3.0 INSTALLATION AND OPERATION
3.1 Transportation and Installation
TABLE 3.1
How to transport and install the system
Transportation
Installation
Transport unit with forklift.
Carry with overhead crane using
eyebolts provided.
Using the pre drilled holes (4 - 24) in the
UPS channel base, anchor the unit using
appropriate hardware. (Not provided)
Note :
Do not transport in a horizontal position. Cabinets must be maintained
upright /- 15° of the vertical during handling
.
3.2 Installation Procedure
A) Note the load tolerance of the floor
Refer to Table 3.2 for list of UPS weights.
TABLE 3.2
List of UPS weights
UPS Capacity (kVA)
30
50
80
Weight (lb)
2060
1810
1990
B) Minimum clearance required for ventilation
Right side
1.0" (25 mm) (not required when sidecars are used)
Left side
1.0" (25 mm) (not required when sidecars are used)
Back side
0.0" (0.0 mm)
Top side
23.6" (600 mm) (for air flow)
C) Space requirement for routine maintenance
Allow for the following space at the time of installation.
Front
39.4" (1000 mm)
Sides
0.0" (0.0 mm)
Rear
0.0" (0.0 mm)