Air Handling Unit Interface
AHU-KIT-SP
MORIKAWA
SPECIFICATION
PSZ000Z308
22/38
MODEL NAME
MODEL TYPE
ISSUE
CLASSIFICATION
DWG NO.
REV.MARK PAGE
21.09.17
●
Input register
・
The following table shows the input registers (read only, 2-byte data).
Data address
Item
Initial
Range
Units
Notes
0
:
Stop
1
:
Run
0
:
Cooling
1
:
Heating
30003
Set temperature display
46(23
℃
) 0
~
65535
0.5
℃
/count
18
~
30
℃
0
:
Remote
1
:
Center/Remote
2
:
Center
0
:
Emergency stop release
1
:
Emergency stop
30007
Return air temperature (Master)
0
-32768
~
32767
0.1
℃
/count
30008
External temperature (Master)
-640
-32768
~
32767
0.1
℃
/count
30009
Request capacity
0
0
~
65535
1 %/count
X_all
0
0
1
0
30006
Emergency stop display
0
~
65535
-
30004
Center/Remote display
0
~
65535
-
30001
System Run/Stop display
0
~
65535
-
30002
Operation mode display
0
~
65535
-
[Data address 30003 set temperature display example]
<0.5
℃
/count>
18=9
℃
36=18
℃
50=25
℃
60=30
℃
[Data address 30007 return air temperature display example]
<0.1
℃
/count>
10=1
℃
30=3
℃
500=50
℃
600=60
℃