2
<A> Top view
<B> Front view
A
Inspection hole
B
On the side of outdoor unit piping
C
Control box
D
On the side of indoor unit piping
*1 Dimensions with which pipe connection can be handled at site
A
Outdoor unit
B
BC controller
C
Indoor unit
D
More than 81
E
Less than H=50 m (when the outdoor unit is higher than the indoor unit)
F
Less than H1=40 m (when the outdoor unit is lower than the indoor unit)
G
Branch pipe (for Y Series) CMY-Y102S-G
H
Combined pipe (CMY-R160-J: optional)
I
Less than 110 m
J
Less than 40 m
K
Up to three units for 1 branch hole
Total capacity: less than 140 (but same in cooling/heating mode)
L
Less than h1=15 m (10 m or less for 200, 250 unit type)
M
Less than h2=15 m
Notes:
*1 Please refer to the figure “Allowable Pipe Length” below when the total
piping length exceeds 300 m.
*2 Please refer to the figure “Distance between BC controller and farthest
indoor unit” when the distance between BC controller and farthest in-
door unit exceeds 40 m.
*3 10 m or less, with indoor units with model numbers of 200, 250.
2
[Fig. 2.1.1]
[Fig. 2.2.1]
3
3.2
[Fig. 3.2.1]
[Fig. 2.3.1]
2.2
2.1
Model name
A
CMB-P104V-G
648
CMB-P105V-G
648
CMB-P106V-G
648
CMB-P108V-G
648
CMB-P1010V-G
648
CMB-P1013V-G
1098
CMB-P1016V-G
1098
C
C
D
C
C
K
C
F
A
B
I
J
H
G
E
L
M
A
B
c
d
e
b
a
H
H1
h1
h2
1
A
C
B
D
A
2
C
B
E
D
1
Hanging method
2
Installing-on-the-floor method
A: Min.30 mm
A
Hanging bolt ø10 (field supply)
B
Nut (field supply)
C
Washer (field supply)
D
Double nuts (field supply)
E
Anchor bolt M10 (field supply)
Model name
A
CMB-P104V-G
648
CMB-P105V-G
648
CMB-P106V-G
648
CMB-P108V-G
648
CMB-P1010V-G
648
CMB-P1013V-G
1098
CMB-P1016V-G
1098
A
On the side of outdoor unit piping
B
On the side of indoor unit piping
2.3
INDOOR UNIT SIDE
100
450
200
A
64
200
250
700
*1
<B>
<A>
B
B
A
D
C
A
500
77
77
118
362
53
B
A
B
A
[Fig. 2.2.2]
Distance between BC controller
and farthest indoor unit
Allowable pipe length
Height difference between
BC controller and farthest
indoor unit (m)
15
10
5
20
10
0
0
Distance between BC contoroller
and farthest indoor unit (m)
110
100
90
80
70
70
60
60
50
50
40
40
30
30
Distance between outdoor
unit and BC controller (m)
400
350
300
250
200
Allowable pipe length (m)
Length
(Unit: m)
Item
Piping portion
Allowable value
Total piping length
A+B+a+b
Below 300*1
+c+d+e
Longest piping length
A+e
Below 150
Between outdoor unit and
A
Below 110
BC controller
(Below 60)*1
Between indoor units and BC controller
e
Below 40
Above outdoor unit
H
Below 50
Below outdoor unit
H1
Below 40
Between indoor units and BC controller
h1
Below 15
(Below 10)*3
Between indoor units
h2
Below 15
(Below 10)*3
Diff
erence of ele
v
ation
Between
indoor and
outdoor units