BC29
B
ATTERY
C
ABINET
4/16/2014
12
755-00087 R03
6.
S
YSTEM
S
PECIFICATIONS
6.1
B
ATTERIES
Please refer to system drawings for model specific information.
Type:
Valve Regulated Lead Acid (VRLA), sealed, non-spillable
Voltage:
12 VDC Nominal
6.2
S
YSTEM
G
ROUNDING
Cabinet Safety Ground:
Each cabinet is supplied with a mechanical ground lug that accepts bare
wire from #14 AWG to 1/0 AWG.
Torque:
Wire Size
Rated Torque
1/0 - #3 AWG
50 IN. LBS.
#4 - #6 AWG
45 IN. LBS.
#8 AWG
40 IN. LBS.
#10 - #14 AWG
35 IN. LBS.
Wire Size and Type:
Ground wire should be sized per NEC and/or all applicable national and
local codes.
Battery Cabinet Breaker or Fuse Size
Minimum Copper Ground Wire Size
Up to 200 amps
6 AWG
201-300 amps
4 AWG
301-400 amps
3 AWG
401-500 amps
2 AWG
501-600 amps
1 AWG
6.3
DC
O
UTPUT
Please refer to system drawings for model specific information.
Voltage:
12-480 VDC Nominal
Circuit Breaker:
UL Listed 600 VDC rated. See system drawings for details.
Fuse Type:
A50QS, A50P or equivalent (for 384VDC Nom. bus or less)
A70QS, A70P or equal (for 480VDC Nom. bus or less)
Type HSJ
Only cabinets with
Flame Retardant Batteries
are suitable for computer room
use.
All system ground wires should be derived from the main building ground source.
Содержание C&C Power BC29
Страница 2: ...4 16 2014 2 755 00087 R03 ...
Страница 4: ...4 16 2014 4 755 00087 R03 ...
Страница 19: ...BC29 BATTERY CABINET 4 16 2014 19 755 00087 R03 9 REFERENCE MATERIALS ...
Страница 20: ...BC29 BATTERY CABINET 4 16 2014 20 755 00087 R03 ...
Страница 21: ...BC29 BATTERY CABINET 4 16 2014 21 755 00087 R03 ...
Страница 23: ...C C Power Inc 395 Mission Street Carol Stream IL 60188 Phone 630 617 9022 www ccpower com ...