MITSUBISHI ELECTRIC 9900D SERIES UPS
9900D SERIES UPS
OWNERS / TECHNICAL MANUAL
Page Number:
3-5
B) Minimum clearance required for ventilation
Right side
25 mm (1 inch) (not required when sidecars are used)
Left side
25 mm (1 inch) (not required when sidecars are used)
Back side
0.0 mm (0 inch)
Top side
610 mm (24 inches) (for air flow)
C) Space requirement for routine maintenance
Allow for the following space at the time of installation.
Front
1075 mm (42 inches)
Sides
0.0 mm (0 inch)
Back side
0.0 mm (0 inch)
Top side
610 mm (24 inches)
EXTERNAL BATTERY SUPPLY
Please refer to the following when installing and maintaining batteries:
1. The customer shall refer to the battery manufacturer's installation manual for battery
installation and maintenance instructions.
2. The maximum permitted fault current from the remote battery supply, and the DC
voltage rating of the battery supply over-current protective device are shown in Table
3.3.
Table 3.2
Maximum Permitted Fault Current
UPS Capacity
(kVA)
DC Voltage
Rating (V)
Maximum Fault
Current Permitted (A)
1200
480
25,000
1250
480
25,000
1500
480
25,000
1600
480
25,000
2000
480
25,000