Basic operation procedure (External operation)
86
4.3
Basic operation procedure (External
operation)
POINT
POINT
• Where is the frequency command source?
- The frequency set in the frequency setting mode of the operation panel
→
Refer to 4.3.1. (Refer to
- Switches (multi-speed setting)
→
Refer to 4.3.2. (Refer to
- Voltage input signals
→
Refer to 4.3.3. (Refer to
- Current input signals
→
Refer to 4.3.5. (Refer to
4.3.1
Using the frequency set by the operation panel
POINT
POINT
• Switch ON the STF (STR) signal to give a start command.
• Use the operation panel (
) to give a start command.
• Set
Pr.79
="3" (External/PU combined operation mode 1).
[Connection diagram]
NOTE
• When both the forward rotation switch (STF) and the reverse rotation switch (STR) are ON, the motor cannot be started. If
both are turned ON while the inverter is running, the inverter decelerates to a stop.
•
Pr.178 STF terminal function selection
must be set to "60" (or
Pr.179 STR terminal function selection
must be set to
"61"). (All are initial values.)
• Setting
Pr.79 Operation mode selection
="3" also enables multi-speed operation.
• If stopped using
on the operation panel during the External operation, the inverter enters the PU stop status.
([PS] appears on the operation panel.)
To reset the PU stop status, turn OFF the start switch (STF or STR), and then press
. (Refer to
Operation example
Operate at 30 Hz.
Operation
1.
Changing the operation mode
Set "3" in
Pr.79
. [PU+E] indicator is on.
2.
Setting the frequency
Turn
to until the target frequency, "30.00 Hz", appears.
Press [SET] to enter the frequency. "Completed" flickers.
3.
Start
→
acceleration
→
constant speed
Turn ON the start switch (STF or STR). The frequency value on the indication increases in
Pr.7 Acceleration time,
and
"30.00 Hz" appears. [FWD] indicator is on during the forward rotation, and [REV] indicator is on during the reverse rotation.
(To change the set frequency, perform the operation in above step 2. The previously set frequency appears.)
4.
Deceleration
→
stop
Turn OFF the start switch (STF or STR). The frequency value on the indication decreases in
Pr.8 Deceleration time,
and
the motor stops rotating with "0.00 Hz" displayed.
Inverter
Operation panel
SD
STF
STR
Forward rotation
start
Reverse rotation
start