5.2.2 Precautions for wiring Version 1.10 compatible CC-Link dedicated
cable
(1) Precautions for wiring
(a) Usage of CC-Link cables
The Version 1.10 compatible CC-Link cable cannot be used together
with other CC-Link cables (CC-Link dedicated cable and CC-Link
dedicated high-performance cable)
When used together, normal data communication cannot be expected.
(b) Branching of CC-Link cable
Connect network modules only with CC-Link cables.
Repeater hubs and connectors cannot be used.
(c) Grounding of CC-Link cable
Ground both ends of the shielded wire of the Version 1.10 compatible
CC-Link dedicated cable to the protective ground conductor by
connecting to "SLD" of each network module via "FG".
The SLD and FG are connected within the module.
(d) Connecting a terminating resistor
For the network module at both ends, connect the DA and DB by a
terminating resister (110 , 1/2W) provided with the module.
(e) Connecting/disconnecting Version 1.10 compatible CC-Link dedicated
cable
Shut off all phases of the external power supply for the system.
(2) Connection of cable
(a) Connection method
Connect a blue, white, and yellow cable to the DA, DB, and (DG)
respectively.
In addition, use terminating resistors for the stations at both ends.
DA
DB
(DG)
SLD
FG
DA
DB
FG
SLD
DA
DB
FG
SLD
Version 1.10
compatible CC-Link
dedicated cable
(DG)
(DG)
Terminating
resistor
(110 , 1/2W)
Terminating
resistor
(110 , 1/2W)
Version 1.10
compatible CC-Link
dedicated cable
(blue)
(White)
(Yellow)
(b) Wiring to spring clamp terminal block
For the wiring method of a cable to a spring clamp terminal block, refer
to Section 5.1.2 (2)(b) in this manual.