MITSUBISHI ELECTRIC 9900D SERIES UPS
9900D SERIES UPS
OWNERS / TECHNICAL MANUAL
Page Number:
2-11
Terminals 17 to 18
"Total Alarm" contact (OUT8)
Activated during major fault, minor fault and alarm events.
Terminals 19 to 20
"52C Close" contact
Activated when the inverter output contactor 52C has closed.
The UPS is equipped with a selectable output contact feature, and above items are the default
settings. Table 2.1 shows the selectable items for output contacts.
Table 2.1
Selectable Items for Output Contacts
No.
Output Item
Default
0 NONE
1 TOTAL ALARM
OUT8
2 MINOR FAULT
3 ALARM
4 AC INPUT ABNORMAL
5 BYPASS ABNORMAL
6 BATTERY ABNORMAL
7 BATTERY LOW VOL.1
8 BATTERY LOW VOL.2
OUT5
9 BATTERY DEPLETION
10 OVERLOAD
OUT6
11 OVERLOAD PREALARM
12 FAULT GROUP 1
13 FAULT GROUP 2
14 BYPS.SYNCHRONOUS
15 BYPS.ASYNCHRONOUS
16 REMOTE OPE.ENABLE
17 LOAD ON INVERTER
OUT2
18 LOAD ON BYPASS
OUT1
19 LOAD ON AC
20 BATTERY OPERATION
OUT3
21 CONVERTER OPERATION
OUT4
22 INVERTER OPERATION
23 CB1 CLOSE
24 CB2 CLOSE
25 52S CLOSE
26 POWER DEMAND ON
27 EQUALIZING CHARGE
28 ANOTHER BUS SYNC.OK
29 SPARE 29
30 SPARE 30
31 SPARE 31
Contact MITSUBISHI ELECTRIC POWER PRODUCTS, INC for Detailed
information.
!
NOTE