MITSUBISHI ELECTRIC 9900B SERIES UPS
MITSUBISHI
ELECTRIC
9900B SERIES UPS
OWNERS / TECHNICAL MANUAL
Page Number:
3-1
3.0 INSTALLATION AND OPERATION
3.1 TRANSPORTATION AND INSTALLATION
Table 3.1
How to Transport and Install the System
Transportation
Installation
Transport unit with forklift.
Carry with overhead crane using
provided screw-eyebolts.
Using the pre-drilled four holes in the UPS
channel base, anchor the unit using appropriate
hardware (not provided).
CAUTION:
Do not transport in a horizontal position. Cabinets must be
maintained upright /- 15
°
of the vertical during handling.
3.2 INSTALLATION PROCEDURE
A) Note the load tolerance of the floor
Refer to Table 3.2 for list of UPS weights.
Table 3.2
List of UPS Weights
UPS Capacity (kVA)
300
500
750
Weight (lb.)
2,250
3,570
4,255
B) Minimum clearance required for ventilation:
Right side
25 mm (1 inch) (not required when sidecars are used)
Left side
25 mm (1 inch) (not required when sidecars are used)
Back side
0.0 mm (0 inch)
Top side
600 mm (24 inches) (for air flow)