background image

– 7 –

1-7. Using external input/output

1. External signal input (CN2)

*To use external input, an external input/output adapter (PAC-YT51HAA; sold separately) is required.

(1) External signal input

Using external dry contact signals, the following operation of all air conditioning units can be controlled from the AT-50B: Emergency stop/Normal 
operation, ON/OFF, Permit/Prohibit local remote controller operation. These settings are made on the External Input Settings on the Initial Settings 
screen that is accessible from the Service Menu. (Refer to section 2-3.)

(2) Level signal and pulse signal

(A) Level signal

(B) Pulse signal

(3) External input specifications

(A) Level signal

• If [Emergency stop (Level signal)] is selected, the air conditioning units in normal operation will stop when the contact turns on. Conversely, 

the units that are stopped will resume normal operation when the contact turns off. The units must be started up manually after the 
emergency stop is reset.

• If [ON/OFF (Level signal)] is selected, the air conditioning units that are stopped will start operation when the contact turns on. Conversely, 

the units that are in operation will stop when the contact turns off.

(B) Pulse signal

• If the incoming signal is the same as the signal that is currently being received, no status change will occur. 
• If local remote controller operation is prohibited, ON/OFF, operation mode, set temperature, filter sign reset, fan speed, and air direction 

settings will be prohibited, and also timer (schedule) settings from the local remote controllers will be deactivated. Depending on the models 
of the connected air conditioning units and remote controllers, operation of some of the items above may not be disabled.

• The ON-signal pulse width should be set to a value between 0.2 and 1 seconds.

Mode

External input setting

Notes

1

Not used (Factory setting)

Select this mode when not using an external signal input function.

2

Emergency Stop (Level signal)

Using a level signal, all the air conditioning units will be stopped collectively in an 
emergency. During an emergency stop, the ON/OFF operation from the local remote 
controllers will be prohibited, and the ON/OFF operation and Prohibit/Permit settings on 
the AT-50B will be prohibited. Scheduled operation will not be performed. 

3

ON/OFF (Level signal)

Using a level signal, all the air conditioning units will be run or stopped collectively. The 
ON/OFF operation from the local remote controllers will be prohibited, and the ON/OFF 
operation and Prohibit/Permit settings on the AT-50B will be prohibited. Scheduled 
operation will not be performed. 

4

ON/OFF/Prohibit/Permit (Pulse signal)

Using a pulse signal, all the air conditioning units will be run or stopped collectively, or the 
operation from the local remote controllers will be prohibited or permitted collectively. 

CN2

Lead wire

Emergency Stop (Level signal)

ON/OFF (Level signal)

ON/OFF/Prohibit/Permit 

(Pulse signal)

1

Green

Built-in 5 VDC power for external input 
* Exclusively for use with external input. Not usable for other purposes.

2

Yellow

Emergency stop/Normal operation 
signal input

ON/OFF signal input

ON signal input

3

Orange

Not used

Not used

OFF signal input

4

Red

Not used

Not used

Prohibit-local-remote-controller-
operation signal input

5

Brown

Not used

Not used

Permit-local-remote-controller-
operation signal input

*Same for Prohibit/Permit remote controller operation.

Contact ON

Contact OFF

Contact ON
Contact OFF

Contact ON

Contact OFF

Contact ON
Contact OFF

Run

Stop

Stop

Run

Stop

Stop

(ex.)ON/OFF

Signal 1 (ON)

Signal 2 (OFF)

0.2 to 1 seconds

0.2 to 1 seconds

Normal 

operation

Normal 

operation

Emergency 

stop

WT06990X04_GB.book  7 ページ  2018年5月22日 火曜日 午後1時55分

Содержание AT-50B

Страница 1: ...ts with wet hands To reduce the risk of injury or electric shock before spraying a chemical around the controller stop the operation and cover the controller To reduce the risk of injury or electric shock stop the operation and switch off the power supply before cleaning maintaining or inspecting the controller Properly install all required covers to keep moisture and dust out of the controller Du...

Страница 2: ...cables and cable access holes with putty The controller should be repaired or moved only by qualified personnel Do not disassemble or modify the controller Improper installation or repair may cause injury electric shock or fire To reduce the risk of shorting electric shock fire or malfunction do not touch the circuit board with tools or with your hands and do not allow dust to accumulate on the ci...

Страница 3: ...ual 1 2 Mounting bracket 1 AT 50B Power lamp Display screen Touch panel For connection to the M NET A B Terminal for connection to the M NET transmission cable non polarized External output adapter cable access hole External input adapter cable access hole Controller cover mounting screw SD memory slot for program updates TB7 TB3 ME MA MA R2 TB7 TB3 MA MA 051 001 106 006 007 008 009 010 056 057 00...

Страница 4: ... as for the indoor units apply An M NET interface sold separately is required 1 50 M NET remote controller Assign an address that equals the address of the main indoor unit with the lowest address in the group plus 100 Add 150 instead of 100 to set a sub remote controller 101 200 Sub system controller Assign an address that equals the lowest number of the group to be controlled plus 200 201 250 DI...

Страница 5: ... the controller Have extra cables to extend these cables as necessary To install the controller according to the instructions provided in sections a and b 1 above Include an extra 30 cm 12 in of cable to provide adequate slack in the cable Remove the sheath on the M NET transmission cable up to 20 cm 8 in from the end To install the controller according to the instructions provided in section b 2 ...

Страница 6: ...transmission cable is non polarized Insert the cables in the groove on the controller so they will not be pinched when the cover is installed To route the cable along the wall surface Secure the cables in place with a cable cover and seal the gap between the cable cover and the controller with putty 5 Replace the cover Snap the cover into place and attach it to the controller with a screw at the b...

Страница 7: ...set to a value between 0 2 and 1 seconds Mode External input setting Notes 1 Not used Factory setting Select this mode when not using an external signal input function 2 Emergency Stop Level signal Using a level signal all the air conditioning units will be stopped collectively in an emergency During an emergency stop the ON OFF operation from the local remote controllers will be prohibited and th...

Страница 8: ... extension cables are field supplied Note External output of the AT 50B is a dry contact Select an external power supply suitable for the relays used 12 VDC or 24 VDC To prevent malfunction connect the external power supply to the input circuit with the correct polarity CN2 X1 AT 50B X1 1 2 3 4 5 Maximum 10 m 32 ft Field supplied Yellow Green ON OFF or Emergency stop X1 X2 Y1 Y2 CN2 X1 AT 50B X2 Y...

Страница 9: ...B and 2GB SD memory cards by SanDisk are supported Parts Model Usage Note External input output adapter PAC YT51HAA Enables the use of external input output function Required to use the external input output function 5 wire cable input 4 wire cable output SD Logo is a trademark of SD 3C LLC a b c a Remove the SD memory card slot cover from the controller b Insert the SD memory card into the slot u...

Страница 10: ... only or both remote controllers and sub system controllers Access to ON OFF Mode Set Temp Filter Reset Air Direction Fan Speed Timer and Check Water sign Air To Water PWFY 13 External input mode Selects the external input mode 13 Filter sign Displays or suppresses the filter sign on the HOME screen 13 Dry mode Includes or excludes Dry mode as an option for the operation mode 13 Operation mode con...

Страница 11: ...GRID zoom out view GRID zoom in view LIST view GROUP view Main Menu screen Login Page screen 1 Password Change screen Service Menu Service Menu screen Initial Settings 1 Basic System Initial Settings 2 Groups Groups Interlocked LOSSNAY Delete All System View Malfunction Log Gas Amount Check Maintenance Test Run Software update Button name Main Menu Service Menu Password Change Return HOME Cancel L...

Страница 12: ... communication g The message shown above will appear on the screen displaying the initialization progress When initialization is complete the screen will automatically return to the HOME screen Initialization will take up to five minutes To change settings later perform a test run or verify the maintenance information 1 Touch Main Menu button on the HOME screen 2 Touch Service Menu button on the M...

Страница 13: ...ohibition Setting on the AT 50B The factory setting is Enabled Remote controller access setting 1 Touch the button labeled 4 in the figure to switch between SC RC and RC Only Select SC RC to prohibit access from both the system controllers and remote controllers and select RC Only to prohibit access from only the remote controllers The factory setting is RC Only Access to ON OFF Mode Set Temp Filt...

Страница 14: ...ing functions Saving the settings 1 Touch the Save button to save the settings 2 2 Group settings This setting can be made only when AT 50B is set as a main controller If AT 50B is set as a sub controller the setting can be monitored only Enter the group settings on the Groups screen air conditioning units general equipment and their respective group names that are connected to AT 50B Touch Initia...

Страница 15: ...n be assigned to each group Do not assign a system controller that does not support Air To Water PWFY to Air To Water PWFY group which may result in unit malfunction 5 After all the settings have been made touch the Save button Group settings for general equipment 1 Touch the model selection button labeled 2 in the figure to access the Model selection screen Touch the model selection button labele...

Страница 16: ...ked indoor unit button labeled 2 in the figure On the popup window that appears check the address of the indoor units to be interlocked with the ventilation units Up to 16 indoor units can be assigned to each ventilation unit 3 After all interlocked operation settings have been made touch the Save button 2 4 Batch deletion Available only when AT 50B is set as a main controller To delete all group ...

Страница 17: ... is Air To Water PWFY group 2 Operation mode Touch this button to switch the operation mode 3 Pipe temperature 1 The pipe temperature of the unit with the lowest address in a given group will appear 4 Advanced settings Touch this button for advanced settings 1 The water temperature will appear if the group is Air To Water PWFY group The water temperature to be displayed depends on which temperatur...

Страница 18: ...utes to 1 hour and check results will be displayed upon completion When the amount of refrigerant charge is normal Normal will appear on the screen and if the outdoor units are low on refrigerant due to leaks Lo will appear It is not necessary to keep this page open until checking is completed Even if the screen is closed the check results and the log will be displayed next time this page is opene...

Страница 19: ...he popup message to begin the update process 6 The lit LEDs on the three buttons F1 F2 and Collective ON OFF will indicate a successful completion of the update While update is in progress the LEDs on the F1 and F2 buttons will alternately blink Consult your dealer if the update is not completed in 10 minutes 7 After the update has been completed turn the DIP switch 4 to OFF to restart the AT 50B ...

Страница 20: ...ions Electromagnetic Compatibility Directive 2014 30 EU Restriction of Hazardous Substances 2011 65 EU HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN MANUFACTURER MITSUBISHI ELECTRIC CORPORATION Air conditioning Refrigeration Systems Works 5 66 Tebira 6 Chome Wakayama city 640 8686 Japan WT06990X04_GB book 20 ページ 2018年5月22日 火曜日 午後1時55分 ...

Отзывы: