5. Miscellaneous Notes

Secure the field-supplied pipes with a pipe cover and a cable tie in place to keep them from coming in contact with other pipes as 
necessary.

WT07685X01 

See reverse.

4. Insulation Cover Installation

Install the insulation cover on the twinning kit after brazing the pipes and twinning kit. 
Insulate all refrigerant pipes. Insulate the high-pressure and low-pressure pipes separately, and pipes located inside the unit as well as 
the outside. Use heat-resistant insulation material (Heat resistant : at least 120°C [248°F], Thickness: high-pressure = 10 mm [13/32 in], 
low-pressure = 20 mm [13/16 in] ). Position the edges of the insulation cover and heat-resistant insulation material so as not to leave a 
gap, and then wrap the exterior perimeter of the pipe joints and middle with tape (field-supplied).

3. Pipe Connection Example

Connect the pipes between outdoor units, referencing 
the figure below.

1

Low-pressure twinning kit

2

High-pressure twinning pipe

Low-pressure connecting pipe 
(field-supplied)

High-pressure connecting pipe 
(field-supplied)

Main high-pressure pipe (field-supplied)

Main low-pressure pipe (field-supplied)

Tape (field-supplied)

Insulation cover

Heat-resistant insulation material (field-supplied)

Tape (field-supplied)

Insulation covers can shrink. 
Overlap the tape as shown in the 
left figure so that there will be no 
gap in between the insulation cover 
or field-installed insulation material.

(6) The length of the straight pipe between indoor units and the twinning pipe (high-pressure pipe)

Use the pipes supplied in the twinning kit, and make sure the section of the field-supplied pipe that connects to the twinning 
pipe has at least 500 mm [19-11/16 in] of straight section. (The section of the field-supplied pipe that connects to the twinning 
pipe must have at least 500 mm [19-11/16 in] of straight section.) If the straight section is less than 500 mm [19-11/16 in], it 
may result in equipment damage.

(7) Pipe connection (high-pressure side)

· Make sure the pipes from the twinning pipe to the outdoor unit are sloped downwards.

A

B

To BC controller

High-pressure twinning pipe

Total pipe length = A + B < 5 m [16-7/16 ft]

· If high-pressure twinning pipe is installed above the base of 

the outdoor unit, it should be no more than 200 mm [7-7/8 in].

To BC controller

To  
BC controller

Upward slope

Downward slope

100 mm 
[3-15/16 in]  
or more

200 mm 
[7-7/8 in]  
max.

High-pressure  
twinning pipe

Outdoor unit 1

Outdoor unit 2

Heat-resistant insulation material (field-supplied)

Heat-resistant insulation material (field-supplied)

To be gap free

To be gap free

field-supplied pipe

field-supplied pipe

field-supplied pipe

h

Insulation cover

2

High-pressure 

twinning pipe

Overlap margin of the tape

Содержание CITY MULTI CMY-ER100CBK

Страница 1: ...ents with bare hands during and immediately after operation In the event of a refrigerant leak thoroughly ventilate the room s Improper installation may result in refrigerant gas leakage and equipment damage s If the wrong twinning pipe or wrong size connecting pipe is used air conditioning performance will suffer s If leaked refrigerant comes in contact with a heat source such as a fan heater sto...

Страница 2: ...llowing items are included with the Twinning Kit CMY ER100CBK Verify that all items are present before starting installation Always use the twinning pipes included in the kit when preparing the twinning kit If the field supplied pipes do not fit the parts in the kit use the accessory piping parts listed below 1 Package contents Model 1 Low pressure twinning kit 2 High pressure twinning pipe 3 Fixing...

Страница 3: ... it to item 1 low pressure twinning kit 4 Braze item 4 elbow pipe to the low pressure pipe in the middle 5 Wrap the pipe in front of item 1 low pressure twinning kit with item 8 pipe cover and attach compressor cables to item 8 pipe cover with item e cable tie to keep them out of direct contact with the pipes 5 Slope of twinning pipes high pressure side only Make sure the slope of the twinning pip...

Страница 4: ...lation covers can shrink Overlap the tape as shown in the left figure so that there will be no gap in between the insulation cover or field installed insulation material 6 The length of the straight pipe between indoor units and the twinning pipe high pressure pipe Use the pipes supplied in the twinning kit and make sure the section of the field supplied pipe that connects to the twinning pipe has at...

Отзывы: