Appendix
21
• To use the inverter of FR-A820-01250(22K) or lower and FR-A840-00620(22K) or lower (IP20) outside of an enclosure in the environment of pollution
degree 2, fix a fan cover with fan cover fixing screws enclosed.
• On the input and output of the inverter, use cables of the type and size set forth in EN 60204-1, IEC 60364-5-52.
• The operating capacity of the relay outputs (terminal symbols A1, B1, C1, A2, B2 and C2) should be 30 VDC, 0.3 A. (Relay output has basic isolation from
the inverter internal circuit.)
• Control circuit terminals on
are safely isolated from the main circuit.
• Environment (For the detail, refer to
For the installation at an altitude above 1000 m, consider a 3% reduction in the rated current per 500 m increase in altitude.
Branch circuit protection
Class T, Class J, Class CC, or Class L fuses, or UL 489 Molded Case Circuit Breaker (MCCB) must be provided.
For the FR-A820 series, Class T, Class J, or Class CC fuses, or UL 489 Molded Case Circuit Breaker (MCCB) must be provided.
(Use a product which conforms to the EN or IEC Standard.)
Maximum allowable rating by US National Electrical Code. Exact size must be chosen for each installation.
Short circuit ratings
• 200 V class
Suitable for use in a circuit capable of delivering not more than 100 kA rms symmetrical amperes, 240 V maximum.
• 400 V class
Suitable for use in a circuit capable of delivering not more than 100 kA rms symmetrical amperes, 500 V maximum.
During operation
In storage
During transportation
Surrounding air temperature
LD, ND (initial setting), HD: -10 to +50°C
SLD: -10 to +40°C
-20 to +65°C
-20 to +65°C
Ambient humidity
95% RH or less
95% RH or less
95% RH or less
Maximum altitude
2500 m
2500 m
10000 m
FR-A820-[ ]-GN
00046
(0.4K)
00077
(0.75K)
00105
(1.5K)
00167
(2.2K)
00250
(3.7K)
00340
(5.5K)
00490
(7.5K)
00630
(11K)
00770
(15K)
Rated fuse voltage (V)
240 V or more
Fuse allowable
rating (A)
Without power
factor improving
reactor
15
20
30
40
60
80
150
175
200
With power factor
improving reactor
15
20
20
30
50
70
125
150
200
Molded case circuit breaker (MCCB)
Maximum allowable rating (A)
15
15
25
40
60
80
110
150
190
FR-A820-[ ]-GN
00930
(18.5K)
01250
(22K)
01540
(30K)
01870
(37K)
02330
(45K)
03160
(55K)
03800
(75K)
04750
(90K)
Rated fuse voltage (V)
240 V or more
Fuse allowable
rating (A)
Without power
factor improving
reactor
225
300
350
400
500
500
―
―
With power factor
improving reactor
200
250
300
350
400
500
600
700
Molded case circuit breaker (MCCB)
Maximum allowable rating (A)
225
300
350
450
500
700
900
1000
FR-A840-[ ]-GN
00023
(0.4K)
00038
(0.75K)
00052
(1.5K)
00083
(2.2K)
00126
(3.7K)
00170
(5.5K)
00250
(7.5K)
00310
(11K)
00380
(15K)
00470
(18.5K)
00620
(22K)
00770
(30K)
Rated fuse voltage (V)
500 V or more
Fuse allowable
rating (A)
Without power
factor improving
reactor
6
10
15
20
30
40
70
80
90
110
150
175
With power factor
improving reactor
6
10
10
15
25
35
60
70
90
100
125
150
Molded case circuit breaker (MCCB)
Maximum allowable rating (A)
15
15
15
20
30
40
60
70
90
100
150
175
FR-A840-[ ]-GN
00930
(37K)
01160
(45K)
01800
(55K)
02160
(75K)
02600
(90K)
03250
(110K)
03610
(132K)
04320
(160K)
04810
(185K)
05470
(220K)
06100
(250K)
06830
(280K)
Rated fuse voltage (V)
500 V or more
Fuse allowable
rating (A)
Without power
factor improving
reactor
200
250
300
―
―
―
―
―
―
―
―
―
With power factor
improving reactor
175
200
250
300
350
400
500
600
700
800
900
1000
Molded case circuit breaker (MCCB)
Maximum allowable rating (A)
225
250
450
450
500
―
―
―
―
―
―
―
Fan cover
Fan cover
fixing screw
Fan
Fan cover
fixing screw
Fan cover
Fan
FR-A820-00105(1.5K) to 00250(3.7K)
FR-A840-00083(2.2K), 00126(3.7K)
FR-A820-00340(5.5K) to 00250(22K)
FR-A840-00170(5.5K) to 00620(22K)