Table 1.5
Detail of Specifications
▲
Rated Output kVA
300
500
750
Rated Output kW
300
500
750
AC INPUT
Configuration
3 phase, 3 wire
Voltage
480 V
+15% to -20%
Frequency
60 Hz +/-10%
Reflected Current THD
3% max. at 100% load
5% max. at 50% load
STATIC BYPASS INPUT
Configuration
3 phase, 3 wire
Voltage
480 V
+/-10%
Frequency
60 Hz +/-5%
BATTERY
Type
Lead Acid
Ride Through
Application Specific
Nominal Voltage
480 Vdc
Minimum Voltage
400 Vdc
Number of Cells
240
AC OUTPUT
Configuration
3 phase, 3 wire
Voltage
480 V
Voltage Stability
+/-1%
Frequency
60 Hz
Frequency Stability
+/-0.01% in free running mode
Power Factor
Unity (nominal)
Power Factor Range
0.7 lagging to 0.8 leading
Voltage THD
2% maximum THD at 100% linear load
5% maximum THD at 100% non-linear load
Transient Response
+/-2% maximum at 100% load step
+/-1% maximum at loss/return of AC power
+/-5% maximum at load transfer to/from static bypass
Transient Recovery
Less than 20ms
Voltage Unbalance
2% maximum at 100% unbalanced load
Voltage Phase Angle
Displacement
+/-1deg. maximum at 100% load
Inverter Overload*
105% to 109% for 1-hour duration
110% to 124% for 10-minute duration
125% to 149% for 1-minute duration
System Overload
(with bypass available)
1000% for 1 cycle
500% for 1 cycle
ENVIRONMENTAL
Cooling
Forced Air
Operating Temperature
41
゚
F to 95
゚
F ( 5
゚
C to 35
゚
C).
Recommended : 68
゚
F to 77
゚
F ( 20
゚
C to 25
゚
C)
Relative Humidity
5% ~ 85% Non-Condensing
Altitude
Operating altitude: Sea Level to 2250 meter (7400ft)
Location
Indoor (free from corrosive gases and dust)
Paint Color
Munsell 5Y7/1 (Beige)
*Voltage regulation maintained
▲
For other stored energy systems, refer to the attached supplement.