58 [1-1/8]

ø34.93 [1-3/8]

*  When the high pressure piping length is 65 m (213 ft) or less, use ø22.2 (ø7/8) pipe. 

When the high pressure piping length exceeds 65 m (213 ft), use ø22.2 (ø7/8) pipe until 65 m (213 ft), use ø28.58 (ø1-1/8) pipe for the part that exceeds 65 m (213 ft).

Twinning kit

Pipe b (Before the twinning)

Insulation cover

L-shape pipe d (After the twinning)

Twinning a

Pipe c (After the twinning)

Outdoor unit 2

Outdoor unit 1

To BC controller (Low pressure pipe)

To BC controller (High pressure pipe)

See reverse.

Содержание CITY MULTI CMY-R100NCBK

Страница 1: ...r wrong size connecting pipe is used air conditioning performance will suffer If leaked refrigerant comes in contact with a heat source such as a fan heater stove or electric grill toxic gases will be generated Improper installation may result in water leakage electric shock or fire Any presence of foreign substance or air can cause abnormal pressure rise or explosion If refrigerant leaks and come...

Страница 2: ...0NCBK High pressure Low pressure OD22 2 7 8 ID28 58 1 1 8 2 OD28 58 1 1 8 ID34 93 1 3 8 CMY R300NCBK High pressure OD19 05 3 4 ID22 2 7 8 2 Low pressure OD34 93 1 3 8 ID41 28 1 5 8 3 List of field supplied parts Refrigerant pipes other than the ones provided in the kit Heat resistant insulation material for field supplied refrigerant pipes Insulation cover tape 2 Selecting the Correct Size Refrige...

Страница 3: ...tion The section of the field supplied pipe that connects to the twinning pipe must have at least 500 mm 19 11 16 in of straight section If the straight section is less than 500 mm 19 11 16 in it may result in equipment damage 4 Pipe connection Make sure the pipes from the twinning pipe to the outdoor unit are sloped downwards A B If twinning pipe is installed above the base of the outdoor unit it...

Страница 4: ...inning kit Insulation cover Tape field supply Tape field supply 5 Miscellaneous Notes Secure the field supplied pipes with a pipe cover and a cable tie in place to keep them from coming in contact with other pipes as necessary The pipe section before the twinning pipe must have at least 500 mm 19 11 16 in of straight section Twinning kit On site piping On site piping Tape field supplied To be gap ...

Отзывы: