(H) Protective function parameter
329
5
GROUP
H
5.10.8
Limiting the output frequency (maximum/
minimum frequency)
For the FR-A860-01080 or lower.
For the FR-A860-01440 or higher.
Setting the maximum frequency (Pr.1, Pr.18)
• Set
Pr.1 Maximum frequency
to the upper limit of the output frequency. If the value of the frequency command entered is
higher than the setting, the output frequency is clamped at the maximum frequency.
• To operate at a frequency higher than the 120 Hz, adjust the upper output frequency limit with
Pr.18 High speed maximum
frequency
. (When setting a frequency in
Pr.18
, the
Pr.1
setting automatically changes to the frequency set in
Pr.18
. Also,
when setting a frequency in
Pr.1
, the
Pr.18
setting automatically changes to the frequency set in
Pr.1
.)
Setting the minimum frequency (Pr.2)
• Set
Pr.2 Minimum frequency
to the lower limit of the output frequency.
• If the set frequency is
Pr.2
or less, the output frequency is clamped at
Pr.2
(will not fall below
Pr.2
).
NOTE
• To operate with a frequency higher than 60 Hz using frequency-setting analog signals, change the
Pr.125 (Pr.126)
(frequency setting gain) setting.
Simply changing the
Pr.1 and Pr.18
settings does not enable operation at a frequency
higher than 60 Hz.
• During Real sensorless vector control, vector control, and PM sensorless vector control, the upper and lower limits are for the
commanded frequency.
• When
Pr.15 Jog frequency
setting is equal to or less than
Pr.2
setting, the
Pr.15
setting has precedence over the
Pr.2
setting.
• If a jump frequency that exceeds
Pr.1(Pr.18) Maximum frequency
is set for the 3-point frequency jump, the maximum
frequency setting is the set frequency. If the set frequency is less than the jump frequency
Pr.2
Minimum frequency
, the
jump frequency is the set frequency. (The set frequency can be equal to or lower than the frequency lower limit.) When stall
prevention is activated to decrease the output frequency, the output frequency may drop to
Pr.2
or below.
???????
Parameters referred to
Pr.13 Starting frequency
Pr.15 Jog frequency
Pr.125 Terminal 2 frequency setting gain frequency, Pr.126 Terminal 4 frequency setting gain frequency
Motor speed can be limited. Clamp the output frequency at the upper and lower limits.
Pr.
Name
Initial value
Setting range
Description
1
H400
Maximum frequency
120 Hz
0 to 120 Hz
Set the upper limit of the output frequency.
60 Hz
2
H401
Minimum frequency
0 Hz
0 to 120 Hz
Set the lower limit of the output frequency.
18
H402
High speed maximum frequency
120 Hz
0 to 590 Hz
Set when operating at 120 Hz or higher.
60 Hz
CAUTION
Note that when Pr.2 is set to any value equal to or higher than Pr.13 Starting frequency, simply
turning ON the start signal will run the motor at the frequency set in Pr.2 even if the command
frequency is not input.
Output frequency
(Hz)
Pr.1
Pr.18
Pr.2
Frequency setting
Clamped at the
maximum frequency
Clamped at the
minimum frequency
5, 10V
(20mA)
0
(4mA)