11
5
Closing method
10
Product Specification
4
Product Specification
Type
AED630-CV
AED1000-CV
AED1250-CV
AED1600-CV
Number of poles
3, 4
Rated insulation voltage (V)
Ui
1000
Impulse withstand voltage (kV)
Uimp
12
Rated operational voltage (V AC 50/60 Hz)
Ue
500
Suitability for isolation
IEC 60947-2
Yes
Pollution degree
IEC 60664-1
3
Environmental condition for EMC
IEC 60947-2
A
Circuit breaker as per IEC 60947-2
Rating of neutral pole (A)
630
1000
1250
1600
Sensor ratings (A)
630
1000
1250
1600
Rated current setting Ir (A)
at 40°C
General use
(Rated current adjustable)
0.5 to 1.0 × In, 0.05 step
315-346.5-378-
409.5-441-472.5-
504-535.5-567-
598.5-630
500-550-600-650-
700-750-800-850-
900-950-1000
625-687.5-750-
812.5-875-937.5-
1000-1062.5-1125-
1187.5-1250
800-880-960-
1040-1120-1200-
1280-1360-1440-
1520-1600
Utilization category
B
Ultimate breaking capacity (kA rms)
50/60 Hz (Note 1) (Note 7)
Icu
240-500 V AC
50
Rated service breaking capacity (kA rms)
Ics
% Icu
100%
Rated short-time withstand current (kA rms)
50/60 Hz
Icw
1 s
50
3 s
36
Rated making capacity (kA peak)
50/60 Hz
Icm
240-500 V AC
105
Breaking time between tripping order and arc extinction (ms)
40 (Note 2)
Closing time (ms)
300
Switch-disconnector as per IEC 60947-3 (Note 8)
Operational current AC-23A
630
1000
1250
1600
Rated making capacity (kA peak)
50/60 Hz
Icm
240-500 V AC
52.5
Rated short-time withstand current (kA rms) Icw
1 s
50
3 s
36
Maintenance/Connection/Installation
Service life (Note 4)
Mechanical
with regular ordinary
maintenance prescribed by the
manufacturer
10000 (Note 3)
Electrical
with regular ordinary
maintenance
prescribed by the
manufacturer
240-500
V AC
6000
Connection (Note 5)
Horizontal
Available
Vertical
Available
Front
Available
Dimensions (mm) (H × W × D)
Fixed
3-pole
410 × 340 × 290
4-pole
410 × 425 × 290
Drawout
3-pole
430 × 300 × 375
4-pole
430 × 385 × 375
Weight (kg) (without accessories)
(Note 6)
Fixed
3-pole
37
4-pole
43
Drawout
3-pole
57
4-pole
66
Reverse connection
Possible
Note 1) The MCR is equipped as standard.
Note 2) This value indicates the operating time for the O operation at the time of short circuit interruption. (For the CO operation, the value is 135 ms.) For the product with a UVT, refer to page 16.
Note 3) The mechanical service life includes the electrical service life.
Note 4) This is a guide of the service life when the regular maintenance specified by the manufacturer is performed. Regular maintenance means inspection, grease lubrication, as-needed replacement of
prescribed component and so on.
Note 5) For the details on the connection method of terminals, refer to Available connections (on page 14).
Note 6) This weight indicates the weight of product with a electronic trip relay, which does not include other accessories. The values in the table are typical values and are not guaranteed values.
Note 7) When the breaker without a trip relay (BARE) and the external OCR for general purpose are used, the breaking capacity is 25 kA.
Note 8) AED-CV complying with IEC 60947-3 will be launched in 2021.
Closing method
The breaker closes electrically.
The following describes the closing methods.
1. The breaker closes by pressing the ON button.
2. The breaker closes electrically by remote operation
and opens by pressing the OFF button.
•
The indicator shows the ON or OFF state of the main contacts.
•
The breaker cannot be closed while the OFF button is being pressed. (Safety design)
•
OFF lock is enabled by padlock (Refer to page 12, 20) as standard.
Solenoid mechanism
Note) The voltage is required to apply to the control circuit terminal block. The rated value and circuit diagram are shown below.
Note) In consideration of the voltage drop, set the power supply capacity for the solenoid not to be less than the operating voltage.
Rated voltage (V)
Applicable
voltage range (V)
Applied voltage (V)
Current
(Peak value) (A)
Operating time (s)
Criterion for power
requirement
AC
(50/60 Hz)
110-125
93.5-137.5
110
6.5
≤ 0.3
1000 VA
125
7.7
220-250
187-275
220
3.3
250
3.9
DC
110-125
93.5-137.5
110
7.1
1000 W
125
8.4
220-250
187-275
220
3.5
250
4.2
ACB (solenoid) control rating
Breaker
Solenoid
coil
ON
button
Close to ON
(less than 10 m)
A2
S1
A1
S2
Solenoid
controller
Standard controller diagram