8
Y Type Water Filter
Malfunctions and Solutions
1. Cooling water used in the system should be
soft and clean. Filter collects the sediment
and other particles in the water passing
through the pipes to prevent possible
damage to the device.
2. Dirty and clogged filter prevents the device
from working properly and the temperature
rises above the optimal value. It should be
cleaned periodically.
3. Filter slot is opened as shown in the picture
to remove and clean the filter.
Malfunction
Cause
Solution
Pump rotates in the wrong
direction.
Phase connections are faulty.
Change phase connections.
Even though the main switch is
on, the machine does not run.
1. Pump key is OFF.
2. Fuse switch is tripped
1. Turn the pump key ON.
2. Switch the fuse switch to the
ON position.
Temperature does not increase
properly.
1. Temperature controller is broken.
2. TC sensor is broken.
3. Electric valve is broken.
4. Heater is broken
1. Replace with new.
2. Replace with new.
3. Replace with new.
4. Replace with new.
Pump and resistance do not work.
System sounds an audible warning. 1. Missing oil or water
1. Check the system for leaks.
2. Add oil or water to the system.
“OVERLOAD” light is on.
1. Blocked pipeline
2. Low voltage
3. Broken pump
1. Clean the pipeline
2. Stabilize the voltage
3. Replace the pump
Draining system does not work.
1. Magnetic valve is broken.
1. Repair or replace with new.
The coolant pressure should be 2 bars. It should not be higher than 5 bars
at any given moment.
Y type filter ensures the cooling capacity of the device is efficient given
that it is cleaned frequently.
This sign indicates the direction of rotation of the pump. When the direction of
rotation of the pump is reversed, the phase reversal lamp lights up and sounds an
audible warning. When the phases are This sign indicates the direction of rotation
of the pump. When the direction of rotation of the pump is reversed, the phase
reversal lamp lights up and sounds an audible warning. When the phases are This
sign indicates the direction of rotation of the pump. When the direction of rotation
of the pump is reversed, the phase reversal lamp lights up and sounds an audible
warning. When the phases are
High Voltage
Operator must take caution.
Warning!!!
It is a general-purpose warning and caution should be exercised.