2. When stacking on a rack
(This is a reference view showing the least installation space.)
[Fig. 2.2.2] (P.2)
Model name
A
CMB-P104V-G
648
CMB-P105V-G
648
CMB-P106V-G
648
CMB-P108V-G
648
CMB-P1010V-G
648
CMB-P1013V-G
1098
CMB-P1016V-G
1098
A
On the side of outdoor unit piping
B
On the side of indoor unit piping
2.3. Checking the installation site
Check that the difference of elevation between indoor and outdoor units and the
length of refrigerant piping are within the following limitations.
[Fig. 2.3.1] (P.2)
A
Outdoor unit
B
BC controller
C
Indoor unit
D
More than 81
E
Less than H=50 m (when the outdoor unit is higher than the indoor unit)
F
Less than H1=40 m (when the outdoor unit is lower than the indoor unit)
G
Branch pipe (for Y Series) CMY-Y102S-G
H
Combined pipe (CMY-R160-J: optional)
I
Less than 110 m
J
Less than 40 m
K
Up to three units for 1 branch hole
Total capacity: less than 140 (but same in cooling/heating mode)
L
Less than h1=15 m (10 m or less for 200, 250 unit type)
M
Less than h2=15 m
Notes:
*1 Please refer to the figure “Allowable Pipe Length” below when the total
piping length exceeds 300 m.
*2 Please refer to the figure “Distance between BC controller and farthest
indoor unit” when the distance between BC controller and farthest in-
door unit exceeds 40 m.
*3 10 m or less, with indoor units with model numbers of 200, 250.
3. Installing BC controller
3.1. Checking the accessories with BC con-
troller
The following items are supplied with each BC controller.
Item
Qty
1
Drain hose
1
2
Tie band
1
3
Hose band
1
4
Reducer (large & small)
Same number as
branch holes
5
Refrigerant connection pipe
3
3.2. Installing BC controllers
Installing hanging bolts
Install locally procured hanging bolts (all screws) following the procedure given in
the figure. The hanging bolt size is ø10 (M10 screw).
To hang the unit, use a lifting machine to lift and pass it through the hanging bolts.
[Fig. 3.2.1] (P.2)
1
Hanging method
2
Installing-on-the-floor method
A: Min.30 mm
A
Hanging bolt ø10 (field supply)
B
Nut (field supply)
C
Washer (field supply)
D
Double nuts (field supply)
E
Anchor bolt M10 (field supply)
s
Be sure to install the BC controllers level. Installing obliquely may cause
a risk of drain leakage. Use a level to check the unit’s level. If it is oblique,
loosen the fixing nut and make an adjustment.
Caution:
Be sure to install the unit body level.
4. Connecting refrigerant pipes and drain pipes
4.1. Connecting refrigerant pipes
1. Connect the liquid and gas pipes of each indoor unit to the same (correct) end
connection numbers as indicated on the indoor unit flare connection section of
each BC controller. If connected to wrong end connection numbers, there will
be no normal operation.
2. List indoor unit model names in the name plate on the BC controller control
box (for identification purposes), and BC controller end connection numbers
and address numbers in the name plate on the indoor unit side.
3. If the number of connected indoor units is less than the number of branch
holes, it does not matter which end connections you leave.
Seal unused end connections using flare nuts with end caps just as they were
capped when shipped from the factory. No end cap will lead to refrigerant leak-
age.
4. When using branch pipes (CMY-Y102S-G), be sure to connect them level.
5. Be sure to tighten the flare nuts using a double spanner. Otherwise the refrig-
erant may leak.
6. Be sure to use non-oxidative brazing where necessary. If you do not use non-
oxidative brazing, it may clog the pipes.
7. After completing pipe connection, support the pipes to ensure that load is not
imparted to the BC controller’s end connections (particularly to the gas pipes
of indoor units).
Warning :
When installing and moving the unit, do not charge it with refrigerant other
than the refrigerant (R410A) specified on the unit.
- Mixing of a different refrigerant, air, etc. may cause the refrigerant cycle to mal-
function and result in severe damage.
Caution:
•
Use refrigerant piping made of C1220 (Cu-DHP) phosphorus deoxidized
copper as specified in the JIS H3300 “Copper and copper alloy seamless
pipes and tubes”. In addition, be sure that the inner and outer surfaces of
the pipes are clean and free of hazardous sulphur, oxides, dust/dirt, shav-
ing particles, oils, moisture, or any other contaminant.
Length
(Unit: m)
Item
Piping portion
Allowable value
Total piping length
A+B+a+b
Below 300*1
+c+d+e
Longest piping length
A+e
Below 150
Between outdoor unit and
A
Below 110
BC controller
(Below 60)*1
Between indoor units and BC controller
e
Below 40
Above outdoor unit
H
Below 50
Below outdoor unit
H1
Below 40
Between indoor units and BC controller
h1
Below 15
(Below 10)*3
Between indoor units
h2
Below 15
(Below 10)*3
Diff
erence of ele
v
ation
Between
indoor and
outdoor unit
Distance between BC controller
and farthest indoor unit
Allowable pipe length
Height difference between
BC controller and farthest
indoor unit (m)
15
10
5
20
10
0
0
Distance between BC contoroller
and farthest indoor unit (m)
110
100
90
80
70
70
60
60
50
50
40
40
30
30
Distance between outdoor
unit and BC controller (m)
400
350
300
250
200
Allowable pipe length (m)
Содержание CITY MULTI CMB-P-V-G Series
Страница 90: ...MEMO ...
Страница 91: ......