2

2. Selecting the Correct Size Refrigerant Pipes and Using the Twinning Kit

(1) Pipe size

1

 Field-supply the pipes to be connected to the kit.

2

 Select the correct size pipe referring to the outline diagram of 

the unit model in use or the Databook.

3

 If the pipe was cut with a pipe cutter, remove the burrs and 

eliminate foreign materials before connecting.

* On the low-pressure side, the twinning kit connects to the field-

supplied pipes inside the outdoor unit. 
The distributor on the low-pressure side must be placed in the 
outdoor unit that has a larger capacity index of the two, regardless 
of the relative positions of the outdoor units or their addresses. 
If the distributor is placed in the outdoor unit that has a smaller 
capacity, refrigerant will not be properly distributed and compressor 
failure may result. 
(If outdoor units that have the same capacity are used in 
combination, the distributor can be placed in either outdoor unit.)

(2) Before installing low-pressure twinning kit

Outdoor unit 1

Outdoor unit 2

To BC controller

To BC controller

Twinning pipe (high pressure)

1. Confirming the Package Contents

The following items are included with the Twinning Kit (CMY-ER100CBK). Verify that all items are present before starting installation.

* Always use the twinning pipes included in the kit when preparing the twinning kit. 

If the field-supplied pipes do not fit the parts in the kit, use the accessory piping parts listed below.

(1) Package contents

Model

1

 Low-pressure 

twinning kit

2

 High-pressure 

twinning pipe

3

 Fixing screw

4

 Elbow pipe 

ø22.2 [7/8]

5

 Elbow pipe 

ø28.58 [1-1/8]

6

 High-pressure 

pipe (for routing 

through the bottom)

7

 High-pressure 

pipe (for routing 

through the front)

8

 Pipe cover

9

 OD22.2 [7/8] 

-ID19.05 [3/4]

0

 OD19.05 [3/4] 

-ID22.2 [7/8]

CMY-ER100CBK

1

1

1

1

1

1

1

1

1

1

Model

a

 OD15.88 [5/8] 

-ID19.05 [3/4]

b

 OD19.05 [3/4] 

-ID15.88 [5/8]

c

 Installation 

Manual  

(this booklet)

d

 Insulation 

cover

e

 Cable tie

Buffer

g

 Saddle

h

 Fixing plate

i

 Packing

CMY-ER100CBK

1

3

1

1

2

1

1

1

1

(2) List of field-supplied parts

· Refrigerant pipes other than the ones provided in the kit.
· Heat-resistant insulation material (for field-supplied refrigerant pipes)
· Insulation cover tape

Twinning Kit (low pressure)

 

See reverse.

Attach buffer 

f

 to the side of the 

compressor cover, keeping the low-pressure 
twinning kit 

1

 out of contact with the cover. 

Attach the buffer in the correct position 
along the bottom of the compressor cover 
and the edge of the rubber bush.

Содержание CITY MULTI CMY-ER100CBK

Страница 1: ...ents with bare hands during and immediately after operation In the event of a refrigerant leak thoroughly ventilate the room s Improper installation may result in refrigerant gas leakage and equipment damage s If the wrong twinning pipe or wrong size connecting pipe is used air conditioning performance will suffer s If leaked refrigerant comes in contact with a heat source such as a fan heater sto...

Страница 2: ...llowing items are included with the Twinning Kit CMY ER100CBK Verify that all items are present before starting installation Always use the twinning pipes included in the kit when preparing the twinning kit If the field supplied pipes do not fit the parts in the kit use the accessory piping parts listed below 1 Package contents Model 1 Low pressure twinning kit 2 High pressure twinning pipe 3 Fixing...

Страница 3: ... it to item 1 low pressure twinning kit 4 Braze item 4 elbow pipe to the low pressure pipe in the middle 5 Wrap the pipe in front of item 1 low pressure twinning kit with item 8 pipe cover and attach compressor cables to item 8 pipe cover with item e cable tie to keep them out of direct contact with the pipes 5 Slope of twinning pipes high pressure side only Make sure the slope of the twinning pip...

Страница 4: ...lation covers can shrink Overlap the tape as shown in the left figure so that there will be no gap in between the insulation cover or field installed insulation material 6 The length of the straight pipe between indoor units and the twinning pipe high pressure pipe Use the pipes supplied in the twinning kit and make sure the section of the field supplied pipe that connects to the twinning pipe has at...

Отзывы: