67
7.6.2
Connecting to a 3G4010 Interface Device in Canada
A typical connection is shown in Figure 22. The PCS-100 Passive Communications Interface
Board (sold separately) is required.
For information on Compatible Receivers see Appendix A - Compatible Receivers on page 76.
Figure 22 Connecting an FX-401 FACP to a 3G4010 Interface Device in Canada
Note:
The DSC interface device 3G4010 is required if the installation requires ULC
S559 certification.
ALARM
RELAY
SPV
RELAY
TRBL
RELAY
Telephone
Line A
Connection
DC IN
EOL
To GSM/GPRS
Typical Installation in Canada
Line 2
Line 1
PCS-100
P
O
W
E
R
2
4
V
G
N
D
P
G
M
4
G
N
D
1
4V
NC
C
O
M
N
O
T
B
L
R
E
L
AY
J
W
1
PGM4
AUX SUPPLY
+
-
Internet
Computer
Printer
SUR-GARD
SYSTEM IV
Internal IP : X.X.X.X
External IP : X.X.X.X
SG-Systems
Console 2.1
Default Gateway : X.X.X.X
Sub-Net Mask:X.X.X.X
Port #: YYYY (UDP)
NO
C
NO
C
NO
C
COM
Z3
Z2
Z1
T
1
R
1
(-)
(+)
FX-401
3G4010 TRBL
Addressable module
configured as 3G4010
radio trouble
3G4010
C.O.
C.O.
FX-401 - 3G4010 Connection - Typical Diagram
Router
- All units must be installed in the same room
- All extended wiring must be in metallic conduit
- Wiring between FACP and 3G4010: 18 m max.
Contact DSC to reprogram the zone inputs to match
the FACP as shown in this diagram
-
i