6
◦ Battery current limit
•
Six user defined General Purpose Inputs (“GPIPs”) which can be software configured as either digital or analogue inputs*
(up to 10 may be made available under special circumstances)
•
Six relay outputs*
5.5.
Rectifier Modules
6.
Installations
WARNING - All upstream AC, Load and Battery breakers must be switched OFF prior to installation. The
system must be completely de-powered.
All circuit breakers in a Newmar power system must be in their OFF position prior to installation.
WARNING - Use extreme care when fitting batteries & their connections. Remove all
conductive materials from yourself such as watches, jewelry, and rings prior to commencing the
installation. DO NOT short terminals when working on them.
CAUTION - Avoid resting cables on sharp edges (cold-creep)
The energy manager contains static sensitive components that require careful handling and proper
precautions to be taken. A grounding strap should be worn.
6.1.
Unpacking and Installing in Frame
Upon unpacking, check that the unit is not damaged, and that you have the required number of rectifiers.
Remove the transport bracket supplied attached to the top of the system.
The unit fits into a standard 19” rack. Use the mounting hardware (#12-24 or #10-32) provided with the rack.
Please note the complete system weight is 12.3 lbs. Ensure the 19” mounting rails can withstand mounting of the system. The
supplied transport bracket can be utilized in cabinets with 19” mounts at the rear of the cabinet to increase the system
mounting rigidity if required.
6.2.
AC Cabling
The AC cables are clearly labelled at the rear of the system (see Fig 3). The AC cable provided is 14AWG cables and a
115 VAC/20 Amp NEMA 5-20 plug is fitted.
AC connection internally is via .25” QC tabs. Longer cables can be easily fitted by replacing the existing cable. Ensure that
the AC color coding is correct for the country of fitment:
Status LEDs
Lock/Unlock
Fan Cooled
Содержание NEWMAR Sentinel
Страница 26: ...25 2 Avoid Tee d Connections ...