18
19
Accessories
8
8
Accessories
1
2
3
4
Cell switch
Shorting b contact (Rear side)
Safety shutter
Safety shutter lock
This is the switch to show the drawout position (CONNECTED, TEST, and
DISCONNECTED) of the breaker. An arbitrary combination up to 4 pieces is available.
Cell switch (CL)
Option
Voltage (V)
Current (A)
Resistive load
Inductive load
AC
(50/60 Hz)
250
10
10
125
DC
250
3
1.5
125
10
6
30
10
10
Contacts max.
Total 4c max.
Switch rating
Standard pattern
Operating sequence
Drawout position of breaker
Disconnected
Connected
Display position of
drawout operation
TEST
CONNECT
CL-C
(CONNECTED)
CL-T
(TEST)
CL-D
(DISCONNECTED)
Sw
itch
fu
nc
tio
n
Cha
ng
e-
ove
r s
eq
ue
nc
e
(a
c
on
ta
ct
)
OFF
OFF
OFF
ON
ON
ON
Note) The setting can be changed by customers later.
A preliminary setting of CL at factory shipment is as follows.
CL1: 1C, CL2: 1C1D, CL3: 1C1T1D, CL4: 2C1T1D
CL-C
CL-T
CL-D
CL1
1
–
–
CL2
1
–
1
CL3
1
1
1
CL4
2
1
1
1
5
Mis-insertion preventor
For drawout type
When moving the breaker from the connected position to the test positions,
this contact is used to short-circuit the auxiliary switch (LAXb), thus maintaining the
correct sequence of operation of the external control circuit. When ordering, SBC with
the same number of contacts as auxiliary switches (LAXb) will be provided. Up to 5
SBCs can be mounted.
Shorting b contact (SBC)
Option
Operating sequence
Main circuit
Disconnected
Connected
Display position of
drawout operation
TEST
CONNECT
Change-over sequence
of SBC
(b contact)
ON
OFF
2
This device enhances the interphase insulation between the terminals of the
breaker, and prevents short-circuit due to conductive objects or dust.
It can be attached and detached easily. The interphase insulation is available for all
connection methods.
Interphase barrier (BA)
Option
The transparent terminal cover prevents users from careless touching to the
live control terminals.
International Protection is IP20 (IEC 60947-1 Annex C). The terminal cover is available
for both the fixed type breakers and the drawout type breakers.
Terminal cover (TTC)
Option
The dust cover prevents the dust or water from entering into the panel board
due to the breaker panel cut.
Protection degree is IP54. DUC can be locked by the padlock. (The padlock should be
supplied by the customer.) For the suitable size of the padlock, refer to page 20. Consult
us for details.
Dust cover (DUC)
Option
DISCONNECT
DISCONNECT