Selection of operation mode and
operation location
(8) Switch-over mode (Setting "6")
⋅
While continuing operation, you can switch among PU operation, External operation and Network operation (when
RS-485 terminals or communication option is used).
(9) PU operation interlock (Setting "7")
⋅
The PU operation interlock function is designed to forcibly change the operation mode to External operation mode
when the PU operation interlock signal (X12) input turns OFF. This function prevents the inverter from being
inoperative by the external command if the mode is accidentally left unswitched from the PU operation mode.
⋅
Set "7" (PU operation interlock) in
Pr. 79
.
⋅
For the terminal used for X12 signal (PU operation interlock signal) input, set "12" in any of
Pr. 178 to Pr. 189 (input
terminal function selection)
to assign the function. (Refer to
page 122
for
Pr. 178 to Pr. 189
.)
⋅
When the X 12 signal has not been assigned, the function of the MRS signal switches from MRS (output stop) to
the PU operation interlock signal.
<Function/operation changed by switching ON/OFF the X12 (MRS) signal>
Operation Mode Switching
Switching Operation/Operating Status
External operation
→
PU
operation
Select the PU operation mode with the operation panel or parameter unit.
⋅
Rotation direction is the same as that of external operation.
⋅
The frequency set with the potentiometer (frequency setting command), etc. is used unchanged. (Note
that the setting will disappear when power is switched OFF or the inverter is reset.)
External operation
→
NET
operation
Send the mode change command to Network operation mode through communication.
⋅
Rotation direction is the same as that of external operation.
⋅
The value set with the setting potentiometer (frequency setting command) or like is used unchanged.
(Note that the setting will disappear when power is switched OFF or the inverter is reset.)
PU operation
→
external
operation
Press the external operation key of the operation panel, parameter unit.
⋅
The rotation direction is determined by the input signal of the external operation.
⋅
The set frequency is determined by the external frequency command signal.
PU operation
→
NET
operation
Send the mode change command to Network operation mode through communication.
⋅
Rotation direction and set frequency are the same as those of PU operation.
NET operation
→
external
operation
Send the mode change command to External operation mode through communication.
⋅
Rotation direction is determined by the external operation input signal.
⋅
The set frequency is determined by the external frequency command signal.
NET operation
→
PU
operation
Select the PU operation mode with the operation panel or parameter unit.
⋅
The rotation direction and frequency command in Network operation mode are used unchanged.
X12 (MRS)
Signal
Function/Operation
Operation mode
Parameter write
ON
Operation mode (external, PU, NET) switching
enabled
Output stop during external operation
Parameter write enabled (
Pr. 77 Parameter write
selection
, depending on the corresponding parameter
write condition (
for the parameter list))
OFF
Forcibly switched to External operation mode
External operation allowed.
Switching to PU or NET operation mode disabled
Parameter write disabled with exception of
Pr. 79
Operating Condition
X12 (MRS)
Signal
Operation
Mode
Operating Status
Switching to
PU, NET
Operation Mode
Operation
mode
Status
PU/NET
During stop ON
→
OFF
*1
External
*2
If external operation frequency setting and start signal
are entered, operation is performed in that status.
Disallowed
Running
ON
→
OFF
*1
Disallowed
External
During stop
OFF
→
ON
External
*2
During stop
Enable
ON
→
OFF
Disallowed
Running
OFF
→
ON
During operation
→
output stop
Disallowed
ON
→
OFF
Output stop
→
operation
Disallowed
*1
The operation mode switches to External operation mode independently of whether the start signal (STF, STR) is ON or OFF. Therefore,
the motor is run in External operation mode when the X12 (MRS) signal is turned OFF with either of STF and STR ON.
*2
At fault occurrence, pressing
of the operation panel resets the inverter.
CAUTION
⋅
If the X12 (MRS) signal is ON, the operation mode cannot be switched to PU operation mode when the start signal (STF, STR) is ON.
⋅
When the MRS signal is used as the PU interlock signal, the MRS signal serves as the normal MRS function (output stop) by
turning on the MRS signal and then changing the
Pr. 79
value to other than "7" in the PU operation mode. Also as soon as "7"
is set in
Pr. 79
, the signal acts as the PU interlock signal.
⋅
When the MRS signal is used as the PU operation interlock signal, the logic of the signal is as set in
Pr. 17
. When
Pr. 17
= "2",
read ON as OFF and OFF as ON in the above explanation.
⋅
Changing the terminal assignment using
Pr. 178 to Pr. 189 (input terminal function selection)
may affect the other functions. Please
set parameters after confirming the function of each terminal.