7 FUNCTIONS
7.1 IO-Link Master Functions
Precautions
If the following ISDU data is written using the RIWT instruction of the program, upload to the IO-Link device is executed even
if the IO-Link module has parameter setting data.
To upload data without using the RIWT instruction, set "Data storage setting" to "Clear" to delete the parameter setting data in
the IO-Link module.
To enable the IO-Link device setting automatic upload/download function, set the device validation setting to "Compatible" or
"Identical".
[Upload setting of the IO-Link device (ISDU data write)]
*1 For details on the settings, refer to the IO-Link specifications (IO-Link Interface and System Specification V1.1.2).
(www.io-link.com/)
Item
Description
Access code
30H
Attribute code
05H
Address code
00H to 07H (each channel number)
Data size
6 bytes
Data
• Index: 0002H
• Subindex: 00H
• Control data: 80H
• Request data: 05H